2.7   INSTRUCTIONS TO INSTALL THE FRESH AIR KIT KR100 

 

The fresh air kit allows the outside air to enter into the room where the air 
conditioner is located. 
This device guarantees that about 90 m3/h are brought into the room, 
resulting in a very good change of air. 
Follow carefully these instructions and you will be able to install perfectly the 
appliance. 
 
 

NOTICE 

 

 

The kit has to be mounted to the wall before the air conditioner 

 

It have to be installed on an outside wall, preferably not on the walls looking 
onto a road or places where there are polluting substances 

 

The minimum height from the ground must be at least 6 metres for walls 
looking onto high traffic-congested roads and 3 metres in all the other cases. 

 

Check that nothing could obstruct the airflow at the device inlet (trees with 
leafs, curtains, etc..) 

 

To improve the air downflow from the room it is recommended to install a 
plenum lock-gate with approx. dimensions 150x150 mm. 

 

 

INSTALLATION 

 
After having determined the position of the indoor unit fixing bracket, trace the centre of 
the hole following the instructions of picture 1. 
 

 

Drill the wall using a suitable drill equipped with core bit with a diameter of at least 
132 mm. The hole has to be perfectly horizontal,  or at the most having a slight 
inclination toward outside. 

 

Put the 130-mm. pipe into the hole, after you cut it according to the wall thickness. 

ATTENTION: the pipe supplied with the kit is long max. 500 mm; for thicker 
walls you have to ask for a longer pipe to the Service Centres. 

 

Seal the pipe at both ends using some silicone or stopper 

 

Apply the outdoor grid, equipped with grate against insects, by means of at least 2 
dowels diam. 6 (supplied with the kit) and putting silicone between the wall and rear 
part of the grid before fixing it. 

 

Put the fan/lock-gate assembly in the hole from inside the room, leaving the power 
cable in the lower part (picture 3). Take the inside protection grid away, fix the device 
to the wall with at least two dowels diam. 6 and then reassemble the grid. 

 

Now install the indoor unit following the user manual’s instructions; before closing the 
front panel, connect the connection cable to the kit as follows: 

o

 

Let the cable pass through the special hole that is placed on the rear casing 
as shown in picture 2 and position the fairlead that is already threaded on 
the connecting cable 

 
 
Calculate the length of the pipe bringing it near the male connector placed on the 
electronic board and put the terminals in the special female connector  supplied with the 
kit. 
 
Connect the connector to the electronic board. 
 
Close the front panel and test the working of the air conditioner. 

 

 

 

 

Содержание Compact Pro

Страница 1: ...INSTALLATION OPERATING MAINTENANCE MANUAL Compact Pro...

Страница 2: ...ning unit You have bought one of the best air conditioners available today Follow the instructions given in this booklet to obtain the very best performance from your air conditioner and to enjoy a fr...

Страница 3: ...nstallation of Wall Mounted Controller page 17 Chap 3 USE AND MAINTENANCE for the user 3 1 Important Recommendations page 26 3 2 Names of parts page 26 3 2 1 List of Units page 26 3 2 2 Description of...

Страница 4: ...conditioner is installed by personnel lacking the necessary qualifications and specialization this invalidates the warranty CHAP 3 USE AND MAINTENANCE by user Contains all information and instructions...

Страница 5: ...its as well as all the precautions suggested by good sense and by the safety regulations in effect in your country CHAP 1 2 SYMBOLS The pictograms in the next chapter provide the necessary information...

Страница 6: ...t at 35 C b s in heating mode Air entering the inside unit at 21 C b s and 19 C b u with air entering the outside unit at 7 C b s and 6 C b u 1 3 4 The air conditioner should be used for the exclusive...

Страница 7: ...UPSIDE DOWN 1 4 2 The packing is made of suitable material and is done by expert personnel Receipt and The units are delivered complete and in perfect condition however we suggest that you perform the...

Страница 8: ...ce that wouldinterferewithcorrectoperation of the unit It must be possible to leave room around the unit for any maintenance operations that may be necessary The air conditioner must be installed on a...

Страница 9: ...es in walls are special drills called core borers with very high twisting torque and adjustable rotation speed depending on the diameter of the hole to be drilled To prevent the creation of large amou...

Страница 10: ...wall should be inspected carefully to determine the best possibleanchorageand typeofboltssuitableforparticular situations Warning The manufacturer is not liable in case of underestimation of the stru...

Страница 11: ...g 5 Caution make sure in this case that the water expelled outward does not damage or disturb persons or property During the winter this type of drainage may cause sheets of ice to form 2 3 3 After dr...

Страница 12: ...l with 4 anchor bolts with a diameter of 6 mm 2 3 4 The air conditioner is equipped with a power supply cable Power supply and plug Connection Ifitisinstallednearanoutlet youneedonlyplugitin In this c...

Страница 13: ...it into position especially at high level CHAP 2 4 PREPARATION FOR ASSEMBLY INSTALLATION WALL TOP PART AT HIGH LEVEL 2 4 1 The air conditioner is assembled in the factory ready to Introduction be inst...

