Chapter 1. INTRODUCION
1 - 3
1.2.3 Digital/ Analog Conversion Characteristics
1) Voltage output
[Fig 1.5] D/A conversion characteristics(Voltage output)
Digital/analog conversion module allows digital value of the CPU to be converted into an analog value
and to be output externally. Digital input v alue of 0 leads to analog output value of -10V and 16000
leads to 10V. Digital input value of 1 is equal to 1.25mV.
2) Current output
[Fig 1.6] D/A conversion characteristics(Current output)
On current output, digital value of 0 is to be converted into 4mA and 16000. into 20mA. Digital input of 1
is equal to 1
㎂
.