IOM / ROOF-TOP FLEXY™ Series - Page 119
041
register time set to 5 seconds. In addition, if the antifreeze thermostat is opened, the 3rd safety
level is immediately automatically maintained. In this case, manual resetting of the thermostat
followed by the CLIMATIC™ is obligatory
Room Overtemperature Safety System
Upper Room Air Limit
If the room temperature is greater than or equal to the setpoint
[C40]
, the safety system is
activated. It automatically cuts out at a temperature lower than 3°C below this setpoint.
Lower Room Air Limit
If the room temperature is less than or equal to the setpoint
[C39]
, the safety system is activate
Faulty Electrical Heater Batteries
The electrical heater battery safety thermostats act directly on the heater stage contactors.
This information is fed to the CLIMATIC™ via auxiliary contacts.
If the CLIMATIC™ gives the order to the heater to operate and if 5 seconds later the auxiliary
contact is still open, the heat safety system is activated and stops the electrical heater assembly.
This safety system is automatically locked-out. In this case a manual reset is obligatory.
Note: This fault is also displayed in the event of a contact "shunt".
Faulty Gas Burners
If there is a fault with the gas control boxes the heat safety system is activated and stops the
respective burner.
This safety system automatically cuts out on the CLIMATIC™ and the control unit must be
manually reset.
Faulty Humidifier (Flexy Only)
If there is a fault with the gas control unit for more than a minute, the safety system is activated
and stops the humidifier.
This safety system is automatically locked-out. In this case a manual reset is obligatory.
Room Humidity Safety System
Lower Room Limit
If the room humidity is less than or equal to the setpoint
[C41]
or
[C42]
, the safety system is
activated. It automatically cuts out at a humidity of 3% above this setpoint.
Upper Room Limit
If the room humidity is greater than or equal to the setpoint
[C43]
or
[C44]
, the safety system is
activated. It automatically cuts out at a humidity of 3% below this setpoint.
Faulty Pump
The internal protection of the water pump motor acts directly on the pump contactor. This information is
transmitted to the CLIMATIC™ via an auxiliary contact of the contactor.
If the CLIMATIC™ gives the pump the order to operate and if 5 seconds later the auxiliary contact
remains open, the safety system is activated and stops the pump.
The safety system is immediately automatically locked out. In this case, manual resetting is obligatory.
Note: This error is also displayed in the event of a "shunt" of the auxiliary contact of the contactor.
SAFETY AND ERROR CODES
023
013
011
031
014
015
032
033
Содержание ROOFTOP FLEXY FCA 100
Страница 1: ...INSTALLATION OPERATING MAINTENANCE MANUAL ROOFTOP FLEXY English August 2003 ...
Страница 2: ......
Страница 33: ...IOM ROOF TOP FLEXY Series Page 31 AIR FLOW BALANCING AT 12 12 FAN ...
Страница 34: ...Page 32 IOM ROOF TOP FLEXY Series AIR FLOW BALANCING AT 15 15 FAN ...
Страница 35: ...IOM ROOF TOP FLEXY Series Page 33 AIR FLOW BALANCING AT 18 13 ...
Страница 36: ...Page 34 IOM ROOF TOP FLEXY Series AIR FLOW BALANCING AT 18 18 FAN ...
Страница 37: ...IOM ROOF TOP FLEXY Series Page 35 AIR FLOW BALANCING RDN 450 FAN ...
Страница 38: ...Page 36 IOM ROOF TOP FLEXY Series AIR FLOW BALANCING ADN 355 FAN ...
Страница 39: ...IOM ROOF TOP FLEXY Series Page 37 AIR FLOW BALANCING ADN 400 FAN ...
Страница 40: ...Page 38 IOM ROOF TOP FLEXY Series AIR FLOW BALANCING ADN 450 FAN ...
Страница 56: ...Page 54 IOM ROOF TOP FLEXY Series GAS BURNERS 60 KW BURNER FOR FGX 60 AND 70 MODELS 1 2 Figure 63 ...
Страница 57: ...IOM ROOF TOP FLEXY Series Page 55 GAS BURNER 120 KW BURNER FOR FGX 60 70 AND 100 MODELS 1 2 3 Figure 64 ...
Страница 58: ...Page 56 IOM ROOF TOP FLEXY Series 180 KW BURNER FOR FGX 120 AND 140 MODELS GAS BURNER 1 2 3 Figure 65 ...
Страница 104: ...Page 102 IOM ROOF TOP FLEXY Series ELECTRICAL WIRING DIAGRAMS MAIN CURRENT DIAGRAM ...
Страница 106: ...Page 104 IOM ROOF TOP FLEXY Series ELECTRICAL WIRING DIAGRAMS CLIMATIC CONTROLLER ...
Страница 107: ...IOM ROOF TOP FLEXY Series Page 105 ELECTRICAL WIRING DIAGRAMS CLIMATIC INPUT FC FH FX Confort Set Point GTC ...
Страница 108: ...Page 106 IOM ROOF TOP FLEXY Series ELECTRICAL WIRING DIAGRAMS CLIMATIC INPUT FG FD ...
Страница 111: ...IOM ROOF TOP FLEXY Series Page 109 ELECTRICAL WIRING DIAGRAMS WIRING DIAGRAM GAS BURNER 33 60 120 Kw ...
Страница 112: ...Page 110 IOM ROOF TOP FLEXY Series ELECTRICAL WIRING DIAGRAMS GAS BURNER 180 Kw ...
Страница 132: ...Page 130 IOM ROOF TOP FLEXY Series ISO 9001 CERTIFICATION ...
Страница 133: ...IOM ROOF TOP FLEXY Series Page 131 PED CERTIFICATION OF CONFORMITY ...
Страница 134: ...Page 132 IOM ROOF TOP FLEXY Series GLASS WOOL FIRE CLASS ...
Страница 135: ...IOM ROOF TOP FLEXY Series Page 133 33 kW GAS BURNER CE CERTIFICATION OF CONFORMITY ...
Страница 136: ...Page 134 IOM ROOF TOP FLEXY Series 60 kW GAS BURNER CE CERTIFICATION OF CONFORMITY ...
Страница 137: ...IOM ROOF TOP FLEXY Series Page 135 120 kW GAS BURNER CE CERTIFICATION OF CONFORMITY ...
Страница 138: ...Page 136 IOM ROOF TOP FLEXY Series 180 kW GAS BURNER CE CERTIFICATION OF CONFORMITY ...
Страница 139: ...IOM ROOF TOP FLEXY Series Page 137 INSULATION FIRE CLASS ...
Страница 140: ...Page 138 IOM ROOF TOP FLEXY Series INSULATION FIRE CLASS ...
Страница 141: ......