Smart Process Gating
Leuze electronic GmbH + Co. KG
MLC 530 SPG
35
4.5.3
Gating sequence reset
WARNING
Unauthorized reset may result in serious injury!
Ä
An instructed person must watch the event carefully.
Ä
Make certain that the danger zone can be viewed from the reset button and that the entire
process can be observed by the instructed person.
RES
PFI
t1
t4
CS
P-Mode
GA
CS
Switching signal from the control
RES
Restart button
PFI
Protective field interrupted
P-mode
Protective mode
GA
Gating active
t1
< 4 s
t4
< 1 h
Fig. 4.10:
Gating sequence reset
If the CS switching signal is applied for more than 4 s without the protective field being interrupted, the de-
vice switches to protective mode and the OSSDs switch off. If there is then no protective field violation, the
RES signal can be used to start a new gating sequence.
• A new gating sequence can be started multiple times if still no protective field violation occurs after ap-
plying the RES signal.
• The gating sequence restart must occur within no more than one hour, otherwise the device switches to
an interlock state.
• It may be necessary to reapply the CS switching signal before initiating a new gating sequence.