806f0a07-0304ffff : [ProcessorElementName] is operating in a Degraded State.
The microprocessor 4 is being throttled due to thermal or power conditions.
May also be shown as 806f0a070304ffff or 0x806f0a070304ffff
Severity
Warning
Serviceable
Yes
Automatically notify support
No
Alert Category
Warning - CPU
SNMP Trap ID
42
CIM Information
Prefix:
PLAT
ID:
0038
User Response
Check the IMM event log for any fan, cooling, or power related issues.
For a thermal condition:
1. Make sure that the airflow at the front and rear of the server is not obstructed and that fillers are
in place and correctly installed.
2. Make sure that the room temperature is within operating specifications.
For a power condition:
1. If Power Supply Unit is rated 1400 Watt, Make sure it is connected to 220V AC input
2. If using a 900 Watt rated power supply (connected at either 110V or 220 V ), may need to
upgrade to a 1400 Watt rated power supply (connected at 220V).
Related links
– Server features and specifications
– Solving power problems
– Installing power supplies
•
806f0a0c-2b810001 : An Over-Temperature Condition has been detected on the
[PhysicalMemoryElementName] on Subsystem [MemoryElementName].
IMM determined DIMM 1 in Compute Book 1 has an Over Temperature Condition.
May also be shown as 806f0a0c2b810001 or 0x806f0a0c2b810001
Severity
Error
Serviceable
yes
Automatically notify support
no
Alert Category
Critical - Temperature
1266
System x3850 X6 and x3950 X6 Installation and Service Guide
Содержание 6241
Страница 1: ...System x3850 X6 and x3950 X6 Installation and Service Guide Machine Type 6241 ...
Страница 6: ...iv System x3850 X6 and x3950 X6 Installation and Service Guide ...
Страница 56: ...42 System x3850 X6 and x3950 X6 Installation and Service Guide ...
Страница 82: ...68 System x3850 X6 and x3950 X6 Installation and Service Guide ...
Страница 132: ...118 System x3850 X6 and x3950 X6 Installation and Service Guide ...
Страница 158: ...144 System x3850 X6 and x3950 X6 Installation and Service Guide ...
Страница 214: ...200 System x3850 X6 and x3950 X6 Installation and Service Guide ...
Страница 358: ...344 System x3850 X6 and x3950 X6 Installation and Service Guide ...
Страница 1938: ...1924 System x3850 X6 and x3950 X6 Installation and Service Guide ...
Страница 1964: ...1950 System x3850 X6 and x3950 X6 Installation and Service Guide ...
Страница 1968: ...1954 System x3850 X6 and x3950 X6 Installation and Service Guide ...
Страница 1975: ...Taiwan Class A compliance statement Appendix F Notices 1961 ...
Страница 1976: ...Taiwan BSMI RoHS declaration 1962 System x3850 X6 and x3950 X6 Installation and Service Guide ...
Страница 1988: ...1974 System x3850 X6 and x3950 X6 Installation and Service Guide ...
Страница 1989: ......
Страница 1990: ......