LEGRAND Wattstopper LMCT-100-2 Скачать руководство пользователя страница 19

19

The top line of the screen shows the serial number of the panel.

Name

This is a label for the panel, useful when working with LMCS in 

a situation where multiple panels are used, to help more easily 

distinguish between the panels. Any numerals or letters can be 

used in naming the panel. By default, the name is the same as 

the serial number. Highlight the value and press Select to open a 

new screen, as shown above. 
Select 

ERASE

 if you want to clear all characters before entering 

a new name. If you have several bridges or panels with a similar 

name, for example Room 101 and Room 102, you can 

COPY

 

the name and then 

PASTE

 it when you configure the next 

bridge or panel. Select 

DONE 

to return to the 

Network Settings

 

screen.

Device ID

The device ID is a unique number, between 0 and 4194302, 

that identifies a device in a BACnet network. Every device in the 

network must have a different number. By default, it is set to the 

last six digits of the serial number, but can be changed if needed, 

for example, when required by an integrator, as part of a BAS. To 

change, highlight the value and press Select.

AutoSet MSTP MAC

The MS/TP MAC address is an additional identifier, used by the 

devices on the network to communicate with each other. It is a 

number between 0 and 127. It is important to understand the 

difference between the device ID and the MS/TP MAC Address. 

The Device ID is, in essence, a number that identifies “who” the 

devices is, while the MS/TP MAC address identifies its relative 

location in the group of BACnet devices.
In a BACnet network, all the devices pass a token to each other 

to determine which device has control of communication over 

the network. The MS/TP MAC address is used to “locate” other 

devices. When a device receives the token, it will take control 

of the communication and send messages to other devices as 

needed. It then passes the token to the device with the 

next 

highest

 MS/TP MAC address. In order to do this, it sends an “Are 

you there?” message on the MAC address one higher than its own. 

If it receives a response, it passes the token. If it does not receive 

a response, it tries again on the next highest number, continuing 

in this manner until it receives a response. This “Are you there?” 

message is referred to as a Poll For Master.

NOTE: 

In order to send and respond to this Poll For Master 

message, a device must be designated as a master 

device. Other devices (slave devices) on the network 

will not respond, and cannot take control of the 

communication.

While the Device ID is fixed and should not change, the  

MS/TP MAC address can change as devices come on or drop 

off the network. By default, with 

AutoSet MSTP MAC 

set to 

“Yes”, the panel or bridge will automatically assign an MS/TP 

MAC address, shown in the 

Auto MSTP MAC

 parameter. When 

the panel or bridge is powered up, it will check the network for 

other devices to determine if its current MAC address is being 

used by another device. If, not it will keep the same address, but 

if it is, and will assign an unused number between 32 and 127.
If you change 

AutoSet MSTP MAC 

to “No”, the parameter 

below changes to you 

Manual MSTP MAC

 and you can 

manually assign an MS/TP MAC address instead of having the 

panel or bridge automatically assign the number. This can be 

useful, especially in larger networks where response time is 

important. Since the Poll For Master message checks the next 

highest address number and then increments that number until it 

finds a device, having devices with gaps between numbers can 

increase latency. If you have 10 devices, numbered 0–9, you will 

have optimal performance since no time is wasted sending the 

Poll For Master message to an unused number. 

Baud Rate

The default rate is 38400, but can be changed. 

Max Master

This is another parameter that will cut down on latency. The 

value you set for this parameter is the highest number the LMCP 

will check when sending a Poll For Master message, before 

returning to 0.
So, in the previous example, where there are 10 devices 

numbered 0–9, if you set the Max Master to 9, it will never check 

addresses 10–127.

NOTE: 

You should be aware that devices connected over the 

DLM Local Network also have MAC addresses for 

communication purposes, but that MAC address is 

entirely separate from the MS/TP MAC address.

If you make any changes, highlight 

SEND

 and press Select. Once 

again, point the LMCT-100-2 at an infrared sensor and press 

Select. You return to the 

Global Network

  screen. Or, if you aren’t 

making any changes, highlight 

DONE

 and press Select to return.

Network Status

N e t w o r k   S t a t u s

 

DONE

L M    

0 6 0 3 9 8 1 2 1 0

N e t   S t a t u s :  

U n h e a l t h y

N e t   D e v i c e   C o u n t :  

< 0 >

The Network Status shows the communication “health” of the 

network and the number of devices currently found on the network.

