Chapter 9. TROUBLESHOOTING
9 - 2
9.2.2 RUN LED Off
RUN LED off
Offset/Set/Gain switch is located on Set position of test mode?
Yes
No
Yes
No
Install the D/A conversion module on the base?
Yes
No
No
Yes
Capacity sufficient for the power supply module on the base?
Yes
No
No
Yes
If D/A conversion module on which the error has occurred
is substituted for new one, normal operation?
Change test mode condition to normal mode condition
Install the D/A conversion module on the base correctly
Calculate current consumption and replace the
power supply module
Yes
No
Yes
No
Fault of other module, not the D/A conversion module.
For more information, see the CPU module User's Manual.