Chapter 4. FUNCITION BLOCK
4 - 7
4.4 Errors on Function Block
This shows the errors on the output variable “STAT” of variables and the resolutions in accordance with them.
Function Block
Write
STAT
No.
Local/
Remote
Descriptions
Initiali
zation Array
type
Single
type
Resolutions
0
Operating with no fault
O
O
O
-
1
The base location number is
exceeding the proper setting range
O
O
O
Correct the number in accordance
with the proper range
(See Section 4.2)
2
H/W error of the base
O
O
O
Contact the service station.
3
The slot location number is
exceeding the proper setting range
O
O
O
Set the right number to the slot
mounting the D/A conversion module
4
The D/A conversion module on the
slot is empty
O
O
O
Mount the D/A conversion module to
the specified slot
5
The module loaded isn't the D/A
module
O
O
O
Mount the D/A conversion module to
the specified slot
6
The channel number is exceeding
the proper range
-
-
O
Specify the available channel
correctly
7
H/W error of the D/A conversion
module
O
O
O
Contact the service station.
8
The D/A conversion module's
shared memory error
O
O
O
Contact the service station.
9
The available channels are not
specified
-
O
O
Make a correct specification of the
available channel on the initialization
function block
10
Local
Test mode
O
O
O
Transmit the test mode to normal
mode
128
H/W error of the communication
module for remote
O
O
See the manual for the remote
communication module
129
The base location number is
exceeding the proper setting range
O
O
Corsets the number in accordance
with the proper range
(See Section 4.2)
131
The slot location number is
exceeding the proper setting range
O
O
Set the right number to the slot
mounting the D/A conversion module
133
The module loaded isn't the D/A
module
O
O
Mount the D/A conversion module to
the specified slot
135
H/W error of the D/A conversion
module
O
O
Contact the service station.
136
The D/A conversion module's
shared memory error
O
O
Contact the service station.
137
The available channels are not
specified
-
O
Make a correct specification of the
available channel on the initialization
function block
138
Remote
Test mode
O
O
-
Transmit the test mode to normal
mode
Содержание G3F-DA4I
Страница 42: ...Chapter 5 GM PROGRAMMING 5 5 6 I O Variables on Program ...
Страница 44: ...Chapter 5 GM PROGRAMMING 5 7 4 Program INI_STAT ...
Страница 45: ...Chapter 5 GM PROGRAMMING 5 8 5 I O Variables on Program ...
Страница 47: ...Chapter 5 GM PROGRAMMING 5 10 4 Program ...
Страница 48: ...Chapter 5 GM PROGRAMMING 5 11 5 I O Variables on Program ...
Страница 74: ...Chapter 10 G3F PA1A G3F PA2A POWER SUPPLY MODULE 10 3 10 4 Dimensions ...
Страница 75: ...Chapter 11 DIMENSIONS 11 1 Chapter 11 DIMENSIONS 11 1 G3F DA4V G3F DA4I Dimensions ...
Страница 76: ...Chapter 11 DIMENSIONS 11 2 11 2 G4F DA1A Dimensions ...