Network Status

This will display as “Unhealthy” if it can’t find the BACnet 

network, or if devices on network drop off and then reappear 

while the panel or bridge is polling the network (indicating 

connection problems). If devices show up consistently, or if they 

disappear and do not show up again (which would indicate the 

device was disabled or disconnected), the status will display as 

“Healthy”.

Net Device Count

This displays the number of devices on the BACnet network.

UTILITIES

A d j u s t   L i g h t   L e v e l

G l o b a l   N e t w o r k

U t i l i t i e s

P a n e l   S e t u p

G r o u p   S e t u p

                            M o r e

=

B AT

Utilities provides access to several advanced features of DLM. 

•  The Smartwire process allows binding buttons and sensors 

to relays in a lighting control panel. 

•  Identify Devices is a means to extract service information 

from room devices. 

•  Forcing PnG restores the room to its original plug and go 

state.

•  Room Mode allows the room to be forced into the after 

hours or normal hours mode for testing.

•  Load Shed allows you to customize how loads respond to a 

Load Shed command via BACnet.

•  Status provides several options for viewing the status of 

different devices in the DLM network

Содержание Wattstopper LMCT-100-2

Страница 1: ...7 Bind 7 Next 7 Exit 7 Daylighting Configuration 7 Specific Photosensor 7 Search Photosensor 7 Zone Setup LMLS400 LMLS 600 Only 8 Zone Setup LMLS 500 Only 9 Calibration LMLS 400 Only 10 Calibration LMLS 500 Only 11 Calibration LMLS 600 Only 11 Zone Settings LMLS 400 Only 12 Zone Settings LMLS 500 Only 13 Zone Settings LMLS 600 Only 13 Switched Bi Level or Tri Level 13 Advanced Settings LMLS 400 on...

Страница 2: ...l Programming 23 Schedules 23 Holidays 24 Panel Status 24 Group Setup 24 Group Loads 24 Using the Smartwire Feature 25 Defining Custom Group Parameters 25 Group Occupancy Sensor Settings 26 Group Dark Light Events 26 Troubleshooting 27 LMLS 400 LMLS 500 Daylighting Control 27 Appendix Updating the Firmware in the LMCT 100 2 29 Installing Firmware in the LMCT 100 2 29 ...

Страница 3: ... can change any of the DLM occupancy sensor parameters such as sensitivity time delay and more With the LMCT 100 2 you can also change load configurations without any new wiring The LMCT 100 2 can change dimming system options such as scene assignments fade rates and other options not available through the standard user interface Additionally the LMCT 100 2 can be used for initial configuration of...

Страница 4: ...on in the sensor Ultrasonic sensors only Trigger Retrigger Mode Dual Tech Sensors only Trigger Indicates whether to use PIR Ultrasonic Either or Both technologies for initial detection of occupancy For Either the sensor will register occupancy if either of the two technologies senses movement whereas for Both both technologies must detect movement Retrigger Indicates whether to use PIR Ultrasonic ...

Страница 5: ... Yes NH Delay 1 Min AH Delay 2 Min NEXT PRIOR SEND DONE After selecting the Analog Occ Sensors option point the LMCT 100 2 at any IR enabled device in the room There must be an LMIO 201 connected with an analog sensor wired correctly to the LMIO 201 or you will receive an error If the LMIO 201 is connected and wired properly and you still receive an error press the Config button on the LMIO 201 Th...

Страница 6: ...irst Load Config PnL Load 1 Operation Auto On Blink Disable Load Type NonDim SEND BIND NEXT EXIT Push to highlight NEXT and push the SELECT button to turn ON the next load and view its settings Once the Load is selected you can bind a button to the load by pressing that button Use the BIND option on the screen to bind sensors to a load this prevents having to access the button on a sensor placed i...

Страница 7: ...rs in high bay applications it is important to stand directly underneath the sensor with the LMCT 100 2 held in a vertical orientation pointed at the bottom of the sensor In some cases direct communications between the LMCT 100 2 and the LMLS 600 may be difficult to achieve due to interference from very high ambient light when looking up from direct sunlight high intensity fluorescent fixtures e g...

