Table 12. CORE Control System Unit Parameters
Control
Parameter
No
Screen Name
Parameter Short
Description
Control Value
Units
Description
Min.
Default
Max.
151
HEAT STAGE4
DIFFER
Heating Stage 4
Differential
0
2
3
°F
•
Heating stage 4 differential
temperature. Used only with room
sensor applications.
•
Differential temperature must
greater than or equal to Parameter
150.
152
AUTO CHGOVR
DEADBND
Automatic
Changeover
Deadband
2
3
10
°F
•
Minimum auto changeover dead-
band temperature. Dead band
must be greater than or equal to
Parameter 142 plus Parameter 143.
•
Used in room sensor applications.
153
AUTO CHGOVR
DELAY
Automatic
Changeover
Delay
1
Default may
be altered at
factory test.
15
Minutes
Auto changeover time delay. Delay
between heating and cooling modes.
154
OCC BLOWER
MODE
Occupied Blower
Mode
AUTO-
CYCLES
Option
Blower control option for room sensor
applications during occupied periods.
•
Auto Cycle
: Blower cycles with
demand
•
On-Continuous 1
: blower is on
with either the occupancy sensor
or occupancy schedule indicates
occupied.
•
On-Continuous 2
: Blower is on only
when both the occupancy sensor
and occupancy scheduler indicates
occupied.
•
On-Continuous 3
: lower is on only
when both the occupancy sensor
and occupancy scheduler indicates
occupied. in addition, blower will be
on a minimum of 25% of the time
when occupancy scheduler indicates
occupied by the occupancy sensor
indicates not occupied. The 25%
minimum is achieved by turning
blower on for 30 minutes and off for
90 minutes.
155
FREECOOL
LOCKOUT SP
Free Cooling
Lockout Set Point
30
30
60
°F
•
Locks out free cooling when outdoor
temperature is below the set value.
•
Setting value to 29°F disables free
cooling lockout.
156
FRESH AIR
HEAT SP
See CORE System Application Guide for further details and to change the fresh air heat (FAH) set point. Modify the
set point only using the method described in the reference section.
157
FAH STAGE
DEADBAND
Fresh Air Heating
Stage Deadband
3
10
15
°F
Fresh Air Heating stage dead-band.
158
FAH MIN CYCLE
TIME
Fresh Air Heating
Minimum Cycle
Time
120
480
1800
Seconds
Fresh Air heating minimum cycle time.
159
FREE COOL
SUPPLY SP
Free Cooling
Supply Set Point
45
55
65
°F
Economizer modulates dampers to
maintain supply air temperature (RT6) at
this set point during free cooling. DACC
reset applies. See Parameter 207 -
Parameter 201
160
ECON FREECL
TEMP SP
Economizer
Free Cooling
Temperature Set
Point
40
60
75
°F
Outdoor Air Temperature is less than
Parameter Set Point between 41-75°F,
or when Outdoor Air temperature is less
than Return Air Temperature between
0-40°F.
161
ECON FRCL
TMP OFFSET
Economizer
Free Cooling
Temperature
Offset
0
10
40
°F
Economizer Free Cooling Temperature
Offset
162
ECON FREECL
ENTH SP
Economizer Free
Cooling Enthalpy
Set Point
10
12
19
mA
Economizer Free Cooling Enthalpy Set
Point
Содержание Core Unit Controller
Страница 75: ...75 Table 15 J297 TSTAT Inputs and Service Relays Table 16 J298 Analog Sensors Table 17 J378 Duct Sensors ...
Страница 77: ...77 Table 22 J383 Ultra Evaporators Table 23 J384 Economizer ...
Страница 80: ...80 Table 32 J393 Gas Heat Table 33 J393 Electric Heat Table 34 J394 ReHeat Table 35 J388 C Box ...
Страница 81: ...81 Table 36 J389 C Box Table 37 J395 Power In Table 38 J358 MODUS Vs COMPR Table 39 J413 Modbus ...
Страница 85: ...85 Table 54 J406 A12 M4 Control J406 A12 Table 55 J374 Versions 1 through 4 ...
Страница 86: ...86 Table 56 J10 GV1 S18 J10 S18 Table 57 J408 GV1 S47 J408 Table 58 J412 MODUS 2 Table 59 J411 MODUS 1 ...
Страница 91: ...91 ...