Smart Process Gating
Leuze electronic GmbH + Co. KG
MLC 530 SPG
27
• The permissible protective field filter time t2 is set to 0.5 s. The protective field can thereby be cleared
for up to 0.5 s, e.g., for gaps in the load, etc.
• At higher transport speeds, the gating end must be performed by the control (see chapter 4.5.1 "Con-
CS
PFI
t1
GA
t3
t2
t4
CS
Switching signal from the control
TH
Timer hold signal from the control (optional)
PFI
Protective field interrupted
GA
Gating active
t1
< 2 s
t2
0.5 s
t3
< 20 s
t4
< 10 min
Fig. 4.4:
Operating mode 5
NOTICE
The timeout of 10 minutes can optionally be extended by another control signal (TH timer hold
signal) from the control to up to 100 hours (see chapter 4.5.2 "Gating timeout extension").