Table 12. CORE Control System Unit Parameters
Control
Parameter
No
Screen Name
Parameter Short
Description
Control Value
Units
Description
Min.
Default
Max.
328
BPC PID P
CONST
Building Pressure
Control PID P
Constant
0
100
127
Count
BPC PID Proportional Constant
329
BPC PID I
CONST
Building Pressure
Control PID I
Constant
0
30
127
Count
BPC PID Integral Constant
330
GP A02 MODE
General Purpose
A02 Mode
0
0
12
Mode
Selection
•
1 - Occupied - PID set point A;
Unoccupied - PID set point B
•
2 - Occupied - PID set point A;
Unoccupied -Staged output B
•
3 - Occupied - Staged output A;
Unoccupied - PID set point B
•
4 - Occupied - Staged output A;
Unoccupied - Staged output B
•
5 - Blower On - PID set point A;
Blower Off - PID set point B
•
6 - Blower On - PID set point A;
Blower Off - Staged output B
•
7 - Blower On - Staged output A;
Blower Off - PID set point B
•
8 - Blower On - Staged output A;
Blower Off - Staged output B
•
9 - DI2 on - PID set point B (1); DI3
on - PID set point A (2); Otherwise
off.
•
10 - DI2 on - PID set point B
(1); DI3 on - Staged Output A (2);
Otherwise off.
•
11 - DI2 on - PID set point B (1);
DI3 on - Staged Output A (2);
Otherwise off.
•
12 - Reserved
•
(1) -DI3 (on M3) doesn’t matter
•
(2) -DI2 (on M3) is off
331
GP A02 SP A
General Purpose
A02 Set Point A
0
0
100
%
Analog output channel 2, set point A.
332
GP A02 SP B
General Purpose
A02 Set Point B
0
0
100
%
Analog output channel 2, set point B.
333
GP A02 STG A
General Purpose
A02 Stage A
0
0
100
%
Analog output channel 2, stage A
334
GP A02 STG B
General Purpose
A02 Stage B
0
0
100
%
Analog output channel 2, stage B
335
GP A02 OUTPUT General Purpose
A02 Output
0
0
1
Selection
•
0 = PWM
•
1 = 0-10 VDC
336
GP A02 PWM
FREQ
General Purpose
A02 Pulse-Width
Modulation
Frequency
50
200
2000
Hz
Analog output PWM frequency.
337
GP A02 KP
General Purpose
A02 Proportional
Constant for PID
0
0
100
Count
Analog output channel 2 PID loop
proportional constant.
338
GP A02 KI
General Purpose
A02 Integral
Constant for PID
0
0
100
Count
Analog output channel 2 PID loop integral
constant.
340
GP A02 MIN
OUPUT
General Purpose
A02 Minimum
Output
0
0
100
%
Analog output channel 2 minimum output.
341
GP A02 MAX
OUPUT
General Purpose
A02 Maximum
Output
0
100
100
%
Analog output channel 2 maximum
output.
Содержание Core Unit Controller
Страница 75: ...75 Table 15 J297 TSTAT Inputs and Service Relays Table 16 J298 Analog Sensors Table 17 J378 Duct Sensors ...
Страница 77: ...77 Table 22 J383 Ultra Evaporators Table 23 J384 Economizer ...
Страница 80: ...80 Table 32 J393 Gas Heat Table 33 J393 Electric Heat Table 34 J394 ReHeat Table 35 J388 C Box ...
Страница 81: ...81 Table 36 J389 C Box Table 37 J395 Power In Table 38 J358 MODUS Vs COMPR Table 39 J413 Modbus ...
Страница 85: ...85 Table 54 J406 A12 M4 Control J406 A12 Table 55 J374 Versions 1 through 4 ...
Страница 86: ...86 Table 56 J10 GV1 S18 J10 S18 Table 57 J408 GV1 S47 J408 Table 58 J412 MODUS 2 Table 59 J411 MODUS 1 ...
Страница 91: ...91 ...