Page 25
BLOWER DATA
EL296UH135XV60D BLOWER PERFORMANCE (less filter)
SINGLE SIDE RETURN AIR
− Air volumes in
bold
require Optional Return Air Base
and
field fabricated transition to accommodate
20 x 25 x 1 in. air filter in order to maintain proper air velocity.
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
First Stage Heating Speed - cfm
Second Stage Heating Speed - cfm
+24%
1725
2070
+18%
1635
1975
+12%
1555
1900
+6%
1470
1815
Factory Default
1405
1715
–6%
1325
1610
–12%
1250
1525
–18%
1185
1420
COOLING
1
Cooling Speed
DIP Switch
Settings
First Stage Cooling Speed - cfm
Second Stage Cooling Speed - cfm
Low
Medium-Low Medium-High
2
High
Low
Medium-Low Medium-High
2
High
+
1130
1275
1405
1555
1595
1805
1975
2180
Factory Default
1040
1185
1280
1415
1450
1625
1840
2000
–
950
1080
1185
1300
1310
1480
1655
1840
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specific DIP Switch Settings.
2
Factory default setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT.
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is selectable at 28% and 38% of the selected second stage cooling speed - minimum 450 cfm.
Lennox iHarmony
®
Zoning System Applications - Minimum blower speed is 450 cfm.
EL296UH135XV60D BLOWER MOTOR WATTS (COOLING)
1
Cooling Speed
DIP Switch
Settings
Motor Watts @ Various External Static Pressures - in. wg.
First Stage
Second Stage
0
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
0
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
+ Setting
Cooling
Speed
Low
87
123
145 178
213
241 270
299
340 244 283
316 356
418 453 491
529
570 598 642
Med-low
131 161
197 228
266 309
334
361 392
340 377 425 477 528 570
615 661
702 732 789
Med-High 168
201
248 283
319
357 385 438 468 479
523
587
615 665
717 762 812 860 907
955
High
239
283
316 356
418 453 491
529
570
661
703 770 822 862 941 994 1037 1098
1136
1177
Factory Default
Cooling
Speed
Low
67
97
126 150
177
210 239
264
296 162 201
243 273
311 353
384 426 469
505
541
Med-low
100 130 165 190 225 255 290 320 350
245 281
322
374 433 465
509
546
596 629 666
Med-High
132 169
198 228 267
306 333
370 401 370 404 458
516 559 600
657
696
746 783 816
High
163 201
243 273
311 353
384 426 469
502
544
601 639
683 744 791 845 884 927
961
– Setting
Cooling
Speed
Low
57
84 107
133
157 177
206 236 259 126
158
192 226 265 290 326 360 392
424 459
Med-low 73
102 132
158 185
221 252
273
302
175
213 252 291
338
366
417 453 487
521
572
Med-High
100 130
167
193 225
257
290 320
354 254
292
343 377 431 475
521 566
604 642 678
High
126
158
192 226 265 290 326 360 392
370 404 458
516 559 600
657
696
746 783 816