a-2000 User Guide
a-2000
Page 25
Dimmer Cabinets with Digital Controls
Revision G November 2006
Table 8- Control Station Loads
Example
:
Suppose we had a network with the following equipment:
•
D4200 LCD Stations
•
D4200 Entry Stations
•
Remote IR Station
•
Powered from an a-2000 24 Cabinet with a Standard Power Supply
Use these quantities along with the Load Rating verification formula (Figure 15) to
do the math and verify that the combined unit input load does not exceed the
maximum input Unit Load Available.
Station Type
Unit Load
(per
station)
Station Type
Unit
Load
(per
station)
D4200 LCD
2
D8000 Entry (Button)
1
D4200 Entry
(Button)
1
D8000 Slider
1
D4200 Room
Combine Station
1
D8000 Key switch
1
D4200 Remote I/R
1
D8000 Port (LumaEdit,
A/V, etc.)
1
Luma-Net Hub
3
D8000 Combine/Closure
(Advanced)
10
D8000 LCD
2
Quantity
Unit Loads
D4200 LCD
Stations
4
x
2
=
8
+
D4200 Entry
Stations
6
x
1
=
6
+
Remote IR
Station
1
x
1
=
1
Total 15