Страница 14: ...ep step motor of the grating Fit the casing back on the air conditioner carefully taking care to hold the wires for the step step motor to one side so that they do not interfere with the inner part of...

Страница 15: ...he LEDs lighting up at once and blinking ten times as well as by an acoustic signal At this time you can adjust the temperature reading on the room temperature sensor This correction is important if t...

Страница 16: ...After eliminating the malfunction the service personnel will take care of closing the evacuation tube CHAP 2 6 PERIODICAL MAINTENANCE Air conditioners of this type do not require any particular routi...

Страница 17: ...fectly horizontal or at the most having a slight inclination toward outside Put the 130 mm pipe into the hole after you cut it according to the wall thickness ATTENTION the pipe supplied with the kit...

Страница 18: ...E INSTRUCTIONS IN THIS MANUAL Themanufacturerhastherightofmodifyingtheunit atanytime whilstmaintainingthe mainfeatures described in this manual During installation or maintenance it is necessary to fo...

Страница 19: ......

Страница 20: ...ructions may cause malfunction of the device and warranty won t be valid anymore B1000 can work in stand alone or in a network by changing the set of switches Positioning of B1000 The card must be pla...

Страница 21: ...box by taking the screw on the right side out B To fix the box to the wall use the screws that are given in the pack C Attention Be very careful in order not to damage the card and its components dur...

Страница 22: ...control box push the trigger on the left side and lift rotating towards the other side Positioning If you put the control farer than 2m from the conditioner you have to take a loner wire In this case...

Страница 23: ...75 230v 50Hz given K2 CAN BUS mains 1 CAN L 2 CAN H 3 GND 4 Screening Screened cable 3x0 34 K3 Serial for the air conditioner 1 TX 2 GND 3 RX Given Not extendible K4 Contact occupied room 1 Contact r...

Страница 24: ...s specified in the instructions if you use the mains connection DIP SWITCH CONFIGURATION On the board there are 12 microswitches dip switch that are subdivided in two groups of 4 S1 and 8 S2 selectors...

Страница 25: ...model In mails Stand alone 1 The address of the board on CAN bus has to be unique and unequivocal the coding is expressed on the basis 2 2 The function of this selector is active only for the configu...

Страница 26: ...2 C and t set C Temp pilot light it lights up when it is fixed a temperature 2 C lower than the set one D Temp pilot light it lights up when it is fixed a temperature 2 C higher than the set one When...

Страница 27: ...h the remote control Once the machine is started through the remote control in compliance with the above data you have to press the button placed on the power board see picture to store on the Eprom t...

Страница 28: ......

Страница 29: ...f airflow 3 Motor operated air baffles for upward airflow 4 Alarm display console 5 Air intake grating 6 Grips for removal of air filter 7 Rubber hose with cap on end for evacuation of 8 condensation...

Страница 30: ...collection points provided by the local authorities for this type of waste REPLACE BOTH BATTERIES AT THE SAME TIME To insert the batteries remove the spring latch cover on the back of the remote contr...

Страница 31: ...witch off or unplugging the machine from the mains 3 4 4 By means of this button the machine is automatically Wellbeingmode regulated in order to create an optimal comfort tempera Automatic ture in th...

Страница 32: ...ing pump HP heatpump To select this mode press button T4 operating mode selection switch until the sun symbol appears on the display First set the desired temperature and fan speed see the specific pa...

Страница 33: ...o the effective room temperature As the room temperature nears the setting fan speed is reduced automatically When the unit is operating in dehumidification mode fan speed adjustment is not possible a...

Страница 34: ...ed Night comfort mode operation is not available for dehumidifying only Night comfort mode operation can be halted at any time ideally when you wake up in the morning by pressing button T3 again At th...

Страница 35: ...ime when you want program 2 to start Every time you press one end of the toggle button the time setting increases or decreases by 30 minutes g Press button T6 Time and Program Setting as many times as...

Страница 36: ...3 5 MAINTENANCE Your air conditioner has been designed to reduce operations of routine maintenance to a minimum and ensure that they can be performed easily by any user The only operations required a...

Страница 37: ...nctions This is to safeguard the compressor When heating on versions with the heating pump the machine does not start emitting heat until a few minutes after the compressor starts If the fan should go...

Страница 38: ...re has been an increase in the heating or cooling load for example a door or window has been left open or a device that dissipates a large amount of heat has been installed in the room what to do make...

Страница 39: ...999A MICRO SWITCH TRIGGER 12 05M0194 DRAIN PUMP 13 281692B72 CONDENSATE DISTRIBUTOR 14 23M0114 CENTRIFUGAL FAN 15 275971A CAPACITOR 4mF 16 591908A85F ELECTRONIC BOARD UNIT SIZE 21 cooling only 17 5919...

Страница 40: ......

Страница 41: ...www lennoxuk com Lennox UK Cornwell Business Park Salthouse Road Brackmills Northampton NN4 7EX Tel 01604 669100 Fax 01604 669150 info uk lennoxeurope com 07 2005...

Отзывы: