Lennox CG90CB Скачать руководство пользователя страница 13

# 45466K003

Page 13

Counterflow Models G1D93BC & CG90CB Non-Direct
Vent Installation

An inlet air restrictor plate (see Figure 1 on page 5) is

supplied with this furnace and can be found in the plastic

bag containing these Installation Instructions and the

User

s Information Manual. This restrictor plate is to be

used only in non-direct vent applications. Attach a 90

°

elbow (not supplied) to the inlet coupler and install the

restrictor plate inside the elbow in all non-direct vent

installations (see Figures 13 and 14).

BURNER BOX

22.5° ELBOWS

STRAIGHT

INLET PIPE

G1D93BC

45,000 & 67,000 BTU/HR Units

Figure 12

Figure 14

Counterflow Non-Direct Vent

Vertical Venting

(Models G1D93BC & CG90CB Only)

The flue pipe screen (see Figure 1 on page 5) should be

installed at the termination of the flue pipe and is designed

to keep objects out of the flue pipe.

Prime the trap system by slowly pouring 1 cup of water

down the vent pipe. For horizontal venting, refer to Figure

13. For vertical venting, refer to Figure 14. The vent pipe

on horizontal runs must slope upward, away from the

furnace, at a minimum pitch of 1/4" per foot of run, to

prevent accumulation of condensate.

On initial start-up of the unit, some of the water used to

prime the trap system may run down into the combustion

blower and cause noise.

Figure 13

Counterflow Non-Direct Vent

Horizontal Venting

(Models G1D93BC & CG90CB Only)

(CL

O

SE

D)

DRA

N

H

O

L

E

THRU.

59.69/

56.64

THE VENT SYSTEM OF

THE FURNACE MUST BE
SELF-SUPPORTING AND

MUST NOT APPLY ANY

WEIGHT LOAD TO THE

COMBUSTION BLOWER.

CAUTION

RUN PITCH = 1/4

PER FOOT MIN.

"

SEE TABLE FOR

PROPER PIPE SIZE.

6

"

HEIGHT TO PROVIDE

12 CLEARANCE TO
MAX. SNOW LEVEL.

"

GROMMET

PVC COLLAR

VENT PIPE

CONDENSATE

COLLAR

COUPLER

INLET

THE INLET AIR
RESTRICTOR PLATE
MUST BE INSTALLED
ON ALL NON-DIRECT
VENT INSTALLATIONS.
ATTACH A 90° ELBOW
TO THE INLET COUPLER
AND INSTALL THE INLET
AIR RESTRICTOR PLATE
INSIDE THE ELBOW.

Содержание CG90CB

Страница 1: ...regulations or requirements take precedence over the general instructions in this manual IMPORTANT Do not store combustible materials including gasoline and other flammable vapors and liquids near the...

Страница 2: ...Supply and Piping beginning on page 15 of these instructions 7 Always install furnace to operate within the furnace s intended temperature rise range with a duct system which has an external static p...

Страница 3: ...in respect to the heat distribution system as much as practicable When installed in a utility room the door should be wide enough to allow the largest part of the furnace to enter or permit the repla...

Страница 4: ...nated Combustion Air Excessive exposure to contaminated combustion air will result in safety and performance related problems The recommended source of combustion air is outdoor air However the use of...

Страница 5: ...tside combustion air An inlet air restrictor plate see Figure 1 is supplied with this furnace and can be found in the plastic bag containing these Installation Instructions and the User s Information...

Страница 6: ...on that cannot be removed by stirring Refer to Table 2 for approved piping and fitting materials cement is recommended Metal or plastic strapping may be used for vent pipe hangers When making ABS join...

Страница 7: ...NR Not Recommended Minimum Pipe Diameter 112 000 125 000 BTU HR Models Minimum Pipe Diameter 90 000 100 000 BTU HR Models e p i P t n e V h t g n e L t f s w o b l E 0 9 f o r e b m u N 0 1 2 3 4 5 6...

Страница 8: ...r a e l C D e h t e v o b a d e t a c o l t i f f o s d e t a l i t n e v o t e c n a r a e l c l a c i t r e V e h t m o r f m c 1 6 t e e f 2 f o e c n a t s i d l a t n o z i r o h a n i h t i w l...

Страница 9: ...C D e h t e v o b a d e t a c o l t i f f o s d e t a l i t n e v o t e c n a r a e l c l a c i t r e V e h t m o r f m c 1 6 t e e f 2 f o e c n a t s i d l a t n o z i r o h a n i h t i w l a n i m...

Страница 10: ...n the same pressure zone There fore in horizontal venting applications they must be on the same side of the house within the parameters shown in Figure 6 On initial start up of the unit some of the wa...

Страница 11: ...8 For vertical venting refer to Figure 9 The vent pipe on horizontal runs must slope upward away from the furnace at a minimum pitch of 1 4 per foot of run to prevent accumulation of condensate Figur...

Страница 12: ...er to Figure 12 for detail of this inlet air assembly On initial start up of the unit some of the water used to prime the trap system may run down into the combustion blower and cause noise Do not cem...

Страница 13: ...Prime the trap system by slowly pouring 1 cup of water down the vent pipe For horizontal venting refer to Figure 13 For vertical venting refer to Figure 14 The vent pipe on horizontal runs must slope...

Страница 14: ...sed openings in the common venting system 2 Visually inspect the venting system for proper size and horizontal pitch as required in the National Fuel Gas Code ANSI Z223 1 NFPA 54 latest edition or the...

Страница 15: ...rnace A return air duct system is recommended If the unit is installed in a confined space or closet a return connection must be run full size to a location outside the closet The air duct in the clos...

Страница 16: ...ividual manual shutoff valve during any pressure testing of the gas supply piping system at test pressure equal to or less than 1 2 psig 3 5 kPa or 14 W C If the piping system is to be tested at press...

Страница 17: ...2 filter are supplied with the furnace Models designed for more than 1600 CFM nominal air delivery include two of each The filter rack is to be installed between the return air duct and the side of th...

Страница 18: ...onic Air Cleaner Terminals are provided on the blower control board for connection of a 120 volt electronic air cleaner The EAC terminal is energized whenever the thermostat is calling for heat coolin...

Страница 19: ...because some gas is heavier than air and will settle on the floor What to do if you smell gas Do not try to light any appliances Extinguish any open flame Do not touch any electric switch do not use a...

Страница 20: ...ay The call for cooling has priority over continuous fan operation while a call for heating has priority over both a call for cooling or continuous fan Ignition lockouts for any reason do not affect c...

Страница 21: ...t the regulator turn the adjusting screw s on the regulator clockwise to increase pressure and input coun terclockwise to decrease pressure and input Replace the barbed fitting and reconnect the hose...

Страница 22: ...a e H e u l a V t f U T B 3 d l o f i n a M e r u s s e r P C W n i g n i t a e H e u l a V t f U T B 3 d l o f i n a M e r u s s e r P C W n i 0 0 0 2 8 4 9 0 5 3 8 7 2 2 0 0 0 1 6 6 6 9 0 0 0 0 3 4...

Страница 23: ...cked or plugged the furnace will not operate properly MAINTENANCE Failure to follow the safety warnings exactly could result in dangerous operation serious injury death or property damage Improper ser...

Страница 24: ...ower housing assembly Blower wheel Blower motor Blower motor mount Blower motor capacitor Burner Group Gas manifold Main burner orifices Main burners Accessories ALPKT572 Natural Gas to Propane Conver...

Страница 25: ...emory A pushbutton switch is located on the control see Figure 22 on page 26 When the pushbutton switch is pressed and released the control flashes the stored fault codes The most recent fault code is...

Страница 26: ...45466K003 Page 26 Figure 22 Connection Diagram P N 45198 005...

Страница 27: ...45466K003 Page 27 Figure 23 Schematic Diagram P N 45198 005...

Отзывы: