Page 12
PED16185 & PED16300
POWER EXHAUST FANS PERFORMANCE
Model No.
Air Volume
(cfm
Exhausted)
Return Air System
Static Pressure
(Inches Water Gauge)
4200
0
3800
.05
3500
.10
PED16185
3200
.15
2700
.20
2200
.25
6300
0
5750
.05
PED16300
5200
.10
4625
.15
4050
.20
CEILING DIFFUSER AIR THROW DATA
Air Volume
*Effective Throw Range (feet)
Model No.
Air Volume
(cfm)
RTD11
StepDown
FD11
Flush
3000
27 33
25 30
CHA16823
CHA16953
3375
30 37
28 34
CHA16953
3750
34 41
31 38
4400
34 42
32 40
CHA161353
4950
38 47
36 45
5500
43 52
40 50
4200
39 46
40 48
CHA161603
5000
41 50
43 52
5800
43 52
45 54
6000
45 55
48 55
CHA161853
6750
47 56
50 58
7500
49 58
55 66
CHA16 2553
8000
39 44
53 62
CHA162553
CHA162753
CHA16 3003
9000
47 56
55 64
CHA163003
10,000
49 58
57 67
*Throw is the horizontal or vertical distance an airstream travels on leaving the outletor
diffuser before the maximum velocity is reduced to 50 ft. per minute. Four sides open.
823/953 PARTS ARRANGEMENT
HEATING ACCESS
HEATING ELEMENTS
ELECTRIC HEAT
CONTROL BOX
MAKE-UP BOX
FIGURE 1
1ST STAGE EVAPORATOR
2ND STAGE EVAPORATOR
FILTER SECTION
CONDENSER FAN
CONDENSER COIL
COMPRESSOR
AND CONTROL
BOX ACCESS
2ND STAGE COMPRESSOR
1ST STAGE COMPRESSOR
INDOOR BLOWER
Содержание CHA16
Страница 47: ...Page 47 FIGURE 52 CYCLE CONTROL KIT WIRING DIAGRAM...
Страница 55: ...Page 55 NOTES...
Страница 58: ...C1diagram electromechanical thermostat with modulating economizer with D5 diagram Page 58...
Страница 60: ...C2 1 diagram electromechanical thermostat with modulating economizer and warm up with D5 diagram Page 60...
Страница 62: ...Page 62 B41 diagram with C1 diagram CHA16 2553 2753 3003 Operating Sequence...
Страница 64: ...Page 64 B9 diagram with C1 diagram CHA16 1853 Operating Sequence...