IOM / ROOF-TOP FLEXY™ Series - Page 121
Customer error
A fault has been detected, external to the unit.
Water leak
If the contact of the water leak detection card is closed for more than 30 seconds, the safety
system is activated.
WATER HEAT EXCHANGER OUTLET TEMPERATURE SAFETY SYSTEM.
Condenser Water Temperature Too Low
If the temperature of the water loop is less than or equal to the preset setpoint
[C80]
during the
operation of one of the compressors, the condenser safety mechanism is applied. The
compressors are stopped.
This safety mechanism automatically cuts out if the loop temperature exceeds 4°C from this
setpoint.
It is also automatically locked out after 3 failures within a day. In this case, manual resetting is
obligatory. The counter is reset to zero every evening at 20:00 if its value does not exceed 3
failures.
Condenser Water Temperature Too High
The temperature of the water loop is greater than or equal to the preset setpoint
[C81]
during
the operation of one of the compressors, the condenser safety mechanism is applied. The
compressors are stopped.
This safety mechanism automatically cuts out if the loop temperature is less than 4°C from this
setpoint.
It is also automatically locked out after 3 failures within a day. In this case, manual resetting is
obligatory. The counter is reset to zero every evening at 20:00 if its value does not exceed 3
failures.
Faulty Water Flow
If the contact of the water flow controller is open for more than 20 seconds, the condenser
safety mechanism is applied. The compressors are stopped.
This safety mechanism automatically cuts out if the loop temperature is less than 4°C from this
setpoint.
It is also automatically locked out after 3 failures within a day. In this case, manual resetting is
obligatory. The meter is reset to zero every evening at 20:00 if its value does not exceed 3
failures.
Error : Smoke
If the contact closes due to the smoke detector card, the smoke safety mechanism is activated.
The unit is completely shut down and the fresh air louver is set to the fresh air position.
This safety mechanism is automaticallylocked out. In this case, manual resetting is obligatory.
SAFETY AND ERROR CODES
094
095
096
096
098
099
Содержание ROOFTOP FLEXY FCA 100
Страница 1: ...INSTALLATION OPERATING MAINTENANCE MANUAL ROOFTOP FLEXY English August 2003 ...
Страница 2: ......
Страница 33: ...IOM ROOF TOP FLEXY Series Page 31 AIR FLOW BALANCING AT 12 12 FAN ...
Страница 34: ...Page 32 IOM ROOF TOP FLEXY Series AIR FLOW BALANCING AT 15 15 FAN ...
Страница 35: ...IOM ROOF TOP FLEXY Series Page 33 AIR FLOW BALANCING AT 18 13 ...
Страница 36: ...Page 34 IOM ROOF TOP FLEXY Series AIR FLOW BALANCING AT 18 18 FAN ...
Страница 37: ...IOM ROOF TOP FLEXY Series Page 35 AIR FLOW BALANCING RDN 450 FAN ...
Страница 38: ...Page 36 IOM ROOF TOP FLEXY Series AIR FLOW BALANCING ADN 355 FAN ...
Страница 39: ...IOM ROOF TOP FLEXY Series Page 37 AIR FLOW BALANCING ADN 400 FAN ...
Страница 40: ...Page 38 IOM ROOF TOP FLEXY Series AIR FLOW BALANCING ADN 450 FAN ...
Страница 56: ...Page 54 IOM ROOF TOP FLEXY Series GAS BURNERS 60 KW BURNER FOR FGX 60 AND 70 MODELS 1 2 Figure 63 ...
Страница 57: ...IOM ROOF TOP FLEXY Series Page 55 GAS BURNER 120 KW BURNER FOR FGX 60 70 AND 100 MODELS 1 2 3 Figure 64 ...
Страница 58: ...Page 56 IOM ROOF TOP FLEXY Series 180 KW BURNER FOR FGX 120 AND 140 MODELS GAS BURNER 1 2 3 Figure 65 ...
Страница 104: ...Page 102 IOM ROOF TOP FLEXY Series ELECTRICAL WIRING DIAGRAMS MAIN CURRENT DIAGRAM ...
Страница 106: ...Page 104 IOM ROOF TOP FLEXY Series ELECTRICAL WIRING DIAGRAMS CLIMATIC CONTROLLER ...
Страница 107: ...IOM ROOF TOP FLEXY Series Page 105 ELECTRICAL WIRING DIAGRAMS CLIMATIC INPUT FC FH FX Confort Set Point GTC ...
Страница 108: ...Page 106 IOM ROOF TOP FLEXY Series ELECTRICAL WIRING DIAGRAMS CLIMATIC INPUT FG FD ...
Страница 111: ...IOM ROOF TOP FLEXY Series Page 109 ELECTRICAL WIRING DIAGRAMS WIRING DIAGRAM GAS BURNER 33 60 120 Kw ...
Страница 112: ...Page 110 IOM ROOF TOP FLEXY Series ELECTRICAL WIRING DIAGRAMS GAS BURNER 180 Kw ...
Страница 132: ...Page 130 IOM ROOF TOP FLEXY Series ISO 9001 CERTIFICATION ...
Страница 133: ...IOM ROOF TOP FLEXY Series Page 131 PED CERTIFICATION OF CONFORMITY ...
Страница 134: ...Page 132 IOM ROOF TOP FLEXY Series GLASS WOOL FIRE CLASS ...
Страница 135: ...IOM ROOF TOP FLEXY Series Page 133 33 kW GAS BURNER CE CERTIFICATION OF CONFORMITY ...
Страница 136: ...Page 134 IOM ROOF TOP FLEXY Series 60 kW GAS BURNER CE CERTIFICATION OF CONFORMITY ...
Страница 137: ...IOM ROOF TOP FLEXY Series Page 135 120 kW GAS BURNER CE CERTIFICATION OF CONFORMITY ...
Страница 138: ...Page 136 IOM ROOF TOP FLEXY Series 180 kW GAS BURNER CE CERTIFICATION OF CONFORMITY ...
Страница 139: ...IOM ROOF TOP FLEXY Series Page 137 INSULATION FIRE CLASS ...
Страница 140: ...Page 138 IOM ROOF TOP FLEXY Series INSULATION FIRE CLASS ...
Страница 141: ......