Chapter 2. SPECIFICATIONS
2 - 8
2.5.3 Relations between Offset/ Gain Value and Analog Output
The resolution of D/A conversion module can be changed by changing offset/ gain value. At the change of
offset/ gain value, the below formula can calculate resolution of analog value and analog output value by
digital input value.
Gain value - Offset value
Resolution =
8000
Gain value - Offset value
Analog output =
5
Digital input value
+
Offset value
8000
Analog output = Resolution
5
Digital input value
5
Offset value
Ex) Gain value : 0 VDC Offset value : - 10 VDC Digital input value : 12000
0 – ( - 10 )
Resolution = = 0.00125
8000
Analog output = 0.00125
5
12000
+
(- 10) = 5(V)
Since maximum resolution of D/A conversion module is like values on table2.5, if digital input value increase
or decrease one at a time, analog output value may be different with a result of above formula
Product code
Analog output range
Maximum resolution
G3F-DA4I
DC 4
~
20 mA
1
μ
A
-10
~
10 VDC
1.25 mV
G3F-DA4V
-5
~
5 VDC
0.625 mV
DC 4
~
20 mA
1
μ
A
G4F-DA1A
-10
~
10 VDC
1.25 mV
[Table 2.5] Maximum resolution
Содержание G3F-DA4I
Страница 42: ...Chapter 5 GM PROGRAMMING 5 5 6 I O Variables on Program ...
Страница 44: ...Chapter 5 GM PROGRAMMING 5 7 4 Program INI_STAT ...
Страница 45: ...Chapter 5 GM PROGRAMMING 5 8 5 I O Variables on Program ...
Страница 47: ...Chapter 5 GM PROGRAMMING 5 10 4 Program ...
Страница 48: ...Chapter 5 GM PROGRAMMING 5 11 5 I O Variables on Program ...
Страница 74: ...Chapter 10 G3F PA1A G3F PA2A POWER SUPPLY MODULE 10 3 10 4 Dimensions ...
Страница 75: ...Chapter 11 DIMENSIONS 11 1 Chapter 11 DIMENSIONS 11 1 G3F DA4V G3F DA4I Dimensions ...
Страница 76: ...Chapter 11 DIMENSIONS 11 2 11 2 G4F DA1A Dimensions ...