IOM / ROOF-TOP FLEXY™ Series - Page 45
GAS BURNER
1.
PRELIMINARY CHECKS AND VERIFI-
CATIONS BEFORE START-UP
NOTE :
ANY WORK ON THE GAS SYSTEM MUST BE
CARRIED OUT BY QUALIFIED PERSONNEL.
THIS UNIT MUST BE INSTALLED IN
ACCORDANCE WITH LOCAL SAFETY CODES
AND REGULATIONS AND CAN ONLY BE USED IN
WELL VENTILLATED AREA.
PLEASE READ CAREFULLY THE
MANUFACTURER'S INSTRUCTIONS BEFORE
STARTING A UNIT.
BEFORE COMMISSIONING A UNIT WITH GAZ
BURNER, IT IS MANDATORY TO ENSURE THAT
THE GAZ DISTRIBUTION SYSTEM (type of gas,
available pressure…) IS COMPATIBLE WITH THE
ADJUSTMENT AND SETTINGS OF THE UNIT.
1.1 Check access and clearances around the
unit :
- Make sure one can move freely around the unit
- A one-meter clearance must be left in front of the burnt
gas exhaust chimney(s)
- Combustion air inlet and burnt gas exhaust(s) must not
be obstructed in any way.
1.2 Supply network pipe sizing
- The gas supply to a
rooftop gas unit must
be according to Sound
Engineering Practice.
- The pipe-work
connected to each
rooftop must not be
smaller than the
diameter of the
connection on the
rooftop unit.
1.3 Shut-off valve in front of each rooftop
- Make sure that a shut off isolation valve has been
installed before EACH rooftop.
- Check that the internal shut off valves in the rooftop unit
is open.
1.4 Pipe-work purging and gas static pressure
checks
- Purge the pipe-work
near the connection on
the HONEYWELL valve
for a few seconds
Standard GN 20 mbar :
Check the pressure at the
inlet of the HONEYWELL
valve.
GN 300 mbar option with pressure regulator :
Check the pressure at the regulator inlet.
Propane 37 mbar option :
Check the pressure at the inlet of the HONEYWELL valve.
Propane 148 mbar option with pressure regulation
(yellow spring) :
Check the pressure at the regulator inlet. A 10% tolerance
around the nominal pressure is acceptable.
1.5 Probes and electrodes position check
Visually check that the ionisation probe is centred in the middle
of the flame.
Check that the end of the ignition electrode is aligned with the
side of the inshot burner.
Figure 40
Figure 41
INCORRECT
CORRECT
Figure 42
Figure 43
Содержание ROOFTOP FLEXY FCA 100
Страница 1: ...INSTALLATION OPERATING MAINTENANCE MANUAL ROOFTOP FLEXY English August 2003 ...
Страница 2: ......
Страница 33: ...IOM ROOF TOP FLEXY Series Page 31 AIR FLOW BALANCING AT 12 12 FAN ...
Страница 34: ...Page 32 IOM ROOF TOP FLEXY Series AIR FLOW BALANCING AT 15 15 FAN ...
Страница 35: ...IOM ROOF TOP FLEXY Series Page 33 AIR FLOW BALANCING AT 18 13 ...
Страница 36: ...Page 34 IOM ROOF TOP FLEXY Series AIR FLOW BALANCING AT 18 18 FAN ...
Страница 37: ...IOM ROOF TOP FLEXY Series Page 35 AIR FLOW BALANCING RDN 450 FAN ...
Страница 38: ...Page 36 IOM ROOF TOP FLEXY Series AIR FLOW BALANCING ADN 355 FAN ...
Страница 39: ...IOM ROOF TOP FLEXY Series Page 37 AIR FLOW BALANCING ADN 400 FAN ...
Страница 40: ...Page 38 IOM ROOF TOP FLEXY Series AIR FLOW BALANCING ADN 450 FAN ...
Страница 56: ...Page 54 IOM ROOF TOP FLEXY Series GAS BURNERS 60 KW BURNER FOR FGX 60 AND 70 MODELS 1 2 Figure 63 ...
Страница 57: ...IOM ROOF TOP FLEXY Series Page 55 GAS BURNER 120 KW BURNER FOR FGX 60 70 AND 100 MODELS 1 2 3 Figure 64 ...
Страница 58: ...Page 56 IOM ROOF TOP FLEXY Series 180 KW BURNER FOR FGX 120 AND 140 MODELS GAS BURNER 1 2 3 Figure 65 ...
Страница 104: ...Page 102 IOM ROOF TOP FLEXY Series ELECTRICAL WIRING DIAGRAMS MAIN CURRENT DIAGRAM ...
Страница 106: ...Page 104 IOM ROOF TOP FLEXY Series ELECTRICAL WIRING DIAGRAMS CLIMATIC CONTROLLER ...
Страница 107: ...IOM ROOF TOP FLEXY Series Page 105 ELECTRICAL WIRING DIAGRAMS CLIMATIC INPUT FC FH FX Confort Set Point GTC ...
Страница 108: ...Page 106 IOM ROOF TOP FLEXY Series ELECTRICAL WIRING DIAGRAMS CLIMATIC INPUT FG FD ...
Страница 111: ...IOM ROOF TOP FLEXY Series Page 109 ELECTRICAL WIRING DIAGRAMS WIRING DIAGRAM GAS BURNER 33 60 120 Kw ...
Страница 112: ...Page 110 IOM ROOF TOP FLEXY Series ELECTRICAL WIRING DIAGRAMS GAS BURNER 180 Kw ...
Страница 132: ...Page 130 IOM ROOF TOP FLEXY Series ISO 9001 CERTIFICATION ...
Страница 133: ...IOM ROOF TOP FLEXY Series Page 131 PED CERTIFICATION OF CONFORMITY ...
Страница 134: ...Page 132 IOM ROOF TOP FLEXY Series GLASS WOOL FIRE CLASS ...
Страница 135: ...IOM ROOF TOP FLEXY Series Page 133 33 kW GAS BURNER CE CERTIFICATION OF CONFORMITY ...
Страница 136: ...Page 134 IOM ROOF TOP FLEXY Series 60 kW GAS BURNER CE CERTIFICATION OF CONFORMITY ...
Страница 137: ...IOM ROOF TOP FLEXY Series Page 135 120 kW GAS BURNER CE CERTIFICATION OF CONFORMITY ...
Страница 138: ...Page 136 IOM ROOF TOP FLEXY Series 180 kW GAS BURNER CE CERTIFICATION OF CONFORMITY ...
Страница 139: ...IOM ROOF TOP FLEXY Series Page 137 INSULATION FIRE CLASS ...
Страница 140: ...Page 138 IOM ROOF TOP FLEXY Series INSULATION FIRE CLASS ...
Страница 141: ......