User Response
No action; information only.
•
806f0a07-0301ffff : [ProcessorElementName] is operating in a Degraded State. (CPU 1)
This message is for the use case when an implementation has detected a Processor is running in the
Degraded state.
May also be shown as 806f0a070301ffff or 0x806f0a070301ffff
Severity
Warning
Serviceable
Yes
Automatically notify support
No
Alert Category
Warning - CPU
SNMP Trap ID
42
CIM Information
Prefix:
PLAT
ID:
0038
User Response
1. Make sure that the fans are operating, that there are no obstructions to the airflow (front and
rear of the server), that the air baffles are in place and correctly installed, and that the server
cover is installed and completely closed.
2. Check the ambient temperature. You must be operating within the specifications.
3. Make sure that the heat sink for microprocessor n is installed correctly.
4. (Trained technician only) Replace microprocessor n. (n = microprocessor number)
•
81010002-0701ffff : Numeric sensor [NumericSensorElementName] going low (lower non-critical)
has deasserted. (CMOS Battery)
This message is for the use case when an implementation has detected a Lower Non-critical sensor
going low has deasserted.
May also be shown as 810100020701ffff or 0x810100020701ffff
Severity
Info
Serviceable
No
Automatically notify support
No
350
Lenovo System x3250 M4 Installation and Service Guide
Содержание System x3250 M4
Страница 1: ...Lenovo System x3250 M4 Installation and Service Guide Machine Type 2583 ...
Страница 6: ...iv Lenovo System x3250 M4 Installation and Service Guide ...
Страница 74: ...60 Lenovo System x3250 M4 Installation and Service Guide ...
Страница 98: ...84 Lenovo System x3250 M4 Installation and Service Guide ...
Страница 136: ...122 Lenovo System x3250 M4 Installation and Service Guide ...
Страница 144: ...130 Lenovo System x3250 M4 Installation and Service Guide ...
Страница 418: ...404 Lenovo System x3250 M4 Installation and Service Guide ...
Страница 596: ...582 Lenovo System x3250 M4 Installation and Service Guide ...
Страница 604: ...Taiwan BSMI RoHS declaration 590 Lenovo System x3250 M4 Installation and Service Guide ...
Страница 612: ...598 Lenovo System x3250 M4 Installation and Service Guide ...
Страница 613: ......
Страница 614: ......