Page 2
SPECIFICATIONS - CHA16823 & CHA16953
Model No.
CHA16823
CHA16953
*ARI Standard
Total cooling capacity (Btuh)
73,000
88,000
*ARI Standard
210/240
R ti
Total unit watts
8,110
9,780
210/240
Ratings
EER (Btuh/Watts)
9.0
9.0
ARI Standard 270 SRN (Bels)
8.6
8.6
Refrigerant (22) Charge
Stage 1
5 lbs. 10 oz.
6 lbs. 4 oz.
Refrigerant (22) Charge
Stage 2
5 lbs. 2 oz.
5 lbs. 14 oz.
Blower wheel nominal diameter x width (in.)
12 x 12
Evaporator Blower
Nominal motor horsepower
2
Evaporator Blower
and
D i
S l ti
**Factory
Installed
Maximum usable horsepower
2.30
and
Drive Selection
y
Installed
Drives
Voltage & phase
208/230/460v3ph
Drives
RPM range
740 1010
Net face area (sq. ft.)
7.75
Evaporator Coil
Tube diameter (in.) & No. of rows
3/8 3
p
Fins per inch
14
Net face area (sq. ft.)
15.67
Condenser Coil
Tube diameter (in.) & No. of rows
3/8 2
Fins per inch
20
Diameter (in.) & No. of blades
24 4
Condenser
Air volume (cfm)
4800
5300
Condenser
Fans
Motor horsepower
1/2
3/4
Motor watts
620
660
Condensate drain size mpt (in.)
3/4
No. & size of filters (in.)
(4) 16 x 20 x 2
Electrical characteristics
208/230v or 460v 60 hertz 3 phase
Sound Rating Number in accordance with ARI Standard 270.
*Rated in accordance with ARI Standard 210/240; 95
F outdoor air temperature and 80
F db/67
F wb entering evaporator air.
**Using total air volume and system static pressure requirements determine from blower performance tables rpm and bhp required. Maximum usable hp of motors
furnished by Lennox are shown. If motors of comparable hp are used, be sure to keep within the service factor limitations outlined on the motor nameplate.
OPTIONAL ACCESSORIES CHA16823 & CHA16953 (Ordered Extra)
Unit Model No.
CHA16823 & CHA16953
Model No.
ECH1682/95
Electric
Kw input range
1015203040
Electric
Heat
*Fuse
208/230 volt
61H86
(823)
61H83
(953)
Fuse
Block
460 volt
61H87
(823)
61H84
(953)
Roof Mounting Frame
RMF1695
(32G90)
Economizer Dampers No. & size of filters (in.)
REMD16M95
(74G22)
(2) 16 x 25 x 1
Horizontal Economizer Dampers No. & size of filters (in.)
EMDH16M95
(24H03)
(2) 16 x 25 x 1
Exhaust Dampers (Net Face Area)
GED1695/135/160 (0.43 sq. ft.)
(34G80)
Differential Enthalpy Control
54G44
Horizontal Supply and Return Air Kit (LB55756BA)
34G71
Bottom Power Entry Kit (LB55757CA)
34G70
Ceiling Supply and
R t
Ai
StepDown
RTD1195
(29G04)
Ceiling Supply and
Return Air
Diffusers
Flush
FD1195
(29G05)
Diffusers
(Net Weight)
Transition
SRT1695
(33G96)
Outdoor Air Dampers No. & size of filters (in.)
OAD1695
(35G26)
(1) 16 x 20 x 1
Automatic OAD16 Damper Kit
35G21
Low Ambient Control Kit (LB57113BG)
15J80
TimedOff Control (2) LB50709BA
40G20
*Must be ordered extra. Factory installed heaters will have fuse block installed. Fuse block must be field installed in field installed heaters.
Содержание CHA16
Страница 47: ...Page 47 FIGURE 52 CYCLE CONTROL KIT WIRING DIAGRAM...
Страница 55: ...Page 55 NOTES...
Страница 58: ...C1diagram electromechanical thermostat with modulating economizer with D5 diagram Page 58...
Страница 60: ...C2 1 diagram electromechanical thermostat with modulating economizer and warm up with D5 diagram Page 60...
Страница 62: ...Page 62 B41 diagram with C1 diagram CHA16 2553 2753 3003 Operating Sequence...
Страница 64: ...Page 64 B9 diagram with C1 diagram CHA16 1853 Operating Sequence...