The machine is set in the factory 

without correction of 

the temperature. 

In addition to the self-test (that can be made under any 
conditions of room temperature) we recommend that you  also 
test the product in the various operating modes accessible 
to the user (see the user manual). One important test you 
should make concerns regular  evacuation of condensation 
water on the models with heat pump. To check this, keep the 
machine running for at least 4-5 hours in the heating mode. If 
the water does not  drain, there should be an “overflow” 
alarm. 

2.5.1 

If there should be a malfunction in the condensation water 

  Evacuation of  

drain system, the air conditioner stops working and 

Condensation 

signals, with flashing orange, green and red lights (the 

   water in case of  

second and third LEDs from the left), the alarm status. 

emergency  

To enable the air conditioner to work temporarily until the service 

personnel arrives, you can drain the water out by  following 
these simple instructions: 
-  Grasp the rubber cap on the bottom centre of the air 

conditioner behind the edge of the frame facing the wall 
between your thumb and forefinger. 

-  Pull the rubber tube closed by the cap out by a few 

centimetres. 

-  Remove  the cap after placing a bucket or other container 

underneath it (at least five litter capacity) to collect the water 
(see fig. 23). 

-  After eliminating the malfunction the service personnel will 

take care of closing the evacuation tube. 

CHAP. 2.6     PERIODICAL MAINTENANCE 

Air conditioners of this type do not require any particular routine 
maintenance except:: 

 

Note: after cleaning the battery replace the noise 
insulation carefully matching the edges and gaskets  with 
their reference markings. 

Before you leave the site of installation you should gather up all 
packing material and use a damp cloth to remove any traces of 
dust that may have deposited on the machine during 
assembly (fig. 24). These operations, though certainly not 
essential, have a beneficial effect as they enhance the 
professional image of the installer in the eyes of the client. 

To prevent unnecessary calls by the user, before you leave the site 
of installation it is also a good idea to: 

- Explain the contents of the Instruction Manual to the user.                 
- Show him how to clean the filter.                                           
- Explain when and how he should contact the Service 
  Department 

 

 

Fig. 24 

-  Cleaning or washing the room air filter when the red 
  led lights up (see user manual). 
-  Cleaning of “external air” battery, to be done as needed, 
  depending on the amount of dirt in the external air, 
  once or twice a year. To do this, you must, of course, open 
  the air conditioner by removing its casing and the 
  noise insulation on the inside.                                        
-  Cleaning can be done using a vacuum cleaner or soft  
  brush, taking particular care not to damage the  
  aluminium heat exchanger baffles.  It may be necessary to 
  use water and detergents to remove heavily encrusted 
  dirt. 

Содержание Compact Pro

Страница 1: ...INSTALLATION OPERATING MAINTENANCE MANUAL Compact Pro...

Страница 2: ...ning unit You have bought one of the best air conditioners available today Follow the instructions given in this booklet to obtain the very best performance from your air conditioner and to enjoy a fr...

Страница 3: ...nstallation of Wall Mounted Controller page 17 Chap 3 USE AND MAINTENANCE for the user 3 1 Important Recommendations page 26 3 2 Names of parts page 26 3 2 1 List of Units page 26 3 2 2 Description of...

Страница 4: ...conditioner is installed by personnel lacking the necessary qualifications and specialization this invalidates the warranty CHAP 3 USE AND MAINTENANCE by user Contains all information and instructions...

Страница 5: ...its as well as all the precautions suggested by good sense and by the safety regulations in effect in your country CHAP 1 2 SYMBOLS The pictograms in the next chapter provide the necessary information...

Страница 6: ...t at 35 C b s in heating mode Air entering the inside unit at 21 C b s and 19 C b u with air entering the outside unit at 7 C b s and 6 C b u 1 3 4 The air conditioner should be used for the exclusive...

Страница 7: ...UPSIDE DOWN 1 4 2 The packing is made of suitable material and is done by expert personnel Receipt and The units are delivered complete and in perfect condition however we suggest that you perform the...

Страница 8: ...ce that wouldinterferewithcorrectoperation of the unit It must be possible to leave room around the unit for any maintenance operations that may be necessary The air conditioner must be installed on a...

Страница 9: ...es in walls are special drills called core borers with very high twisting torque and adjustable rotation speed depending on the diameter of the hole to be drilled To prevent the creation of large amou...

Страница 10: ...wall should be inspected carefully to determine the best possibleanchorageand typeofboltssuitableforparticular situations Warning The manufacturer is not liable in case of underestimation of the stru...

Страница 11: ...g 5 Caution make sure in this case that the water expelled outward does not damage or disturb persons or property During the winter this type of drainage may cause sheets of ice to form 2 3 3 After dr...

Страница 12: ...l with 4 anchor bolts with a diameter of 6 mm 2 3 4 The air conditioner is equipped with a power supply cable Power supply and plug Connection Ifitisinstallednearanoutlet youneedonlyplugitin In this c...

Страница 13: ...it into position especially at high level CHAP 2 4 PREPARATION FOR ASSEMBLY INSTALLATION WALL TOP PART AT HIGH LEVEL 2 4 1 The air conditioner is assembled in the factory ready to Introduction be inst...

