Chapter 2. SPECIFICATIONS
2 - 1
Chapter 2. SPECIFICATIONS
2.1 General Specifications
Table 2.1 shows the common specifications of GLOFA GM series and MASTER-K series
No
Items
Specifications
Reference
Specification
1 Operating ambient
temperature
0 ~ 55
℃
2
Storage ambient
temperature
-25 ~ 75
℃
3 Operating ambient
humidity
5 ~ 95%RH, non-condensing
4
Storage ambient
humidity
5 ~ 95%RH, non-condensing
Occasional vibration
Frequency
Acceleration
Amplitude
Sweep count
10
≤
f
∠
57 Hz
-
0.075mm
57
≤
f
≤
150 Hz 9.8 m/s
2
{1G}
-
Continuous vibration
Frequency
Acceleration
Amplitude
10
≤
f
∠
57 Hz
-
0.035mm
5
Vibration
57
≤
f
≤
150 Hz 4.9 m/s
2
{0.5G}
-
10 times in
each direction
for X, Y, Z
IEC 61131-2
6
Shocks
•
Maximum shock acceleration: 147 m/s
2
{15G}
•
Duration time :11ms
•
Pulse wave: half sine wave pulse( 3 times in each of X, Y and Z directions )
IEC 61131-2
Square wave impulse noise
±
1,500 V
Electrostatic discharge
Voltage :4kV(contact discharge)
IEC 61131-2
IEC 1000-4-2
Radiated
electromagnetic field
27 to 500 MHz, 10V/m
IEC 61131-2
IEC 1000-4-3
Severity
Level
All power
modules
Digital
I/Os(U
e
≥
24 V)
Digital I/Os
(Ue < 24 V)
Analog/Os
communication
I/Os
IEC 61131-2
IEC 1000-4-4
7
Noise immunity
Fast transient /burst noise
Voltage
2kV
1kV
0.25kV
8
Operating
atmosphere
Free from corrosive gases and excessive dust
9
Altitude for use
Up to 2,000m
10 Pollution degree
2 or lower
11
Cooling method
Self-cooling
[Table 2.1 ] General Specifications
REMARK
1) IEC(International Electrotechnical Commission)
:The international civilian organization which produces standards for electrical and electronics industry..
2) Pollution degree
:It indicates a standard of operating ambient pollution level.
The pollution degree 2 means the condition in which only non conductive pollution occurs. Occasionally,
however, a temporary conductivity caused by condensation shall be expected.
Содержание G3F-DA4I
Страница 42: ...Chapter 5 GM PROGRAMMING 5 5 6 I O Variables on Program ...
Страница 44: ...Chapter 5 GM PROGRAMMING 5 7 4 Program INI_STAT ...
Страница 45: ...Chapter 5 GM PROGRAMMING 5 8 5 I O Variables on Program ...
Страница 47: ...Chapter 5 GM PROGRAMMING 5 10 4 Program ...
Страница 48: ...Chapter 5 GM PROGRAMMING 5 11 5 I O Variables on Program ...
Страница 74: ...Chapter 10 G3F PA1A G3F PA2A POWER SUPPLY MODULE 10 3 10 4 Dimensions ...
Страница 75: ...Chapter 11 DIMENSIONS 11 1 Chapter 11 DIMENSIONS 11 1 G3F DA4V G3F DA4I Dimensions ...
Страница 76: ...Chapter 11 DIMENSIONS 11 2 11 2 G4F DA1A Dimensions ...