Page 62 - IOM / ROOF-TOP FLEXY™ Series
USING THE KP02 MAINTENANCE CONTROL DISPLAY
LIST OF SETPOINTS (LF 20 - APRIL 2002)
1st Level
Mini. Factory Maxi.
C 000
[Kp02] Password, technician level
0
#
255
C 001
[Kp17] [Mode] Required room temperature (in °c).
This value corresponds to the middle of the dead zone - (active for
Day mode only)
C
051 21.0°C C
050
C 002
[Kp17] Forced occupied mode (Day) –
This action deactivates automatically when the clock first pass
midnight - Yellow led lit
Off Off On
C 003
[Kp17] Cancels the override of day or night modes- Yellow led
flashing
Off Off On
C 004
[Kp17] Forced unoccupied mode (Night) –
This action automatically deactivates when the clock pass midnight
for the second time –
Yellow led off
Off Off On
C 005
[Reset] Fault reset
Off Off On
C 006
[On / Off] Remote control, On / Off unit
Off Off On
C 007
[Kp02] Selection of the memory number for the defaults to be
visualized
1 # 5
C 008
[Kp02] [Mode] Mode selection for the visualization and the adjustment
of the settings
0 = Day,
1 =
Week-End,
2 = Night,
3 =
not used,
4 = Morning,
5 =
Midday,
6 = Evening
7 =
BMS
0 # 7
C 009
[Mode] Day of the week, Start of mode - (active for the Week-End
mode)
1 # 7
C 010
[Mode] Hour, Start of mode - (active for the modes Week-End, Night,
Morning, Midday, Evening)
0 h
# h
22 h
C 011
[Mode] Minute, Start of mode - (active for the modes Week-end,
Night, Morning, Midday, Evening)
0 m
# m
59 m
C 012
[Mode] Day of the week, End of mode - (active for the Week-End
mode)
1 # 7
C 013
[Mode] Hour, End of mode - (active for the modes Week-End,
Morning, Midday, Evening)
0 h
# h
23 h
C 014
[Mode] Minute, End of mode - (active for the modes Week-End,
Morning, Midday, Evening)
0 m
# m
59 m
C 015
[Mode] Required maximum room temperature (in °c) - Cooling set
point
8.0 c
# c
35.0 c
C 016
[Mode] Required minimum room temperature (in °c) - Heating set
point
8.0 c
# c
35.0 c
C 017
[Mode] Selection of humidity control mode
[Off] The relative humidity set points are taken into account (in %)
[On] The absolute humidity set points are taken into account - (in
g/kg)
Off Off On
C 018
[Mode] Required maximum room relative humidity (in %) –
Dehumidification set point
0 %
# %
100 %
C 019
[Mode] Required maximum room absolute humidity (in g/kg) –
Dehumidification set point
0.0 g/kg
# g/kg
30.0 g/kg
C 020
[Mode] Required minimum room relative humidity (in %) –
Humidification set point
0 %
# %
100 %
Содержание ROOFTOP FLEXY FCA 100
Страница 1: ...INSTALLATION OPERATING MAINTENANCE MANUAL ROOFTOP FLEXY English August 2003 ...
Страница 2: ......
Страница 33: ...IOM ROOF TOP FLEXY Series Page 31 AIR FLOW BALANCING AT 12 12 FAN ...
Страница 34: ...Page 32 IOM ROOF TOP FLEXY Series AIR FLOW BALANCING AT 15 15 FAN ...
Страница 35: ...IOM ROOF TOP FLEXY Series Page 33 AIR FLOW BALANCING AT 18 13 ...
Страница 36: ...Page 34 IOM ROOF TOP FLEXY Series AIR FLOW BALANCING AT 18 18 FAN ...
Страница 37: ...IOM ROOF TOP FLEXY Series Page 35 AIR FLOW BALANCING RDN 450 FAN ...
Страница 38: ...Page 36 IOM ROOF TOP FLEXY Series AIR FLOW BALANCING ADN 355 FAN ...
Страница 39: ...IOM ROOF TOP FLEXY Series Page 37 AIR FLOW BALANCING ADN 400 FAN ...
Страница 40: ...Page 38 IOM ROOF TOP FLEXY Series AIR FLOW BALANCING ADN 450 FAN ...
Страница 56: ...Page 54 IOM ROOF TOP FLEXY Series GAS BURNERS 60 KW BURNER FOR FGX 60 AND 70 MODELS 1 2 Figure 63 ...
Страница 57: ...IOM ROOF TOP FLEXY Series Page 55 GAS BURNER 120 KW BURNER FOR FGX 60 70 AND 100 MODELS 1 2 3 Figure 64 ...
Страница 58: ...Page 56 IOM ROOF TOP FLEXY Series 180 KW BURNER FOR FGX 120 AND 140 MODELS GAS BURNER 1 2 3 Figure 65 ...
Страница 104: ...Page 102 IOM ROOF TOP FLEXY Series ELECTRICAL WIRING DIAGRAMS MAIN CURRENT DIAGRAM ...
Страница 106: ...Page 104 IOM ROOF TOP FLEXY Series ELECTRICAL WIRING DIAGRAMS CLIMATIC CONTROLLER ...
Страница 107: ...IOM ROOF TOP FLEXY Series Page 105 ELECTRICAL WIRING DIAGRAMS CLIMATIC INPUT FC FH FX Confort Set Point GTC ...
Страница 108: ...Page 106 IOM ROOF TOP FLEXY Series ELECTRICAL WIRING DIAGRAMS CLIMATIC INPUT FG FD ...
Страница 111: ...IOM ROOF TOP FLEXY Series Page 109 ELECTRICAL WIRING DIAGRAMS WIRING DIAGRAM GAS BURNER 33 60 120 Kw ...
Страница 112: ...Page 110 IOM ROOF TOP FLEXY Series ELECTRICAL WIRING DIAGRAMS GAS BURNER 180 Kw ...
Страница 132: ...Page 130 IOM ROOF TOP FLEXY Series ISO 9001 CERTIFICATION ...
Страница 133: ...IOM ROOF TOP FLEXY Series Page 131 PED CERTIFICATION OF CONFORMITY ...
Страница 134: ...Page 132 IOM ROOF TOP FLEXY Series GLASS WOOL FIRE CLASS ...
Страница 135: ...IOM ROOF TOP FLEXY Series Page 133 33 kW GAS BURNER CE CERTIFICATION OF CONFORMITY ...
Страница 136: ...Page 134 IOM ROOF TOP FLEXY Series 60 kW GAS BURNER CE CERTIFICATION OF CONFORMITY ...
Страница 137: ...IOM ROOF TOP FLEXY Series Page 135 120 kW GAS BURNER CE CERTIFICATION OF CONFORMITY ...
Страница 138: ...Page 136 IOM ROOF TOP FLEXY Series 180 kW GAS BURNER CE CERTIFICATION OF CONFORMITY ...
Страница 139: ...IOM ROOF TOP FLEXY Series Page 137 INSULATION FIRE CLASS ...
Страница 140: ...Page 138 IOM ROOF TOP FLEXY Series INSULATION FIRE CLASS ...
Страница 141: ......