65
Table 12. CORE Control System Unit Parameters
Control
Parameter
No
Screen Name
Parameter Short
Description
Control Value
Units
Description
Min.
Default
Max.
228
CL LO CFM
CALIB
Advanced Airflow
Low Speed
Calibration
-1200
0
1200
Count
•
Applicable to Standard Efficiency 3-
to 6-ton units only.
•
If the absolute value of this
Parameter is greater than Parameter
17. then this is not considered in
target calculation.
229
CL HI SPD CALIB
Advanced
Airflow Hi Speed
Calibration
-1200
0
1200
Count
•
Applicable to Standard Efficiency 3-
to 6-ton units only.
•
If the absolute value of this
Parameter is greater than Parameter
14, then this is not considered in
target calculation
230
CL MED LO SPD
CALIB
Advanced Airflow
Medium Speed
Calibration
-1200
0
1200
Count
Applicable to Standard Efficiency 3- to
6-ton units only.
231
CL MED HI SPD
CALIB
Advanced Airflow
Medium High
Speed Calibration
-1200
0
1200
Count
Applicable to Standard Efficiency 3- to
6-ton units only.
232
HEAT CFM
CALIB
Advanced Airflow
Heat CFM
Calibration
-1200
0
1200
Count
Applicable to Standard Efficiency 3- to
6-ton units only.
233
VENT CFM CALB
Advanced
Airflow Vent CFM
Calibration
-1200
0
1200
Count
Applicable to Standard Efficiency 3- to
6-ton units only.
234
LO SP CFM
ALARM SP
Advanced Airflow
Low Speed CFM
Alarm Set Point
15
25
100
%
Applicable to Standard Efficiency 3- to
6-ton units only.
235
LO SP CFM
ALARM EU
Advanced Airflow
Low Speed CFM
Alarm Evaluation
0
1800
3600
Seconds
Applicable to Standard Efficiency 3- to
6-ton units only.
236
NO AIRFLOW
ALARM EU
Advanced Airflow
No Airflow Alarm
Evaluation
0
20
300
Count
Applicable to Standard Efficiency 3- to
6-ton units only.
237
OUTDOOR AIR
TARGET
Outdoor Air Target
0
0
750
CFM
Applicable to Standard Efficiency 3- to
6-ton units only.
238
OUTDOOR CFM
CALIB
Advanced Airflow
Outdoor CFM
Calibration
-600
0
600
Count
Applicable to Standard Efficiency 3- to
6-ton units only.
239
LO OD CFM
ALARM SP
Advanced Airflow
Outdoor CFM
Alarm Set Point
15
25
100
%
Applicable to Standard Efficiency 3- to
6-ton units only.
240
HI OD CFM
ALARM SP
Advanced
Air Flow High
Outdoor CFM
Alarm Set Point
15
25
100
%
Applicable to Standard Efficiency 3- to
6-ton units only.
241
MAX OD CFM
DCV SP
Advanced
Airflow Maximum
Outdoor CFM
Demand Control
Ventilation Set
Point
0
600 (3-ton
Unit)
800 (4-ton
Unit)
1000 (5-ton
Unit)
2400
CFM
Applicable to Standard Efficiency 3- to
6-ton units only.
243
LO OD CFM
ALARM EU
Advanced Air
Flow Low Outdoor
CFM Alarm
Evaluation
0
1800
3600
Seconds
Applicable to Standard Efficiency 3- to
6-ton units only.
244
HI OD CFM
ALARM EU
Advanced
Air Flow High
Outdoor CFM
Alarm Evaluation
0
1800
3600
Seconds
Applicable to Standard Efficiency 3- to
6-ton units only.
245
OD DP ERR
ALARM EU
Advanced Airflow
Outdoor Air
Damper Error
Alarm Evaluation
0
1800
3600
Seconds
Applicable to Standard Efficiency 3- to
6-ton units only.
Содержание Core Unit Controller
Страница 75: ...75 Table 15 J297 TSTAT Inputs and Service Relays Table 16 J298 Analog Sensors Table 17 J378 Duct Sensors ...
Страница 77: ...77 Table 22 J383 Ultra Evaporators Table 23 J384 Economizer ...
Страница 80: ...80 Table 32 J393 Gas Heat Table 33 J393 Electric Heat Table 34 J394 ReHeat Table 35 J388 C Box ...
Страница 81: ...81 Table 36 J389 C Box Table 37 J395 Power In Table 38 J358 MODUS Vs COMPR Table 39 J413 Modbus ...
Страница 85: ...85 Table 54 J406 A12 M4 Control J406 A12 Table 55 J374 Versions 1 through 4 ...
Страница 86: ...86 Table 56 J10 GV1 S18 J10 S18 Table 57 J408 GV1 S47 J408 Table 58 J412 MODUS 2 Table 59 J411 MODUS 1 ...
Страница 91: ...91 ...