Страница 8: ...ing 2 load circuits Load 1 OFF Off 0 Med 50 Max 100 Load 2 OFF Load 1 ON Load 2 OFF Load 1 ON Load 2 ON Tri Level Tri level mode provides four light levels within the daylighting zone controlled by the photosensor by using 2 load circuits Off 0 Low 33 High 66 Max 100 Load 1 OFF Load 2 OFF Load 1 OFF Load 2 ON Load 1 ON Load 2 OFF Load 1 ON Load 2 ON Dimmed Dimmed mode provides continuous dimming w...

Страница 9: ... Control Mode Zone Setup LMLS 5 0 0 Number of Zo nes 3 CONT IN U E Press Left Right arrow to select the number of Zones 1 2 or 3 Point to A ny IR enabled d evi ce o n the n et w o rk Press Sel ect Choose the numb er o f Daylight i ng Zo nes Zone Setup LMLS 500 Zone 1 Bi Level Zone 2 Switched Zone 3 Tri Level CONTINUE Pick a control type for ALL Zones Zone Setup LMLS 5 0 0 Bi L evel NEXT PRIOR D ON...

Страница 10: ...changes based on the Operating Mode Switched Bi Level and Tri Level Choose a reference location within the daylighting zone that is most likely to have the lowest light level when day lit and is located farthest from the window Calibrating LMLS 400 Desired Light Level at the workplane 50fc Actual Light Level at at the workplane 35fc SEND To set the On and Off Setpoints automatically to best match ...

Страница 11: ...s the skylight area remain free of any obstructions and that no changes occur including human foot traffic within the cone of view of the closed loop sensor Please clear the area before starting the Automatic Calibration and wait for the calibration completion when the blue LED stops flashing once every 4 seconds before reentering the area Daylighting Confi g LMLS 400 Night Setup Night Setpoint Sa...

Страница 12: ... a t io n Zone Se t t in g s Adva n c e d Se t t in g s Con t ro l Mo d e Zone Settings When Zone Settings is selected one of two screens is displayed depending on the Operation Mode of the device Switched Bi Level or Tri Level or Dimmed Switched Bi Level or Tri Level Daylighting LMLS 400 Bi Level SEND ON Setpoint OFF Setpoint ON Time Delay OFF Time Delay 7 5fc 11fc 20sec 10min This heading differ...

Страница 13: ... 3 min to 30 min Send To send the changed settings to the LMLS 500 select SEND point the LMCT 100 2 at an IR enabled device and press Select Dimmed Daylighting LMLS 500 SEND NEXT ZONE DONE Setpoint Ramp Up Ramp Down Cut Off Delay 50fc 20 sec 2 sec 10min Zone 1 Dimmed Setpoint The desired light level at the task per zone To determine the correct dimming level for any given photocell reading it calc...

Страница 14: ... details However the LMLS 500 has a NEXT option Select that option to display the following screen Daylighting LMLS 500 PRIOR DR Z1 300 fc 300 fc DR Z2 300 fc 300 fc DR Z3 300 fc 300 fc EL Z1 300 0 fc EL Z2 300 0 fc EL Z3 300 0 fc This screen displays the current readings of the Daylight Ratio DR and Electric Light contribution EL for each zone OFF Setpoint The target illuminance level above which...

Страница 15: ... of all of the controlled electric lights as seen in the closed loop down looking sensor Daylight Ratio Shows the latest average ratio between the daylight contribution seen in the closed loop down looking sensor and that measured by the open loop up looking sensor Force Open Loop When set to Yes this parameter causes the sensor to always reference the Open Loop sensor during control operations an...

Страница 16: ... loads bound to the button Any bound load ON LED ON Bound loads OFF LED OFF Bound loads ON LED ON ToggleNT mode is intended for use when the button is assigned to a Group For details on this mode see the section on Group Button Parameters on page 17 Fade On Fade Off Fade On and Fade Off determines the time that it takes for loads bound to this button to reach the target level The fade time default...

Страница 17: ...t level to a scene button by pressing and holding the button for 7 seconds If set to Yes this feature is locked and the user can t change the scene setting Fade On Fade Off Fade On and Fade Off determines how much time it takes for the loads to reach their target levels when this button is pressed The fade time defaults are Use Load s By default all loads in a scene carry a two second ON and OFF f...

Страница 18: ...or fade the load turns ON or OFF The value options are 1 25 51 75 or 100 The default is 51 NOTE For a room controller that does not support dimming the Type will not be selectable and will specify a switched load only Send Next Prior These options function the same as with dimming loads ADJUST LIGHT LEVEL To access the Adjust Light Level option select More when on the initial Home screen to view t...

Страница 19: ...for other devices to determine if its current MAC address is being used by another device If not it will keep the same address but if it is and will assign an unused number between 32 and 127 If you change AutoSet MSTP MAC to No the parameter below changes to you Manual MSTP MAC and you can manually assign an MS TP MAC address instead of having the panel or bridge automatically assign the number T...

Страница 20: ...ify Devices Force System into PnG Room Mode Load Shed Status Done SmartWire Menu Start SmartWire Stop SmartWire Done The Smartwire feature is used to configure LMSW buttons and DLM occupancy sensors to control relays in the LILM series Lighting Integrator panel With Start Smartwire selected point the LMCT 100 2 at the switch or sensor to be programmed and press Select to enter the Smartwire mode S...

Страница 21: ...lay countdown will start When the countdown reaches 0 the blink function re occurs NOTE Blink does not apply when transitioning from After Hours to Normal Hours TDelay NH None TDelay AH 120 min NH AH Tur n Off AH NH Do Nothing Load 2 Properties 2 NEXT PRIOR DONE TDelay NH If a load is commanded to turn ON when the schedule switches to Normal Hours the load will automatically turn OFF after the tim...

Страница 22: ...rn to the Status screen Light Level Li ght L evel 1 f c 301 1 of 2 Level MAC 0373303229 NEXT PRIOR DONE This screen displays the current light level in foot candles registered by an LMIO 301 with an attached photosensor The top line of the display shows the number of LMIO 301s connected to the network The display shows the light level of a single device The second line shows the serial number MAC ...

Страница 23: ... 24 NOTE While bridges can store group data schedules are specific to panels So you can set up groups within a panel and a bridge and then have the panel send schedule events to both its internal groups and an external bridge Schedules 603981210 Schedules Holidays Panel Programming Select Schedules point the LMCT 100 2 at the infrared sensor on the LMRD board and press Select to open the Program S...

Страница 24: ...e SensAutomatic Group Setup LOADS CUSTOM DONE DELETE SEND Group Select the group number Each panel has 99 memory locations for storing group parameters and each bridge has 16 locations Type Select one of the predefined macros see below or select Custom to define the group behavior parameters Next Select LOADS Point the LMCT 100 2 at the infrared sensor on the LMRD board and press Select to open th...

Страница 25: ... is available for bridges as well as panels it is less practical for bridges as it requires you to have easy access to each room controller so you can press the relay switches for individual loads on the room controller Defining Custom Group Parameters If you select a value of Custom for Type on the Group Setup screen then you must select the CUSTOM option on that screen which opens the Group x Cu...

Страница 26: ... Select You return to the Group Setup screen Important You must SEND the settings for an event before selecting another event or those settings will be lost Group Dark Light Events Group Loads Group Occ Sensors Group Dark Light DONE Group Setup LMBC On this set of screens you assign individual dark light events based on sunrise sunset settings or on dark light triggers from a photo sensor connecte...

Страница 27: ...Normal to resume daylighting operation time value of 20 minutes the Dark event will trigger 10 minutes before sunset and the Light event will trigger 10 minutes after sunrise The LMCP User Guide contains a chart shows this example in greater detail Finally you assign a Group for this event to control the relays belonging to that group LMIO 301 Events Contro ller LMIO 301 1 Dark L N Z Li ght Tu r n...

Страница 28: ...ation If the latter complete the commissioning operation first otherwise use a wall switch to turn off the controlled loads to terminate the override Explanation If the blink is faster one flash every second the photosensor is in Test Mode or Demo Mode 1 Test Mode will cancel automatically after five minutes 2 Alternatively it can be turned off by selecting the Control Mode menu from the LMLS 400 ...

Страница 29: ... not be able to upgrade the firmware but there will be no error message saying that the driver is missing Installing Firmware in the LMCT 100 2 Wattstopper support can provide information how to download a copy of the most recent firmware Once that file is saved on your computer take the following steps to install the file 1 Remover the battery cover from the LMCT 100 2 to expose the micro USB jac...

Страница 30: ...lié à la perte de propriété de revenus ou de profits ou aux coûts d enlèvement d installation ou de réinstallation Wattstopper garantiza que sus productos están libres de defectos en materiales y mano de obra por un período de cinco 5 años No existen obligaciones ni responsabilidades por parte de Wattstopper por daños consecuentes que se deriven o estén relacionados con el uso o el rendimiento de ...

Отзывы: