Lennox CG90CB Скачать руководство пользователя страница 14

# 45466K003

Page 14

Existing Venting Systems

When an existing furnace is removed or replaced, the

original venting system may no longer be sized to properly

vent the attached appliances. An improperly sized venting

system can result in spillage of flue products into the living

space, the formation of condensate, leakage, etc. See the

WARNING

 box below for proper test procedure.

Condensate Disposal Installation

Install the condensate drain line to the unit as follows. The

condensate can be drained from either the right or left

side of the furnace. Install the 1/2" NPT x 3/4" PVC

adapter (supplied) in the drain on the side that the draining

will occur. Install the plastic pipe plug opposite of the drain.

Using 3/4" PVC pipe, make a connection from the adapter

just installed to extend just outside the unit. Install a 3/4"

PVC tee as shown in Figure 15. From the tee, install the

drain to the disposal area. The top of the tee must be left

open for proper condensate drainage.

It is recommended that the condensate drain be routed

directly to a locally acceptable disposal area. The conden-

sate drain line should not be run directly to the outdoors

especially in colder climates where temperatures may

cause the condensate to freeze in the drain line.

Failure to follow the steps outlined below for each appliance connected to the venting system being placed into opera-

tion could result in carbon monoxide poisoning or death.

The following steps shall be followed for each appliance connected to the venting system being placed into operation,

while all other appliances connected to the common venting system are not in operation:

1. Seal any unused openings in the common venting system.

2. Visually inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code,

ANSI Z223.1/NFPA 54 (latest edition) or the CSA B149.1 Natural Gas and Propane Installation Codes and these

instructions. Determine that there is no blockage or restriction, leakage, corrosion, or other deficiencies which could

cause an unsafe condition.

3. As far as practical, close all building doors and windows between the space in which the appliance(s) connected to the

venting system are located and other spaces in the building.

4. Close fireplace dampers.

5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as

range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.

6. Follow the lighting instructions. Place the unit being inspected in operation. Adjust the thermostat so appliance is

operating continuously.

7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner

operation. Use the flame of a match or candle.

8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with

the National Fuel Gas Code, ANSI Z223.1/NFPA 54 (latest edition) and/or the CSA B149.1 Natural Gas and Propane

Installation Codes.

9. After it has been determined that each appliance remaining connected to the venting system properly vents when

tested as outlined above, return doors, windows, exhaust fans, fireplace dampers, and any other gas-fired burning

appliance to their previous conditions of use.

CARBON MONOXIDE POISONING HAZARD

 WARNING

Figure 15

Condensate Disposal

TH

R

U

.

59.69/56.64

1/2” NPT PLUG

(SUPPLIED)

1/2” NPT x 3/4” PVC ADAPTER

(SUPPLIED)

3/4” PVC

TEE MUST REMAIN

OPEN

Содержание CG90CB

Страница 1: ...regulations or requirements take precedence over the general instructions in this manual IMPORTANT Do not store combustible materials including gasoline and other flammable vapors and liquids near the...

Страница 2: ...Supply and Piping beginning on page 15 of these instructions 7 Always install furnace to operate within the furnace s intended temperature rise range with a duct system which has an external static p...

Страница 3: ...in respect to the heat distribution system as much as practicable When installed in a utility room the door should be wide enough to allow the largest part of the furnace to enter or permit the repla...

Страница 4: ...nated Combustion Air Excessive exposure to contaminated combustion air will result in safety and performance related problems The recommended source of combustion air is outdoor air However the use of...

Страница 5: ...tside combustion air An inlet air restrictor plate see Figure 1 is supplied with this furnace and can be found in the plastic bag containing these Installation Instructions and the User s Information...

Страница 6: ...on that cannot be removed by stirring Refer to Table 2 for approved piping and fitting materials cement is recommended Metal or plastic strapping may be used for vent pipe hangers When making ABS join...

Страница 7: ...NR Not Recommended Minimum Pipe Diameter 112 000 125 000 BTU HR Models Minimum Pipe Diameter 90 000 100 000 BTU HR Models e p i P t n e V h t g n e L t f s w o b l E 0 9 f o r e b m u N 0 1 2 3 4 5 6...

