Page 64 - IOM / ROOF-TOP FLEXY™ Series
USING THE KP02 MAINTENANCE CONTROL DISPLAY
LIST OF SETPOINTS (LF 20 - APRIL 2002) - cont'd
1st Level
Mini. Factory Maxi.
C 041
[Safety limits] Room relative humidity low limit (in %) - Threshold of
activation of the safety cut-out
0 %
0 %
50 %
C 042
[Limit safety] Room absolute humidity low limit (in g/kg) - Threshold of
activation of the safety cut-out
0.0 g/kg
0.0 g/kg
30.0 g/kg
C 043
[Safety limits] Room relative humidity high limit (in %) - Threshold of
activation of the safety cut-out
50 %
100 %
100 %
C 044
[Limit safety] Room absolute humidity high limit (in g/kg) - Threshold
of activation of the safety cut-out
0.0 g/kg
30.0 g/kg
30.0 g/kg
C 045
[Anticipation function] Bottom of slope (in °c) - Limit of activation of
the function - This allows an anticipated start-up in the morning mode
depending on the outside temperature.
0.0 c
10.0 c
20.0 c
C 046
[Anticipation function] Slope - Number of minutes of anticipation per
degrees. This allows an anticipated start-up in the morning mode
depending on the outside temperature.
0 0
100
C 047
[Co²] Fresh air dampers opening threshold (in ppm)
0 ppm
1000 ppm
2000 ppm
C 048
[Co²] Fresh air dampers maximum opening limit (in ppm)
0 ppm
1500 ppm
2000 ppm
C 049
[Extraction] Threshold of activation of the power exhaust fan
according to the position of the economiser damper (in %)
0 %
10%
100 %
2nd Level
Mini. Factory Maxi.
C 050
[kp17] [Mode] Maximum limit for room temperature, Day mode (in °c)
- (active for the mode Day)
21.0 c
27.0 c
35.0 c
C 051
[kp17] [Mode] Minimum limit for room temperature, Day mode (in °c) -
(active for the mode Day)
8.0 c
17.0 c
21.0 c
C 052
[Room control] Minimum operation time for a stage (in seconds)
25 s
180 s
1800 s
C 053
[Room control] Temperature difference between the beginning and
the end of a stage of control in cooling. (in °c)
0.0 c
1.0 c
10.0 c
C 054
[Room regulation] Temperature difference between two stages of
control in cooling. (in °c)
0.1 c
1.0 c
10.0 c
C 055
[Room control] Temperature difference between the beginning and
the end of a stage of control in heating. (in °c)
0.0 c
0.5 c
10.0 c
C 056
[Room control] Temperature difference between two stages of control
in heating. (in °c)
0.1 c
0.5 c
10.0 c
C 057
[Room control] Choice of the priority for the control in heating.
[On] Hot water coil or electrical heater or gas then compressors
[Off]. Compressors then hot water coil or electrical heater or gas
Off Off On
C 058
[Supply control] Activation of the control. – The control of the supply
applies when the room temperature is in the dead zone. - This
function allows to maintain comfort with the supply air
Off Off On
C 059
[Supply control] Sampling time (in seconds)
1 s
10 s
120 s
C 060
[Supply control] Choice of the priority for the control in heating
[On] Hot water coil or electrical heater or gas then compressors
[Off] Compressors then hot water coil or electrical heater or gas
Off Off On
Содержание ROOFTOP FLEXY FCA 100
Страница 1: ...INSTALLATION OPERATING MAINTENANCE MANUAL ROOFTOP FLEXY English August 2003 ...
Страница 2: ......
Страница 33: ...IOM ROOF TOP FLEXY Series Page 31 AIR FLOW BALANCING AT 12 12 FAN ...
Страница 34: ...Page 32 IOM ROOF TOP FLEXY Series AIR FLOW BALANCING AT 15 15 FAN ...
Страница 35: ...IOM ROOF TOP FLEXY Series Page 33 AIR FLOW BALANCING AT 18 13 ...
Страница 36: ...Page 34 IOM ROOF TOP FLEXY Series AIR FLOW BALANCING AT 18 18 FAN ...
Страница 37: ...IOM ROOF TOP FLEXY Series Page 35 AIR FLOW BALANCING RDN 450 FAN ...
Страница 38: ...Page 36 IOM ROOF TOP FLEXY Series AIR FLOW BALANCING ADN 355 FAN ...
Страница 39: ...IOM ROOF TOP FLEXY Series Page 37 AIR FLOW BALANCING ADN 400 FAN ...
Страница 40: ...Page 38 IOM ROOF TOP FLEXY Series AIR FLOW BALANCING ADN 450 FAN ...
Страница 56: ...Page 54 IOM ROOF TOP FLEXY Series GAS BURNERS 60 KW BURNER FOR FGX 60 AND 70 MODELS 1 2 Figure 63 ...
Страница 57: ...IOM ROOF TOP FLEXY Series Page 55 GAS BURNER 120 KW BURNER FOR FGX 60 70 AND 100 MODELS 1 2 3 Figure 64 ...
Страница 58: ...Page 56 IOM ROOF TOP FLEXY Series 180 KW BURNER FOR FGX 120 AND 140 MODELS GAS BURNER 1 2 3 Figure 65 ...
Страница 104: ...Page 102 IOM ROOF TOP FLEXY Series ELECTRICAL WIRING DIAGRAMS MAIN CURRENT DIAGRAM ...
Страница 106: ...Page 104 IOM ROOF TOP FLEXY Series ELECTRICAL WIRING DIAGRAMS CLIMATIC CONTROLLER ...
Страница 107: ...IOM ROOF TOP FLEXY Series Page 105 ELECTRICAL WIRING DIAGRAMS CLIMATIC INPUT FC FH FX Confort Set Point GTC ...
Страница 108: ...Page 106 IOM ROOF TOP FLEXY Series ELECTRICAL WIRING DIAGRAMS CLIMATIC INPUT FG FD ...
Страница 111: ...IOM ROOF TOP FLEXY Series Page 109 ELECTRICAL WIRING DIAGRAMS WIRING DIAGRAM GAS BURNER 33 60 120 Kw ...
Страница 112: ...Page 110 IOM ROOF TOP FLEXY Series ELECTRICAL WIRING DIAGRAMS GAS BURNER 180 Kw ...
Страница 132: ...Page 130 IOM ROOF TOP FLEXY Series ISO 9001 CERTIFICATION ...
Страница 133: ...IOM ROOF TOP FLEXY Series Page 131 PED CERTIFICATION OF CONFORMITY ...
Страница 134: ...Page 132 IOM ROOF TOP FLEXY Series GLASS WOOL FIRE CLASS ...
Страница 135: ...IOM ROOF TOP FLEXY Series Page 133 33 kW GAS BURNER CE CERTIFICATION OF CONFORMITY ...
Страница 136: ...Page 134 IOM ROOF TOP FLEXY Series 60 kW GAS BURNER CE CERTIFICATION OF CONFORMITY ...
Страница 137: ...IOM ROOF TOP FLEXY Series Page 135 120 kW GAS BURNER CE CERTIFICATION OF CONFORMITY ...
Страница 138: ...Page 136 IOM ROOF TOP FLEXY Series 180 kW GAS BURNER CE CERTIFICATION OF CONFORMITY ...
Страница 139: ...IOM ROOF TOP FLEXY Series Page 137 INSULATION FIRE CLASS ...
Страница 140: ...Page 138 IOM ROOF TOP FLEXY Series INSULATION FIRE CLASS ...
Страница 141: ......