4
J386
J387
J388
J389
J390
J391 J392
J393
J395
J394
MODBUS
J413
LONTalk
Module
24VAC
Gnd
S-BUS SmartWire
™
System J304
Humidistat
Digital
Inputs
Smoke
24VAC
Gnd
24VAC
Thermostat
Service Relays
R + C
Spare
Analog
Inputs
Room
and RH
Sensors
Sensor
IAQ
TX
J358
Duct Sensor
J378
4-Character Seven
Segment LED
J379
J380
J381
J382
J383
J385
J384
J298
J297
J299
Sensor
IAQ
A11
HUM TMP
Sensor
Inputs
A12 C R
White Push
Button
Black Push
Button
Service Relays
P5
S-BUS
Factory Test
P2 Expansion
Card Connection
(C4)
CORE Unit Controller (A55)
Wireless Control (W4)
Figure 1. Lennox CORE Unit Controller Interfaces and LEDs Locations
• LED Indicators
NOTE:
CORE™ Control System features vary with the
type of rooftop unit in which the control is installed.
1.6. Lennox CORE Unit Controller -
Connections, Inputs / Outputs,
Jumpers, and LEDs Locations
THERMOSTAT COMMON ISOLATION - TSTAT_COM
Jumper
Thermostat (TSTAT) sensor commons are located on
connector P298 and may be isolated if they are powered
remotely. Remove jumper.
This jumper is located to the left of P297 connector. This
jumper would be removed only in unique situations where
the device supplying the thermostat signals to the CORE
Unit Controller has its own power source and does not share
a common reference voltage with the CORE unit controller.
Otherwise the jumper would remain installed across both
pins, as shipped from the factory.
A. HUMIDISTAT COMMON ISOLATION -
:
HMD_COM
Jumper
The humidity (HUM) sensor commons are located on
connector P298 and may be isolated if they are powered
remotely. Remove jumper. This jumper is located to the right
of P299 connector. This jumper would be removed only in
unique situations where the device supplying the thermostat/
humidistat signals to the CORE Unit Controller has its own
power source and does not share a common reference
voltage with the CORE Unit Controller. Otherwise the jumper
would remain installed across both pins, as shipped from the
factory.
b. W4 CONTROL - USb FLASH DRIVE INTERFACE
USAGE
The W4 Control uses a USB type A interface. This USB port is
used for verifying service, downloading reports, transferring
unit profiles and performing firmware updates.
On-site data collection requires use of either a USB flash
drive or download and shared from the CORE Service App.
Data written to the drive includes date, time, serial number,
catalog number, basic data, error code buffer, and unit
configuration.
C. S-bUS (SMARTWIRE
™
) (J304)
This is the L-connection interface. This is a R485 network
connection with other devices (NCP, comfort sensors, other
RTU, etc.).
D. MODbUS CONNECTION (J413)
This is a TIA-485 serial line over MODBUS (messaging
structure) communication. This connection is used for
multiple components.
E. CORE UNIT CONTROLLER LED INDICATORS
NOTE:
See “g. Local Interface - four character seven
segment LED - Status Codes” on page 5 for
further information.
Содержание Core Unit Controller
Страница 75: ...75 Table 15 J297 TSTAT Inputs and Service Relays Table 16 J298 Analog Sensors Table 17 J378 Duct Sensors ...
Страница 77: ...77 Table 22 J383 Ultra Evaporators Table 23 J384 Economizer ...
Страница 80: ...80 Table 32 J393 Gas Heat Table 33 J393 Electric Heat Table 34 J394 ReHeat Table 35 J388 C Box ...