Page 8
BLOWER DATA
EL296UH070XV36B BLOWER PERFORMANCE (less filter)
BOTTOM RETURN AIR
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
First Stage Heating Speed - cfm
Second Stage Heating Speed - cfm
+24%
1095
1220
+18%
1035
1170
+12%
985
1120
+6%
915
1055
Factory Default
850
995
–6%
835
915
–12%
755
845
–18%
695
810
COOLING
1
Cooling Speed
DIP Switch
Settings
First Stage Cooling Speed - cfm
Second Stage Cooling Speed - cfm
Low
Medium-Low Medium-High
2
High
Low
Medium-Low Medium-High
2
High
+
600
740
840
970
860
1060
1215
1365
Factory Default
555
665
770
855
810
960
1130
1265
–
500
600
680
790
705
840
1005
1140
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specific DIP Switch Settings.
2
Factory default setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT.
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is selectable at 28% and 38% of the selected second stage cooling speed - minimum 250 cfm.
Lennox iHarmony
®
Zoning System Applications - Minimum blower speed is 250 cfm.
EL296UH070XV36B BLOWER MOTOR WATTS (COOLING)
1
Cooling Speed
DIP Switch
Settings
Motor Watts @ Various External Static Pressures - in. wg.
First Stage
Second Stage
0
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
0
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
+ Setting
Cooling
Speed
Low
22
36
51
60
80
95 101
117 138 68
88
105 129 152 169
198 214
231
244 274
Med-low 37
57
75
89
106
127 148 168 182
121
144 168
192 211
243
262
287
305 329
358
Med-High
62
85
97
122
144 164 180
203 220 213 231 259
285
311
328 357 374 397 419 445
High
88
115 132 155
176
203 233
240 274 304
322 359
379 411 442 458 486
502
527 554
Factory Default
Cooling
Speed
Low
16
29
42
55
71
82
98
112 120 52
69
86 107
122
146
165
183
199 212 229
Med-low
26
41
63
79
88
112
128 145
159
89 108
135 151
174 198
223
247 268 288 298
Med-High
39
62
77
96
117 140
156
180
196 151
173
201 225
243
266
289
313 339
368 383
High
65
84 104
125
148
166
178
206 225
237
256
284
303
328 343 374
395
421 435 454
– Setting
Cooling
Speed
Low
11
21
35
53
64
75
82
95 113
34
50
67
86
106 121
141
159
174 186
201
Med-low
21
36
51
66
81
92
107 127 141 64
85
100
114 145
160
182
206 219
237
251
Med-High
35
48
66
82 104 118 137 146
159 101 125
143 171
193 211
242 258 282 304
330
High
43
60
82
100 123
144
159
174 197
161
188
211 229
258 277 307 327 354 379 404