Страница 8: ...r a e l C D e h t e v o b a d e t a c o l t i f f o s d e t a l i t n e v o t e c n a r a e l c l a c i t r e V e h t m o r f m c 1 6 t e e f 2 f o e c n a t s i d l a t n o z i r o h a n i h t i w l...

Страница 9: ...C D e h t e v o b a d e t a c o l t i f f o s d e t a l i t n e v o t e c n a r a e l c l a c i t r e V e h t m o r f m c 1 6 t e e f 2 f o e c n a t s i d l a t n o z i r o h a n i h t i w l a n i m...

Страница 10: ...n the same pressure zone There fore in horizontal venting applications they must be on the same side of the house within the parameters shown in Figure 6 On initial start up of the unit some of the wa...

Страница 11: ...8 For vertical venting refer to Figure 9 The vent pipe on horizontal runs must slope upward away from the furnace at a minimum pitch of 1 4 per foot of run to prevent accumulation of condensate Figur...

Страница 12: ...er to Figure 12 for detail of this inlet air assembly On initial start up of the unit some of the water used to prime the trap system may run down into the combustion blower and cause noise Do not cem...

Страница 13: ...Prime the trap system by slowly pouring 1 cup of water down the vent pipe For horizontal venting refer to Figure 13 For vertical venting refer to Figure 14 The vent pipe on horizontal runs must slope...

Страница 14: ...sed openings in the common venting system 2 Visually inspect the venting system for proper size and horizontal pitch as required in the National Fuel Gas Code ANSI Z223 1 NFPA 54 latest edition or the...

Страница 15: ...rnace A return air duct system is recommended If the unit is installed in a confined space or closet a return connection must be run full size to a location outside the closet The air duct in the clos...

Страница 16: ...ividual manual shutoff valve during any pressure testing of the gas supply piping system at test pressure equal to or less than 1 2 psig 3 5 kPa or 14 W C If the piping system is to be tested at press...

Страница 17: ...2 filter are supplied with the furnace Models designed for more than 1600 CFM nominal air delivery include two of each The filter rack is to be installed between the return air duct and the side of th...

Страница 18: ...onic Air Cleaner Terminals are provided on the blower control board for connection of a 120 volt electronic air cleaner The EAC terminal is energized whenever the thermostat is calling for heat coolin...

Страница 19: ...because some gas is heavier than air and will settle on the floor What to do if you smell gas Do not try to light any appliances Extinguish any open flame Do not touch any electric switch do not use a...

Страница 20: ...ay The call for cooling has priority over continuous fan operation while a call for heating has priority over both a call for cooling or continuous fan Ignition lockouts for any reason do not affect c...

Страница 21: ...t the regulator turn the adjusting screw s on the regulator clockwise to increase pressure and input coun terclockwise to decrease pressure and input Replace the barbed fitting and reconnect the hose...

Страница 22: ...a e H e u l a V t f U T B 3 d l o f i n a M e r u s s e r P C W n i g n i t a e H e u l a V t f U T B 3 d l o f i n a M e r u s s e r P C W n i 0 0 0 2 8 4 9 0 5 3 8 7 2 2 0 0 0 1 6 6 6 9 0 0 0 0 3 4...

Страница 23: ...cked or plugged the furnace will not operate properly MAINTENANCE Failure to follow the safety warnings exactly could result in dangerous operation serious injury death or property damage Improper ser...

Страница 24: ...ower housing assembly Blower wheel Blower motor Blower motor mount Blower motor capacitor Burner Group Gas manifold Main burner orifices Main burners Accessories ALPKT572 Natural Gas to Propane Conver...

Страница 25: ...emory A pushbutton switch is located on the control see Figure 22 on page 26 When the pushbutton switch is pressed and released the control flashes the stored fault codes The most recent fault code is...

Страница 26: ...45466K003 Page 26 Figure 22 Connection Diagram P N 45198 005...

Страница 27: ...45466K003 Page 27 Figure 23 Schematic Diagram P N 45198 005...

Отзывы: