58
Table 12. CORE Control System Unit Parameters
Control
Parameter
No
Screen Name
Parameter Short
Description
Control Value
Units
Description
Min.
Default
Max.
140
UNOCC COOL
STPT
Unoccupied
Cooling Set Point
40
85
95
°F
•
Backup unoccupied cooling set
point.
•
Used if the communications link
is lost for 5 minutes between the
CORE Unit Controller and network
control panel. Used only in room
sensor applications.
•
Set point temperature must be
greater than or equal to Parameter
138 plus Parameter 152).
141
AFTERHOUR
OVRRD DLY
After Hours
Override Time
Delay
0
60
480
Minutes
•
After hours override timer.
•
Only used on room sensor
applications without a network
control panel.
142
HEAT STAGE
DEADBAND
Heat Stage
Deadband
1
1
3.75
°F
•
Heating dead-band. Used only with
CORE Unit Controller room sensor
applications.
•
Dead band must be less than or
equal to Parameter 152 minus
Parameter 143.
143
COOL STAGE
DEADBAND
Cool Stage
Deadband
1
1
3.75
°F
•
Cooling dead-band. Used only with
room sensor applications.
•
Dead band must be less than or
equal to Parameter 152 minus
Parameter 142.
144
COOL STAGE1
DIFFER
Cooling Stage 1
Differential
0
0.5
3
°F
•
Cooling stage 1 differential. Used
only with room sensor applications.
•
Differential temperature must be
less than or equal to Parameter 145.
145
COOL STAGE2
DIFFER
Cooling Stage 2
Differential
0
1
3
°F
•
Cooling stage 2 differential. Used
only with room sensor applications.
•
Differential temperature must be
greater than or equal to Parameter
144 and less than or equal to
Parameter 146.
146
COOL STAGE3
DIFFER
Cooling Stage 3
Differential
0
1.5
3
°F
•
Cooling stage 3 differential. Used
only with room sensor applications.
•
Differential temperature must be
greater than or equal to Parameter
145 and less than or equal to
Parameter 147.
147
COOL STAGE4
DIFFER
Cooling Stage 4
Differential
0
2
3
°F
•
Cooling stage 4 differential. Used
only with room sensor applications.
•
Differential temperature must be
greater than or equal to Parameter
146.
148
HEAT STAGE1
DIFFER
Heating Stage 1
Differential
0
0.5
3
°F
•
Heating stage 1 differential. Used
only with room sensor applications.
•
Differential temperature must be
less than or equal to Parameter 149.
149
HEAT STAGE2
DIFFER
Heating Stage 2
Differential
0
1
3
°F
•
Heating stage 2 differential. Used
only with room sensor applications.
•
Differential temperature must be
greater or equal to Parameter 148.
150
HEAT STAGE3
DIFFER
Heating Stage 3
Differential
0
1.5
3
°F
•
Heating stage 3 differential
temperature. Used only with room
sensor applications.
•
Differential temperature must be
greater than or equal to Parameter
149.
Содержание Core Unit Controller
Страница 75: ...75 Table 15 J297 TSTAT Inputs and Service Relays Table 16 J298 Analog Sensors Table 17 J378 Duct Sensors ...
Страница 77: ...77 Table 22 J383 Ultra Evaporators Table 23 J384 Economizer ...
Страница 80: ...80 Table 32 J393 Gas Heat Table 33 J393 Electric Heat Table 34 J394 ReHeat Table 35 J388 C Box ...
Страница 81: ...81 Table 36 J389 C Box Table 37 J395 Power In Table 38 J358 MODUS Vs COMPR Table 39 J413 Modbus ...
Страница 85: ...85 Table 54 J406 A12 M4 Control J406 A12 Table 55 J374 Versions 1 through 4 ...
Страница 86: ...86 Table 56 J10 GV1 S18 J10 S18 Table 57 J408 GV1 S47 J408 Table 58 J412 MODUS 2 Table 59 J411 MODUS 1 ...
Страница 91: ...91 ...