The cable should not pass near any source of electrical noise such as
fluorescent circuits or motor wiring. Avoid close proximity to any AC
wiring. All control/power wiring must be in conduit.
Figure 15 - The Right and Wrong Way to Run Luma-Net
•
See Table 10 for recommended Wire Types
•
Use RS485 compatible cable for the communications. It is recommended that a cable with 2
Twisted Pair, 24 AWG, stranded conductors be used. The spare pair is for future uses.
•
Capacitance of wire shall be 12pF/ft. or less
•
Nominal Impedance of wire shall be between 100-120 ohms
•
A second pair (#14 AWG stranded or larger) is required for the power.
•
Drain/Shields to be tied together, insulated and grounded (on
one point
only)!
•
We strongly recommend the use of either Belden 9829 or Belden 9729 for the Luma-
Net wire runs.
The most effective way to insulate the drain/shield wire is to use a piece of heat shrink
tubing!
D4200 CONTROL STATION
PRESET SELECT STATION
C
12
18
15
16
17
13
14
6
9
10
11
7
8
3
4
5
1
2
A
B
DMX
CANCEL
LUMANET
CLEAR
PHASE LOSS
AUXILIARY
FULL BRIGHT
COMMUNICATION PORTS
FAN
SAVE
FULL
SELECT
BRIGHT
a-2000D
a-2000D
PRESET SELECT STATION
17
16
18
10
11
14
13
15
12
5
8
7
9
6
B
2
4
3
C
1
A
D4200 CONTROL STATION
LUMANET
DMX
CLEAR
CANCEL
FAN
COMMUNICATION PORTS
FULL BRIGHT
AUXILIARY
PHASE LOSS
BRIGHT
SELECT
FULL
SAVE
LUMA-NET III HUB
Note: a-2000D Cabinet can be in the
middle of a daisy chain
a-2000D
PRESET SELECT STATION
17
16
18
10
11
14
13
15
12
5
8
7
9
6
B
2
4
3
C
1
A
D4200 CONTROL STATION
LUMANET
DMX
CLEAR
CANCEL
FAN
COMMUNICATION PORTS
FULL BRIGHT
AUXILIARY
PHASE LOSS
BRIGHT
SELECT
FULL
SAVE
Содержание a-2000
Страница 2: ...Notes ...
Страница 6: ...Page 4 ...
Страница 78: ...Page 76 ...
Страница 82: ...Page 80 ...