Table 11. CORE Control System Alarm and Event Codes
SELECTED ALARMS (MARKED WITH * IN TAbLE RESULT IN THE CLOSURE OF THE SERVICE RELAY CONTACTS (DO1).
ALARM
CODE
DISPLAY MESSAGE
EVENT ACTION
188
INVERTER MAJOR
•
Alarming Value = Inverter error code
•
Possible alarming values for unit controller alarm 188 are:
>
21 - Peak DC current
>
22 - Maximum current reached lockout
>
23 - DC Link low voltage
>
26 - Locked Rotor
>
28 - DC Link high voltage
>
29 - Compressor over current
>
61 - Low outdoor ambient inverter lockout
>
62 - High Heat Sink Temperature lockout
>
75 - Low Input Voltage
•
No action required. Compressor stops for the duration of the minimum run time. Unit
shuts down after ten occurrences in one hour and Alarm 189 is initiated. Alarm 188
will automatically clear when inverter error clears.
•
Refer to trouble shooting guide in service manual for more information.
189
INVERTER FATAL
•
Alarming Value = Inverter error code
•
Possible alarming values for alarm 189 are 21, 22, 23, 26, 28, 29, 61, 62 and 75.
•
Alarm 189 will clear upon manual reset.
•
Refer to trouble shooting guide in service manual for more information.
190
INVERTER COMM
Unable to communicate with inverter. The unit controller will disable compressor operation.
Replace communication cable between inverter and CORE Unit Controller. If alarm
continues, replace CORE Unit Controller or inverter.
191
INVERTER VOLTAGE MISMATCH
The unit controller will disable compressor operation. Replace with correct inverter part.
192
HIGH TEMP S7 OPEN COMP1
Check temperature trip switch. Compressor is off. Also check charge, fans and coil. The
unit controller will clear the temperature trip alarm when corresponding compressor top
cap temperature trip switch is detected as closed. Compressor will not restart until the
corresponding temperature trip switch is closed and the minimum off delay has expired.
193
STRIKE3 HIGH TEMP S7 OPEN COMP1
The unit controller will disable compressor operation (lockout). Check switch, charge, fans
and coil. Default is three occurrences. Alarm will be automatically cleared after removal of
cooling demand.
194
CRITICAL LOSS CONDENSER
AIRFLOW
Critical Loss of Condenser Airflow
195
C1 CRITICAL LOSS OF CHARGE
Critical Loss of Charge Compressor 1. In Model L this is determined by temperature
readings from sensors on the coils.
196
C2 CRITICAL LOSS OF CHARGE
Critical Loss of Charge Compressor 2. In Model L this is determined by temperature
readings from sensors on the coils.
197
C3 CRITICAL LOSS OF CHARGE
Critical Loss of Charge Compressor 3. In Model L this is determined by temperature
readings from sensors on the coils.
198
C4 CRITICAL LOSS OF CHARGE
Critical Loss of Charge Compressor 4. In Model L this is determined by temperature
readings from sensors on the coils.
199
CRITICAL LOSS OF EVAPORATOR
AIRFLOW
Critical Loss of Evaporator Airflow
200
C1 NON OPERATING COMPRESSOR
Compressor 1 Not Operating
201
C2 NON OPERATING COMPRESSOR
Compressor 2 Not Operating
202
C3 NON OPERATING COMPRESSOR
Compressor 3 Not Operating
203
C4 NON OPERATING COMPRESSOR
Compressor 4 Not Operating
204
C1 TXV FAILED CLOSED
Compressor 1 TXV Failed Closed
205
C2 TXV FAILED CLOSED
Compressor 2 TXV Failed Closed
206
C3 TXV FAILED CLOSED
Compressor 3 TXV Failed Closed
207
C4 TXV FAILED CLOSED
Compressor 4 TXV Failed Closed
208
C1 MAJOR LOSS CHARGE
Major Loss of Charge Compressor 1
209
C2 MAJOR LOSS CHARGE
Major Loss of Charge Compressor 2
210
C3 MAJOR LOSS CHARGE
Major Loss of Charge Compressor 3
211
C4 MAJOR LOSS CHARGE
Major Loss of Charge Compressor 4
Содержание Core Unit Controller
Страница 75: ...75 Table 15 J297 TSTAT Inputs and Service Relays Table 16 J298 Analog Sensors Table 17 J378 Duct Sensors ...
Страница 77: ...77 Table 22 J383 Ultra Evaporators Table 23 J384 Economizer ...
Страница 80: ...80 Table 32 J393 Gas Heat Table 33 J393 Electric Heat Table 34 J394 ReHeat Table 35 J388 C Box ...
Страница 81: ...81 Table 36 J389 C Box Table 37 J395 Power In Table 38 J358 MODUS Vs COMPR Table 39 J413 Modbus ...
Страница 85: ...85 Table 54 J406 A12 M4 Control J406 A12 Table 55 J374 Versions 1 through 4 ...
Страница 86: ...86 Table 56 J10 GV1 S18 J10 S18 Table 57 J408 GV1 S47 J408 Table 58 J412 MODUS 2 Table 59 J411 MODUS 1 ...
Страница 91: ...91 ...