Page 3
SPECIFICATIONS CHA161353 & CHA161603
Model No.
CHA161353
CHA161603
*ARI Standard
Total cooling capacity (btuh)
119,000
142,000
*ARI Standard
210/240 Ratings
Total unit watts
13,220
16,820
210/240 Ratings
or
Standard
360 Ratings
EER (Btuh/Watts)
9.0
8.50
Standard
360 Ratings
Integrated Part Load Value
8.8
ARI Standard 270 SRN (Bels)
8.8
Refrigerant (22) Charge
Stage 1
7 lbs 4 oz
10 lbs. 12 oz.
Refrigerant (22) Charge
Stage 2
7 lbs. 4 oz.
7 lbs. 12 oz.
Blower wheel nominal diameter x width (in.)
15 x 15
Nominal motor horsepower
2
3
**Factory
Installed
Maximum usable horsepower
2.30
3.45
Evaporator Blower
y
Installed
Drives
Voltage & phase
208/230/460v3ph
Evaporator Blower
and
D i
S l ti
Drives
RPM range
730 950
and
Drive Selection
**Optional
Nominal motor horsepower
3
**Optional
Factory
Maximum usable horsepower
3.45
Factory
Installed
Drives
Voltage & phase
208/230/460v3ph
Drives
RPM range
730 950
E
t
Net face area (sq. ft.)
9.46
11.9
Evaporator
Coil
Tube diameter (in.) & No. of rows
3/8 4
3/8 3
Coil
Fins per inch
12
12
C d
Net face area (sq. ft.)
20.0
24.4
Condenser
Coil
Tube diameter (in.) & No. of rows
3/8 2
3/8 2
Coil
Fins per inch
20
Diameter (in.) & No. of blades
(2) 20 5
(2) 22 4
Condenser
Air volume (cfm)
6400 Total
7700 Total
Condenser
Fans
Motor horsepower
(2) 1/3
(2) 1/2
Motor watts
875 Total
1050 Total
Condensate drain size mpt (in.)
3/4
No. & size of filters (in.)
(4) 16 x 25 x 2
(4) 20 x 25 x 2
Electrical characteristics
208/230v or 460v 60 hertz 3 phase
Sound Rating Number in accordance with ARI Standard 270.
*Rated in accordance with ARI Standard 210/240 or
360; 95
F outdoor air temperature and 80
F db/67
F wb entering evaporator air.
**Using total air volume and system static pressure requirements determine from blower performance tables rpm and bhp required. Maximum usable hp of motors
furnished by Lennox are shown. If motors of comparable hp are used, be sure to keep within the service factor limitations outlined on the motor nameplate.
OPTIONAL ACCESSORIES CHA161353 & CHA161603 (Ordered Extra)
Unit Model No.
CHA161353
CHA161603
Model No.
ECH16135/160
ECH16135/160
Electric
Kw input range
1520304050
Electric
Heat
*Fuse
208/230 volt
72G10
72G13
Fuse
Block
460 volt
72G11
72G14
Roof Mounting Frame
RMF16135/160
(32G91)
Economizer Dampers No. & size of filters (in.)
REMD16M135 (2) 16 x 25 x 1
(74G23)
REMD16M160 (2) 20 x 25 x 1
(51G25)
Horizontal Economizer Dampers No. & size of filters (in.)
EMDH16M135 (2) 16 x 25 x 1
(24H04)
EMDH16M160 (2) 20 x 25 x 1
(24H05)
Exhaust Dampers (Net Face Area)
GED1695/135/160 (0.43 sq. ft.)
(34G80)
Differential Enthalpy Control
54G44
Horizontal Supply and Return Air Kit
LB55756BB
(35G42)
LB55756BC
(51G27)
Bottom Power Entry Kit (LB55757CA)
34G70
Ceiling Supply and
StepDown
RTD11135
(29G05)
RTD11185
(29G06)
Ceiling Supply and
Return Air
Diff
Flush
FD11135
(29G09)
FD11185
(29G10)
Return Air
Diffusers
Transition
SRT16135
(97H10)
SRT16160
(97H11)
Outdoor Air Dampers No. & size of filters (in.)
OAD16135
(35G25)
(1) 16 x 20 x 1
OAD16160
(51G30)
(1) 16 x 20 x 1
Automatic OAD16 Damper Kit
35G21
Low Ambient Control Kit
LB57113BH
(16J86)
LB57113BJ
(16J87)
TimedOff Control (2) LB50709BA
40G20
*Must be ordered extra. Factory installed heaters will have fuse block installed. Fuse block must be field installed in field installed heaters.
Содержание CHA16
Страница 47: ...Page 47 FIGURE 52 CYCLE CONTROL KIT WIRING DIAGRAM...
Страница 55: ...Page 55 NOTES...
Страница 58: ...C1diagram electromechanical thermostat with modulating economizer with D5 diagram Page 58...
Страница 60: ...C2 1 diagram electromechanical thermostat with modulating economizer and warm up with D5 diagram Page 60...
Страница 62: ...Page 62 B41 diagram with C1 diagram CHA16 2553 2753 3003 Operating Sequence...
Страница 64: ...Page 64 B9 diagram with C1 diagram CHA16 1853 Operating Sequence...