Page 7
BLOWER DATA
EL296UH045XV36B BLOWER PERFORMANCE (less filter)
SINGLE SIDE RETURN AIR WITH OPTIONAL RETURN AIR BASE
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
First Stage Heating Speed - cfm
Second Stage Heating Speed - cfm
+24%
895
1115
+18%
850
1070
+12%
795
1030
+6%
755
980
Factory Default
715
920
–6%
665
850
–12%
645
805
–18%
595
740
COOLING
1
Cooling Speed
DIP Switch
Settings
First Stage Cooling Speed - cfm
Second Stage Cooling Speed - cfm
Low
Medium-Low Medium-High
2
High
Low
Medium-Low Medium-High
2
High
+
605
730
845
965
895
1060
1185
1345
Factory Default
550
660
760
875
820
975
1105
1215
–
490
610
685
770
720
860
1015
1125
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specific DIP Switch Settings.
2
Factory default setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT.
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is selectable at 28% and 38% of the selected second stage cooling speed - minimum 250 cfm.
Lennox iHarmony
®
Zoning System Applications - Minimum blower speed is 250 cfm.
EL296UH045XV36B BLOWER MOTOR WATTS (COOLING)
1
Cooling Speed
DIP Switch
Settings
Motor Watts @ Various External Static Pressures - in. wg.
First Stage
Second Stage
0
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
0
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
+ Setting
Cooling
Speed
Low
20
36
57
77
99 111 133
149 168 54
82
99 130
157 180
210
238
259
282 308
Med-low 28
50
72
97 118 141
161
184 207
103 122 159
189
220 250
277
303 331 353
382
Med-High 45
74
94
121
148 170
201 221
254
162
188 227
259
283 318
353
383 414 435 473
High
73
98
130
157 186
219
247 274 294 224 249 283
326 366
398 433 473 491
529
545
Factory Default
Cooling
Speed
Low
14
32
47
62
82
100 119 132
149 38
63
82
109 131 161
176
210 231 250
272
Med-low
20
40
60
80
105 120
145
160
180 74
96 125 152
182 214 242 268 289
313 335
Med-High
31
57
76 104
126 153
170
196 223 123
143 180
215
240 272
300 326 359
379 408
High
51
81
98 128
156
178 208
235
258 173
206
240
261
297 337
365
402 431 456 490
– Setting
Cooling
Speed
Low
8
27
38
54
73
88
106 119
137 27
46
71
92 112 133 155
178
195
214 242
Med-low
21
37
57
77
100 112
134 149
169
48
75
95 122
149 171
201 222 255
271 294
Med-High
25
44
67
86
110
127
150
170 187 84
105 139
167 197
229 256
284
305 330 355
High
34
60
79
106
128 157 173
203
227
130 153
188
225
248 282 307
339
371
392
420
Содержание EL296UH045XV36B
Страница 89: ...Page 89 VII Wiring and Sequence of Operation Ignition Control 103130 05 EL296 Schematic Diagram...
Страница 90: ...Page 90 Ignition Control 103130 05 and Blower Drive EL296 Units With Blower Drive...
Страница 91: ...Page 91 Ignition Control 107045 01...
Страница 92: ...Page 92 Ignition Control 107045 01 and Blower Drive...