Do not replace a different type of I/O book after the PCIe lane has been assigned. Replace with the
same type.
•
80070221-2c02ffff : Sensor [SensorElementName] has transitioned to critical from a less severe
state.
A IOBook2 mismatch has been detected.
May also be shown as 800702212c02ffff or 0x800702212c02ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Other
SNMP Trap ID
50
CIM Information
Prefix:
PLAT
ID:
0522
User Response
Do not replace a different type of I/O book after the PCIe lane has been assigned. Replace with the
same type.
•
80070301-0301ffff : Sensor [SensorElementName] has transitioned to non-recoverable from a less
severe state.
IMM has detected that the temperature for microprocessor 1 has transitioned to a non recoverable state.
May also be shown as 800703010301ffff or 0x800703010301ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Temperature
SNMP Trap ID
0
CIM Information
Prefix:
PLAT
ID:
0524
User Response
Complete the following steps until the problem is solved:
1. Check the IMM event log for any fan or cooling related issues.
2. Make sure that the airflow at the front and rear of the server is not obstructed and that fillers are
in place and correctly installed.
3. Make sure that the room temperature is within operating specifications.
Appendix C. Integrated management module II (IMM2) error messages
643
Содержание 6241
Страница 1: ...System x3850 X6 and x3950 X6 Installation and Service Guide Machine Type 6241 ...
Страница 6: ...iv System x3850 X6 and x3950 X6 Installation and Service Guide ...
Страница 56: ...42 System x3850 X6 and x3950 X6 Installation and Service Guide ...
Страница 82: ...68 System x3850 X6 and x3950 X6 Installation and Service Guide ...
Страница 132: ...118 System x3850 X6 and x3950 X6 Installation and Service Guide ...
Страница 158: ...144 System x3850 X6 and x3950 X6 Installation and Service Guide ...
Страница 214: ...200 System x3850 X6 and x3950 X6 Installation and Service Guide ...
Страница 358: ...344 System x3850 X6 and x3950 X6 Installation and Service Guide ...
Страница 1938: ...1924 System x3850 X6 and x3950 X6 Installation and Service Guide ...
Страница 1964: ...1950 System x3850 X6 and x3950 X6 Installation and Service Guide ...
Страница 1968: ...1954 System x3850 X6 and x3950 X6 Installation and Service Guide ...
Страница 1975: ...Taiwan Class A compliance statement Appendix F Notices 1961 ...
Страница 1976: ...Taiwan BSMI RoHS declaration 1962 System x3850 X6 and x3950 X6 Installation and Service Guide ...
Страница 1988: ...1974 System x3850 X6 and x3950 X6 Installation and Service Guide ...
Страница 1989: ......
Страница 1990: ......