Страница 14: ...ep step motor of the grating Fit the casing back on the air conditioner carefully taking care to hold the wires for the step step motor to one side so that they do not interfere with the inner part of...

Страница 15: ...he LEDs lighting up at once and blinking ten times as well as by an acoustic signal At this time you can adjust the temperature reading on the room temperature sensor This correction is important if t...

Страница 16: ...After eliminating the malfunction the service personnel will take care of closing the evacuation tube CHAP 2 6 PERIODICAL MAINTENANCE Air conditioners of this type do not require any particular routi...

Страница 17: ...fectly horizontal or at the most having a slight inclination toward outside Put the 130 mm pipe into the hole after you cut it according to the wall thickness ATTENTION the pipe supplied with the kit...

Страница 18: ...E INSTRUCTIONS IN THIS MANUAL Themanufacturerhastherightofmodifyingtheunit atanytime whilstmaintainingthe mainfeatures described in this manual During installation or maintenance it is necessary to fo...

Страница 19: ......

Страница 20: ...ructions may cause malfunction of the device and warranty won t be valid anymore B1000 can work in stand alone or in a network by changing the set of switches Positioning of B1000 The card must be pla...

Страница 21: ...box by taking the screw on the right side out B To fix the box to the wall use the screws that are given in the pack C Attention Be very careful in order not to damage the card and its components dur...

Страница 22: ...control box push the trigger on the left side and lift rotating towards the other side Positioning If you put the control farer than 2m from the conditioner you have to take a loner wire In this case...

Страница 23: ...75 230v 50Hz given K2 CAN BUS mains 1 CAN L 2 CAN H 3 GND 4 Screening Screened cable 3x0 34 K3 Serial for the air conditioner 1 TX 2 GND 3 RX Given Not extendible K4 Contact occupied room 1 Contact r...

Страница 24: ...s specified in the instructions if you use the mains connection DIP SWITCH CONFIGURATION On the board there are 12 microswitches dip switch that are subdivided in two groups of 4 S1 and 8 S2 selectors...

Страница 25: ...model In mails Stand alone 1 The address of the board on CAN bus has to be unique and unequivocal the coding is expressed on the basis 2 2 The function of this selector is active only for the configu...

Страница 26: ...2 C and t set C Temp pilot light it lights up when it is fixed a temperature 2 C lower than the set one D Temp pilot light it lights up when it is fixed a temperature 2 C higher than the set one When...

Страница 27: ...h the remote control Once the machine is started through the remote control in compliance with the above data you have to press the button placed on the power board see picture to store on the Eprom t...

Страница 28: ......

Страница 29: ...f airflow 3 Motor operated air baffles for upward airflow 4 Alarm display console 5 Air intake grating 6 Grips for removal of air filter 7 Rubber hose with cap on end for evacuation of 8 condensation...

Страница 30: ...collection points provided by the local authorities for this type of waste REPLACE BOTH BATTERIES AT THE SAME TIME To insert the batteries remove the spring latch cover on the back of the remote contr...

Страница 31: ...witch off or unplugging the machine from the mains 3 4 4 By means of this button the machine is automatically Wellbeingmode regulated in order to create an optimal comfort tempera Automatic ture in th...

Страница 32: ...ing pump HP heatpump To select this mode press button T4 operating mode selection switch until the sun symbol appears on the display First set the desired temperature and fan speed see the specific pa...

Страница 33: ...o the effective room temperature As the room temperature nears the setting fan speed is reduced automatically When the unit is operating in dehumidification mode fan speed adjustment is not possible a...

Страница 34: ...ed Night comfort mode operation is not available for dehumidifying only Night comfort mode operation can be halted at any time ideally when you wake up in the morning by pressing button T3 again At th...

Страница 35: ...ime when you want program 2 to start Every time you press one end of the toggle button the time setting increases or decreases by 30 minutes g Press button T6 Time and Program Setting as many times as...

Страница 36: ...3 5 MAINTENANCE Your air conditioner has been designed to reduce operations of routine maintenance to a minimum and ensure that they can be performed easily by any user The only operations required a...

Страница 37: ...nctions This is to safeguard the compressor When heating on versions with the heating pump the machine does not start emitting heat until a few minutes after the compressor starts If the fan should go...

Страница 38: ...re has been an increase in the heating or cooling load for example a door or window has been left open or a device that dissipates a large amount of heat has been installed in the room what to do make...

Страница 39: ...999A MICRO SWITCH TRIGGER 12 05M0194 DRAIN PUMP 13 281692B72 CONDENSATE DISTRIBUTOR 14 23M0114 CENTRIFUGAL FAN 15 275971A CAPACITOR 4mF 16 591908A85F ELECTRONIC BOARD UNIT SIZE 21 cooling only 17 5919...

Страница 40: ......

Страница 41: ...www lennoxuk com Lennox UK Cornwell Business Park Salthouse Road Brackmills Northampton NN4 7EX Tel 01604 669100 Fax 01604 669150 info uk lennoxeurope com 07 2005...

Отзывы: