The Load Shed utility determines how the loads in the room will
respond to a Load Shed command via BACnet.
L o a d S h e d M e n u
SHEDS ALL ROOM LOADS!
S h e d t o L e v e l :
< 6 5 >
T i m e o u t M i n u t e s :
< 3 0 >
M o d e :
< N o O v e r r i d e >
SEND DONE
Shed to Level
The maximum level the load will go to when it receives a Load
Shed command. If the load is currently at a higher level, it will
reduce to this amount. If it is currently at a lower level, it will
remain at that level. Once the load shed is relinquished, the load
will go to the level determined by the next highest priority. This
could be the setting of a switch such as a scene switch, or the
level set as part of a schedule.
Available values: 5% to 100%, in 5 % increments, and Load. If
set to Load, the load will use the individual Shed to Level that
can be set for a specific load. LMCS-100 software is required to
access that parameter.
Timeout Minutes
This limits the amount of time after the Load Shed occurs
before relinquishing the load shed. Available values are 5 to 250
minutes in 5 minute increments, and Off. If set to Off, the load
shed is not relinquished until a command is received via BACnet
to do so.
Mode
This parameter has three possible values:
•
No Override
– Initiates the load shed, but does not allow
users to adjust the lighting levels
•
Override
– Initiates the load shed, but allows users to
adjust the lighting levels
•
Disable
– Prevents the load from responding to the load
shed command.
Once you have edited the parameters as needed, choose
SEND
and press Select, then point at an IR receiver and press Select
again. To exit , press
DONE
.
Status
U t i l i t i e s M e n u
S m a r t W i r e
I d e n t i f y D e v i c e s
F o r c e S y s t e m i n t o P n G
R o o m M o d e
L o a d S h e d
S t a t u s
D o n e
A panel or bridge is required to use this option. It provides
status information on loads, groups, photosensors, and sensors
connected to the panel or bridge.
An additional screen containing status information specific to
panels is also available from the
Panel Setup
screen. See
.
Load Status
S t a t u s – P a n e l
L o a d S t a t u s
G r o u p S t a t u s
L i g h t L e v e l
O c c u p a n c y S e n s o r s
D o n e
This set of screens displays details about each load in the panel,
as well as any loads in connected room controllers.
Smart Wire
U t i l i t i e s M e n u
S m a r t W i r e
I d e n t i f y D e v i c e s
F o r c e S y s t e m i n t o P n G
R o o m M o d e
L o a d S h e d
S t a t u s
D o n e
S m a r t W i r e M e n u
S t a r t S m a r t W i r e
S t o p S m a r t W i r e
D o n e
The Smartwire feature is used to configure LMSW buttons and
DLM occupancy sensors to control relays in the LILM series
Lighting Integrator panel.
With
Start Smartwire
selected, point the LMCT-100-2 at the
switch or sensor to be programmed and press Select to enter
the Smartwire mode. Select Stop Smartwire and point at the
device to exit the Smartwire mode.
NOTE:
The LILM panels are no longer sold, so this option is for
legacy support only.
Identify Devices
U t i l i t i e s M e n u
S m a r t W i r e
I d e n t i f y D e v i c e s
F o r c e S y s t e m i n t o P n G
R o o m M o d e
L o a d S h e d
S t a t u s
D o n e
Identify Device 01-06
LMRC-102 0461385398
HW: 10 Year 14 Week
HW Version: 008
FW Version: 005.025
NEXT
PRIOR DONE
Identify Devices provides access to service information for
individual DLM devices in the room. Note that this feature only
works with DLM room devices shipped after January 2012.
The room controller (or panel) assigns a number to each device
when connection between devices is first established. The
NEXT
and
PRIOR
buttons will cycle through the devices in that
order. The number in the upper right corner shows the device
number and total number of devices. In the example above the
room controller is device 1 of 6 in the local network. The room
controller (or panel) will always be the first device.
Force System into PnG
U t i l i t i e s M e n u
S m a r t W i r e
I d e n t i f y D e v i c e s
F o r c e S y s t e m i n t o P n G
R o o m M o d e
L o a d S h e d
S t a t u s
D o n e
F o r c e S y s t e m i n t o P n G
I f y o u a r e s u r e y o u
w a n t t o f o r c e a P n G
P o i n t t o A N Y I R
e n a b l e d d e v i c e , a n d
P r e s s ‘ S e l e c t ’
Forcing a PnG will reset the room devices back to their original
Plug and Go states and the room will immediately initiate a fresh
Plug and Go sequence.
Room Mode
U t i l i t i e s M e n u
S m a r t W i r e
I d e n t i f y D e v i c e s
F o r c e S y s t e m i n t o P n G
R o o m M o d e
L o a d S h e d
S t a t u s
D o n e
S e t R o o m M o d e
S e l e c t e i t h e r N o r m a l
H o u r s o r A f t e r H o u r s
N o r m a l H r s
A f t e r H r s
Room Mode will force the mode of the room into the After Hours
or Normal Hours mode. Since sensor settings changed while in
After Hours mode will apply only when the room is in that state,
switching to After Hours mode will allow testing of the settings
when a room is usually in Normal Hours. Be sure to return the
room to the proper mode before exiting.
Load Shed
U t i l i t i e s M e n u
S m a r t W i r e
I d e n t i f y D e v i c e s
F o r c e S y s t e m i n t o P n G
R o o m M o d e
L o a d S h e d
S t a t u s
D o n e