BLOWER DATA
EL296UH070XV36B BLOWER PERFORMANCE (less filter)
SINGLE SIDE RETURN AIR
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
First Stage Heating Speed - cfm
Second Stage Heating Speed - cfm
+24%
1090
1205
+18%
1025
1165
+12%
960
1090
+6%
890
1045
Factory Default
815
975
–6%
755
895
–12%
720
810
–18%
675
750
COOLING
1
Cooling Speed
DIP Switch
Settings
First Stage Cooling Speed - cfm
Second Stage Cooling Speed - cfm
Low
Medium-Low Medium-High
2
High
Low
Medium-Low Medium-High
2
High
+
590
705
805
955
840
1050
1205
1355
Factory Default
540
640
725
820
750
945
1130
1230
–
500
580
665
720
685
805
990
1110
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specific DIP Switch Settings.
2
Factory default setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT.
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is selectable at 28% and 38% of the selected second stage cooling speed - minimum 250 cfm.
Lennox iHarmony
®
Zoning System Applications - Minimum blower speed is 250 cfm.
EL296UH070XV36B BLOWER MOTOR WATTS (COOLING)
1
Cooling Speed
DIP Switch
Settings
Motor Watts @ Various External Static Pressures - in. wg.
First Stage
Second Stage
0
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
0
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
+ Setting
Cooling
Speed
Low
17
29
48
61
73
94
100 123 130 63
84 104 117 142
160
174 208
215
245
255
Med-low
30
50
66
79 107 128 137
159
178
121
137
165 195 213 239
257 283
303 329
342
Med-High
51
70
92 106
127
150
170 184 207
195
214 243 268
290
324 348 370 387 409 434
High
88
109
134
150
184
201 221
243
265
294
309
344 372
399
421 445 474 495
520 532
Factory Default
Cooling
Speed
Low
12
25
38
52
66
83
96 105
117 43
65
75
98
120 139 152
170
192 212
228
Med-low
22
41
55
70
86
103 123
141 154 88
106 130 150
173 197
220 239 259
276 297
Med-High
36
55
75
90
107
129 152
167 184 142
161
187
211 239 263
287 307
332 352 369
High
57
76
99 116 135 153
176 197
213 220 236
267 294
323
342 364 382 411 436 455
– Setting
Cooling
Speed
Low
8
22
32
50
60
77
86
100 116 31
48
63
83
102 122
137
150 166
188
203
Med-low
19
32
47
63
77
93 103 120 133 53
75
91 111 129 152 169
188
210
227
251
Med-High
25
42
58
74
90 109 131
143 154
101 120
141 170
190 215 233 256
274 298 317
High
37
56
76
95 115 135 153
173
192
157 177
201
224 254 277
303 321
346
362
385
Содержание EL296UH045XV36B
Страница 89: ...Page 89 VII Wiring and Sequence of Operation Ignition Control 103130 05 EL296 Schematic Diagram...
Страница 90: ...Page 90 Ignition Control 103130 05 and Blower Drive EL296 Units With Blower Drive...
Страница 91: ...Page 91 Ignition Control 107045 01...
Страница 92: ...Page 92 Ignition Control 107045 01 and Blower Drive...