Page 19
BLOWER DATA
EL296UH110XV48C BLOWER PERFORMANCE (less filter)
BOTTOM RETURN AIR
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
First Stage Heating Speed - cfm
Second Stage Heating Speed - cfm
+24%
1470
1605
+18%
1450
1495
+12%
1385
1445
+6%
1295
1385
Factory Default
1225
1305
–6%
1160
1225
–12%
1090
1150
–18%
1035
1070
COOLING
1
Cooling Speed
DIP Switch
Settings
First Stage Cooling Speed - cfm
Second Stage Cooling Speed - cfm
Low
Medium-Low Medium-High
2
High
Low
Medium-Low Medium-High
2
High
+
810
980
1085
1235
1100
1325
1530
1760
Factory Default
760
875
1010
1135
1025
1205
1405
1565
–
695
805
905
1040
920
1080
1260
1440
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specific DIP Switch Settings.
2
Factory default setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT.
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is selectable at 28% and 38% of the selected second stage cooling speed - minimum 380 cfm.
Lennox iHarmony
®
Zoning System Applications - Minimum blower speed is 380 cfm.
EL296UH110XV48C BLOWER MOTOR WATTS (COOLING)
1
Cooling Speed
DIP Switch
Settings
Motor Watts @ Various External Static Pressures - in. wg.
First Stage
Second Stage
0
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
0
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
+ Setting
Cooling
Speed
Low
37
59
80
96 119
140
166
182
203 92 122
147 173
201 230 255
286
313
340
369
Med-low 57
85
105 132 153
175
206 230 256 136
170 204 237 275
311 351
382 411 447 481
Med-High 87
115
141 167
195 221
245 277
302 215 239
289 338 385 416 452 494
523 562 600
High
115 152
175
213
240 275
309
338 376
331
378 427 465 514
559
589 658
693
738 793
Factory Default
Cooling
Speed
Low
33
53
72
92 111 129
146 167
191 69
94 118 145 168
201 225 250
272 297
321
Med-low 40
70
85
110 135 155
185
200 230
108 145
166 201 226 262 292 321
358 383 417
Med-High 64
91 113
140
162 191
218 242
266 166 199
240 275
315
345 387 418 456 490
526
High
96 129 151
179
205 239
264 294
322 232
267
310 353 393
434 471
506
546 589
625
– Setting
Cooling
Speed
Low
27
45
65
83
99 116 139 155
176 49
75
97 117 144 171
191 219
246 268 286
Med-low 38
59
81
98
119
137 158 184
202
89 117 144
169
197
223
248 279
305 333 360
Med-High 46
73
93 115
142 164 188
211
241
120 156
182
219
249 286
321 351
385 415 449
High
71
97
122
149 172
205
228 254 277 184 217
256 300
337
369
409 443 483 517 554
Содержание EL296UH045XV36B
Страница 89: ...Page 89 VII Wiring and Sequence of Operation Ignition Control 103130 05 EL296 Schematic Diagram...
Страница 90: ...Page 90 Ignition Control 103130 05 and Blower Drive EL296 Units With Blower Drive...
Страница 91: ...Page 91 Ignition Control 107045 01...
Страница 92: ...Page 92 Ignition Control 107045 01 and Blower Drive...