Chapter 6. BUFFER MEMORY CONFIGURATION AND FUNCTIONS
6 - 4
(2) G4F-DA1A
6.2.3 Digital Input (G3F-DA4V / G3F-DA4I : addresses 2 to 17, G4F-DA1A: addresses 2, 3)
1) Digital input value can be used within the range -192 to 16191 or -8192 to 8191 according to the data input
type specification(address 1)
2) When digital input value isn't set, digital input value has to be set to 8000.
6.2.4 Specification of CPU Module's Stop Condition or disabled Channel's Output Condition
(G3F-DA4V / G3F-DA4I :addresses 18 to 33, G4F-DA1A :addresses 4, 5)
1) When CPU module is stop, or channel is disabled, analog output value on terminal block is written onto
these addresses.
2) Output condition according to set value is as follows.
Set value
Output condition
0
Output of the medium value of setting range.
1
The previous value remains.
2
Output of the maximum value of setting range.
3
Output of the minimum value of setting range.
Excess range
Set value condition remains in the former range before exceeded