Chapter 2. SPECIFICATIONS
2 - 4
No.
Descriptions
RUN LED
①
Indicates the operating condition of the D/A conversion module
* On: Normal operation
* Flickering: An error has occurred. (For more information, see the Section 6.1)
* Off : 5 VDC power off or D/A conversion module fault
Channel select switch
②
Used to set the channel of the adjustment of offset/gain in the test mode.
Setting range: 0
~
F
Offset/gain select switch
③
Used to select Offset/Set/Gain .
*Offset position: offset value adjustment mode
*Gain position: gain value adjustment mode
*Set position: the mode which stores offset/gain value.
(When the switch is changed to "set" position from "Offset/ Gain" position, offset/gain value
is stored in the memory of D/A conversion module.)
Up/Down switch
④
-Used to make micro adjustment of offset/gain value.
-Analog output value according to up/down location is changed as follows.:
*Up/down location of less than 2 sec :
G3F-DA4I - Add or fall of 1
㎂
/1 time
G3F-DA4V-Add or fall of 1.25 mV/1 time
*Up/down location of more than 2 sec :
G3F-DA4I-Add or fall of 10
㎂
/ 0.2 sec.
G3F-DA4V Add or fall of 12.5 mV/0.2 sec
Test terminal block
⑤
Test mode is to be a connection of terminal block 1 and 2
Normal mode is to be a disconnection of terminal block 1 and 2
Output range select switch
⑥
It's only for the G3F-DA4V.
*Factory set is made to -10
~
10 VDC.
Содержание G3F-DA4I
Страница 42: ...Chapter 5 GM PROGRAMMING 5 5 6 I O Variables on Program ...
Страница 44: ...Chapter 5 GM PROGRAMMING 5 7 4 Program INI_STAT ...
Страница 45: ...Chapter 5 GM PROGRAMMING 5 8 5 I O Variables on Program ...
Страница 47: ...Chapter 5 GM PROGRAMMING 5 10 4 Program ...
Страница 48: ...Chapter 5 GM PROGRAMMING 5 11 5 I O Variables on Program ...
Страница 74: ...Chapter 10 G3F PA1A G3F PA2A POWER SUPPLY MODULE 10 3 10 4 Dimensions ...
Страница 75: ...Chapter 11 DIMENSIONS 11 1 Chapter 11 DIMENSIONS 11 1 G3F DA4V G3F DA4I Dimensions ...
Страница 76: ...Chapter 11 DIMENSIONS 11 2 11 2 G4F DA1A Dimensions ...