Control Device Loads
Power Wire - Run Length
The maximum total run length of each segment is a function of the total number
of unit loads. A run becomes too long when the voltage drop, due to wire size and
run length, increases to a point where the station does not have sufficient voltage
to operate. The maximum run length, in feet, based on the total number of unit
loads is shown below:
(2) Tables are provided, (1) @ 12VDC and (1) at 24VDC. Make
sure that you use the correct table!
Wire Size vs. Length of Runs - Power Wiring @24 VDC
Photocell, pcout-
000
-
Photocell, pcsky-
000
-
Control Devices
Unit
Load
@12VD
C
Unit
Load
@24VD
C
Station Type
Unit
Load
@
12VDC
Unit
Load @
24VDC
Voltage Drop Table
(Ams) (Unit Loads
12V
24V
12V
24V
12V
24V
12V
24V
12V
24V
0.25
10
756
3,528
1,200
5,600
1,904
8,885
3,000
14,000
4,800
22,400
0.50
20
378
1,764
600
2,800
952
4,443
1,500
7,000
2,400
11,200
0.75
30
252
1,176
400
1,867
635
2,962
1,000
4,667
1,600
7,467
1.00
40
189
882
300
1,400
476
2,221
750
3,500
1,200
5,600
1.25
50
151
706
240
1,120
381
1,777
600
2,800
960
4,480
1.50
60
126
588
200
933
317
1,481
500
2,333
800
3,733
1.75
70
108
504
171
800
272
1,269
429
2,000
686
3,200
2.00
80
150
700
238
1,111
375
1,750
600
2,800
2.25
90
133
622
212
987
333
1,556
533
2,489
2.50
100
120
560
190
889
300
1,400
480
2,240
2.75
110
109
509
173
808
273
1,273
436
2,036
3.00
120
100
467
159
740
250
1,167
400
1,867
3.25
130
146
683
231
1,077
369
1,723
3.50
140
136
635
214
1,000
343
1,600
3.75
150
127
592
200
933
320
1,493
4.00
160
119
555
188
875
300
1,400
4.25
170
112
523
176
824
282
1,318
4.50
180
106
494
167
778
267
1,244
4.75
190
100
468
158
737
253
1,179
5.00
200
150
700
240
1,120
10AWG
Current
18AWG
16AWG
14AWG
12AWG