User interface
Building up serial communication
4
19
SW-HB 13.0002-EN EN 3.0
ƒ
Retry with old parameters (COM3, 9600 Baud):
To solve the access conflict with a program using the interface, close the other program
(withMS-DOS programs,also closethe MS-DOSshell!!)andclick
Retrywitholdparameters
(COM3, 9600 Baud)
.
ƒ
Change COM port:
Click
Change COM port
to correct a wrong interface setting and select a different interface.
ƒ
Search Baud rates:
Under certain conditions, the servo positioning controller may use a baud rate other than
the baud rate selected in the parameterisation program. If you select
Search Baud rates
,
the parameterisation program will try to build up communication with different baud
rates.
ƒ
Offline parameterisation:
The
Offline parameterisation
is only useful, if you want to edit parameter set files without
the servo positioning controller. For more information, please see the chapter ”Offline
parameterisation”. (
187)
ƒ
Firmware download:
If the servo positioning controller contains an invalid firmware version or if you want to
download a new firmware, select
Firmware download
to initiate the firmware download.
ƒ
Exit program:
Click
Exit program
to exit the program.
The below table lists possible error causes and troubleshooting strategies:
Error
Remedy
Communication problem
Click
Retry with old parameters
.
Wrong COM port
Click
Change COM port
and follow the instructions.
Baud rate of parameterisation program and servo
positioning controller is not identical
Click
Search Baud rates
.
Communication of servo positioning controller has
been interfered
RESET
the servo positioning controller, i.e.
power-off/power-on. After this, click
Retry with old
parameters
.
Hardware error
Servo positioning controller is not switched on
Remove error, then click
Retry with old parameters
.
Connecting cable has not been plugged in
Connecting cable is broken
Wrong pin assignment for serial connection
Connecting cable is too long
Reduce baud rate or use shorter cable.