Page 66
B2 diagram with C1 diagram
CHA16-1603 Operating Sequence
CHA161603 Operation Sequence: B2 Section and C1 Sections
(Basic Unit with Basic Electromechanical Thermostat)
Blower Operation:
1- Blower demand from thermostat terminal G energizes blower contactor K3.
2- N.O. K31 closes, blower begins operation. N.O. K32 closes energizing economizer damper motor
(if economizer is installed, outdoor damper drives to minimum position).
1st Stage Cooling (Low Ambient Kit Installed):
3- Cooling demand energizes Y1 and G in the thermostat. G energizes blower (see step 1.)
4- 24VAC power energizes low ambient relay K128.
5- N.O. K1281 closes energizing outdoor fan relay K10.
6- N.O. K101,2 close energizing condenser fan motors B4 and B5.
7- N.O. K103 closes. 24VAC power is routed around N.C. low discharge temp. sensor S3, through
N.C. freezstat S49, N.C. high pressure limit S4 and N.C. low pressure limit S24 to energize com
pressor contactor K1.
8- N.O. Contacts K1-1 close energizing compressor B1.
1st Stage Cooling (Low Ambient Kit Not Installed):
9- Cooling demand energizes Y1 and G in the thermostat. G energizes blower (see step 1.)
10- 24VAC power energizes outdoor fan relay K10.
11-
N.O. K101,2 close energizing condenser fan motors B4 and B5.
12- N.O. K103 closes. 24VAC power is routed through N.C. low discharge temp. sensor S3, N.C.
freezstat S49, N.C. high pressure limit S4 and N.C. low pressure limit S24 to energize compressor
contactor K1.
13- N.O. Contacts K1-1 close energizing compressor B1.
2nd Stage Cooling (With Low Ambient Kit):
14- Second stage cooling demand energizes Y2. 24VAC power is routed through N.C freezstat S50,
around N.C. low discharge temp. sensor S30, through high pressure limit S7 and low pressure limit
S25 energizing compressor contactor K2.
15- N.O. contacts K21 close energizing compressor B2.
2nd Stage Cooling (With Out Low Ambient Kit):
16- Second stage cooling demand energizes Y2. 24VAC power is routed through N.C freezstat S50,
through N.C. low discharge temp. sensor S30, through high pressure limit S7 and low pressure
limit S25 energizing compressor contactor K2.
17- N.O. contacts K21 close energizing compressor B2.
1st Stage Heating: (See CHA161853 with Electric Heat Pages 5657)
18- Heating demand energizes W1 in the thermostat. The operation sequence of electric heat units
varies depending on size (kW input rating) and line voltage rating.
2nd Stage Heating (If equipped with multiple stage heating):
(See CHA161853 with Electric Heat Pages 5657)
19- Additional heating demand energizes W2 in the thermostat. The operation sequence of electric
heat units varies depending on size (kW input rating) and line voltage rating.
Safety Blower Operation:
20- If either limits in the electric heat section trip, the heating elements are immediately deen
ergized.
21- Indoor blower remains energized powered by K3 energized by thermostat demand.
Содержание CHA16
Страница 47: ...Page 47 FIGURE 52 CYCLE CONTROL KIT WIRING DIAGRAM...
Страница 55: ...Page 55 NOTES...
Страница 58: ...C1diagram electromechanical thermostat with modulating economizer with D5 diagram Page 58...
Страница 60: ...C2 1 diagram electromechanical thermostat with modulating economizer and warm up with D5 diagram Page 60...
Страница 62: ...Page 62 B41 diagram with C1 diagram CHA16 2553 2753 3003 Operating Sequence...
Страница 64: ...Page 64 B9 diagram with C1 diagram CHA16 1853 Operating Sequence...