To position the external grids, proceed as follows: 
-  Fit the small eyelet of the spring, with the long stem, on 

the cap pin (on both components) (fig. 10/2). 

-   Fit the two caps (with spring), from the front part of the 

external grid, on the two housings, pulling until a click is heard 
(fig. 10/3) and attach the two chains to the large eyelet 
of the spring. 

-  Using one hand, grip the two chains connected to the grid. 
-   Bend the external grids back, gripping these with your 
 

free hand where the bend is and introducing your 

 

fingers inside the single fins (fig. 10/4). 
Introduce your arm into the pipe until the grid protrudes 
completely outwards. 

-   Allow the grid to reopen, being careful to keep your 

fingers inside the fins. 

-   Turn the grid until the fins are fully horizontal and tilted 

towards the outside. 

-   Pull the chain, tensioning the spring, and fasten the ring 

of the chain onto the pin of the inner washer (fig. 11). 

-   Using a pair of nippers, cut the excess chain links (fig. 

12). 

Warning:  If the external grating is accessible, to 
prevent the hazards resulting from its possible 
removal (insertion of the hands into the pipes and 
touching moving or powered parts) it is absolutely 
essential to fasten it to the wall with 4 anchor bolts 
with a diameter of 6 mm. 

 

2.3.4 

The air conditioner is equipped with a power supply cable 

Power supply 

and plug.  

    Connection 

If it is installed near an outlet, you need only plug it in. 

 

      In this case, it is important to make sure the outlet to which 
      you are plugged in is effectively grounded and connected 
     to the mains by wiring of adequate size (minimum 1.5  
     sq.mm. cross section). 

To make an electrical connection 

with the shielded cable (recommended for installations high on 
the wall) proceed as follows: 
Install a shunt box in the wall in the position shown on the 
installation template (fig. 6), where you should provide a power 
cable with a cross-section (two poles plus ground  wire) of 2,5 
sq.mm. 

 

          Warning: The external power line should be provided with   
          an overload circuit breaker with suitable capacity  for the 

rating of the machine. 

 

                                                                                

Make all connections in compliance with the laws in effect. 

 
                       
Close the shunt box with its cover after drilling a hole in it for 
passage of the cable. 
Alternatively, you can use a cable in the wall in the position shown 
on the template, for making the connection. In  this case, 
remove the casing (as described in paragraph 2.4.2) and 
connect the cable to the power terminal board. 

 

                                                                           

Caution: these operations should be performed with  the 
machine already positioned on the bracket. Read  the 
instructions carefully before completely the electric 
connection. 

 

 

 
 

 

  

Содержание Compact Pro

Страница 1: ...INSTALLATION OPERATING MAINTENANCE MANUAL Compact Pro...

Страница 2: ...ning unit You have bought one of the best air conditioners available today Follow the instructions given in this booklet to obtain the very best performance from your air conditioner and to enjoy a fr...

Страница 3: ...nstallation of Wall Mounted Controller page 17 Chap 3 USE AND MAINTENANCE for the user 3 1 Important Recommendations page 26 3 2 Names of parts page 26 3 2 1 List of Units page 26 3 2 2 Description of...

Страница 4: ...conditioner is installed by personnel lacking the necessary qualifications and specialization this invalidates the warranty CHAP 3 USE AND MAINTENANCE by user Contains all information and instructions...

Страница 5: ...its as well as all the precautions suggested by good sense and by the safety regulations in effect in your country CHAP 1 2 SYMBOLS The pictograms in the next chapter provide the necessary information...

Страница 6: ...t at 35 C b s in heating mode Air entering the inside unit at 21 C b s and 19 C b u with air entering the outside unit at 7 C b s and 6 C b u 1 3 4 The air conditioner should be used for the exclusive...

Страница 7: ...UPSIDE DOWN 1 4 2 The packing is made of suitable material and is done by expert personnel Receipt and The units are delivered complete and in perfect condition however we suggest that you perform the...

Страница 8: ...ce that wouldinterferewithcorrectoperation of the unit It must be possible to leave room around the unit for any maintenance operations that may be necessary The air conditioner must be installed on a...

Страница 9: ...es in walls are special drills called core borers with very high twisting torque and adjustable rotation speed depending on the diameter of the hole to be drilled To prevent the creation of large amou...

Страница 10: ...wall should be inspected carefully to determine the best possibleanchorageand typeofboltssuitableforparticular situations Warning The manufacturer is not liable in case of underestimation of the stru...

Страница 11: ...g 5 Caution make sure in this case that the water expelled outward does not damage or disturb persons or property During the winter this type of drainage may cause sheets of ice to form 2 3 3 After dr...

Страница 12: ...l with 4 anchor bolts with a diameter of 6 mm 2 3 4 The air conditioner is equipped with a power supply cable Power supply and plug Connection Ifitisinstallednearanoutlet youneedonlyplugitin In this c...

Страница 13: ...it into position especially at high level CHAP 2 4 PREPARATION FOR ASSEMBLY INSTALLATION WALL TOP PART AT HIGH LEVEL 2 4 1 The air conditioner is assembled in the factory ready to Introduction be inst...

Страница 14: ...ep step motor of the grating Fit the casing back on the air conditioner carefully taking care to hold the wires for the step step motor to one side so that they do not interfere with the inner part of...

Страница 15: ...he LEDs lighting up at once and blinking ten times as well as by an acoustic signal At this time you can adjust the temperature reading on the room temperature sensor This correction is important if t...

Страница 16: ...After eliminating the malfunction the service personnel will take care of closing the evacuation tube CHAP 2 6 PERIODICAL MAINTENANCE Air conditioners of this type do not require any particular routi...

Страница 17: ...fectly horizontal or at the most having a slight inclination toward outside Put the 130 mm pipe into the hole after you cut it according to the wall thickness ATTENTION the pipe supplied with the kit...

Страница 18: ...E INSTRUCTIONS IN THIS MANUAL Themanufacturerhastherightofmodifyingtheunit atanytime whilstmaintainingthe mainfeatures described in this manual During installation or maintenance it is necessary to fo...

Страница 19: ......

Страница 20: ...ructions may cause malfunction of the device and warranty won t be valid anymore B1000 can work in stand alone or in a network by changing the set of switches Positioning of B1000 The card must be pla...

Страница 21: ...box by taking the screw on the right side out B To fix the box to the wall use the screws that are given in the pack C Attention Be very careful in order not to damage the card and its components dur...

Страница 22: ...control box push the trigger on the left side and lift rotating towards the other side Positioning If you put the control farer than 2m from the conditioner you have to take a loner wire In this case...

Страница 23: ...75 230v 50Hz given K2 CAN BUS mains 1 CAN L 2 CAN H 3 GND 4 Screening Screened cable 3x0 34 K3 Serial for the air conditioner 1 TX 2 GND 3 RX Given Not extendible K4 Contact occupied room 1 Contact r...

Страница 24: ...s specified in the instructions if you use the mains connection DIP SWITCH CONFIGURATION On the board there are 12 microswitches dip switch that are subdivided in two groups of 4 S1 and 8 S2 selectors...

Страница 25: ...model In mails Stand alone 1 The address of the board on CAN bus has to be unique and unequivocal the coding is expressed on the basis 2 2 The function of this selector is active only for the configu...

Страница 26: ...2 C and t set C Temp pilot light it lights up when it is fixed a temperature 2 C lower than the set one D Temp pilot light it lights up when it is fixed a temperature 2 C higher than the set one When...

Страница 27: ...h the remote control Once the machine is started through the remote control in compliance with the above data you have to press the button placed on the power board see picture to store on the Eprom t...

Страница 28: ......

Страница 29: ...f airflow 3 Motor operated air baffles for upward airflow 4 Alarm display console 5 Air intake grating 6 Grips for removal of air filter 7 Rubber hose with cap on end for evacuation of 8 condensation...

Страница 30: ...collection points provided by the local authorities for this type of waste REPLACE BOTH BATTERIES AT THE SAME TIME To insert the batteries remove the spring latch cover on the back of the remote contr...

Страница 31: ...witch off or unplugging the machine from the mains 3 4 4 By means of this button the machine is automatically Wellbeingmode regulated in order to create an optimal comfort tempera Automatic ture in th...

Страница 32: ...ing pump HP heatpump To select this mode press button T4 operating mode selection switch until the sun symbol appears on the display First set the desired temperature and fan speed see the specific pa...

Страница 33: ...o the effective room temperature As the room temperature nears the setting fan speed is reduced automatically When the unit is operating in dehumidification mode fan speed adjustment is not possible a...

Страница 34: ...ed Night comfort mode operation is not available for dehumidifying only Night comfort mode operation can be halted at any time ideally when you wake up in the morning by pressing button T3 again At th...

Страница 35: ...ime when you want program 2 to start Every time you press one end of the toggle button the time setting increases or decreases by 30 minutes g Press button T6 Time and Program Setting as many times as...

Страница 36: ...3 5 MAINTENANCE Your air conditioner has been designed to reduce operations of routine maintenance to a minimum and ensure that they can be performed easily by any user The only operations required a...

Страница 37: ...nctions This is to safeguard the compressor When heating on versions with the heating pump the machine does not start emitting heat until a few minutes after the compressor starts If the fan should go...

Страница 38: ...re has been an increase in the heating or cooling load for example a door or window has been left open or a device that dissipates a large amount of heat has been installed in the room what to do make...

Страница 39: ...999A MICRO SWITCH TRIGGER 12 05M0194 DRAIN PUMP 13 281692B72 CONDENSATE DISTRIBUTOR 14 23M0114 CENTRIFUGAL FAN 15 275971A CAPACITOR 4mF 16 591908A85F ELECTRONIC BOARD UNIT SIZE 21 cooling only 17 5919...

Страница 40: ......

Страница 41: ...www lennoxuk com Lennox UK Cornwell Business Park Salthouse Road Brackmills Northampton NN4 7EX Tel 01604 669100 Fax 01604 669150 info uk lennoxeurope com 07 2005...

Отзывы: