5
SAVED CONFIGURATIONS
Use this feature to view the settings for any previously saved
configurations and send those settings to a sensor. Using this
feature, you can quickly configure multiple sensors with the
same settings.
S e n s o r C o n fi g u r a t i o n
C u r r e n t S e t t i n g s
Te s t M o d e
S a v e d C o n fi g u r a t i o n s
A n a l o g O c c S e n s o r
Press
Select
Press
Select
Press the
Down Arrow for
Saved Configurations
S a v e d S e n s o r C o n fi g s
P i c k D T S a v e d C o n fi g
< 1 2 0 / 9 0 / 7 0 / W >
R E C A L L D E L E T E
D e l e t e d S e n s o r C o n fi g
i n M e m o r y S l o t 2
P r e s s ‘ S e l e c t ’
P o i n t t o d e s i r e d Ty p e
o f O c c u p a n c y S e n s o r
t o r e t r i e v e s a v e d
c o n fi g u r a t i o n s f o r
t h a t s e n s o r t y p e
P r e s s ‘ S e l e c t ’
Press
Select
Press
Select
To Review the Config
Settings Select
RECALL:
Press
Select
Press
Select
To Delete the Saved
Config Select
DELETE:
Press the
Right or
Left Arrow
to view other
Saved Configs
S a v e d S e n s o r C o n fi g s
P i c k D T S a v e d C o n fi g
< 2 5 / 8 0 / 7 0 >
R E C A L L
D E L E T E
S a v e d S e n s o r C o n fi g s
P i c k D T S a v e d C o n fi g
< 2 5 / 8 0 / 7 0 >
R E C A L L
D E L E T E
Dual Sensor Config
Time Delay:
<5 min>
PIR Sens:
<80%>
US Sens:
<70%>
Trigger :
<PIR & US>
Retrigger:
<PIR or US>
Walkthru:
<Off>
SEND
SAVE
Press
Select
Press the
Down Arrow
for SAVE
Memory
Slot Number
(up to 9 per
sensor type)
Up to 4 enabled settings, e.g.:
20....Time Delay minutes
90....% PIR Sensitivity
70....% US Sensitivity
W...Walkthrough Enabled
S e n s o r C o n fi g u r a t i o n
L o a d C o n fi g ( P n L )
D a y l i g h t i n g C o n fi g
B u t t o n C o n fi g u r a t i o n
D i m m i n g C o n fi g u r a t i o n
M o r e
=
B AT
NOTE:
If no saved configurations exist, you will see:
No Sensor Configurations exist, Press ‘Select’.
CONFIGURING ANALOG SENSORS
This option is used if you have an LMIO-201 connected to an
analog sensor, which allows limited control of the analog sensor
over DLM.
S e n s o r C o n fi g u r a t i o n
C u r r e n t S e t t i n g s
Te s t M o d e
S a v e d C o n fi g u r a t i o n s
A n a l o g O c c S e n s o r
LMIO-201
0188743930
Sensor is
Occupied
Sensor in
NormalHours
Load Tracking:
<Yes>
Follows AH:
<Yes>
NH Delay:
<1 Min>
AH Delay:
<2 Min>
NEXT PRIOR SEND DONE
After selecting the
Analog Occ Sensors
, option, point the
LMCT-100-2 at any IR enabled device in the room. There
must be an LMIO-201 connected with an analog sensor wired
correctly to the LMIO-201, or you will receive an error. If the
LMIO-201 is connected and wired properly and you still receive
an error, press the Config button on the LMIO-201. This will
cause the LMIO-201 to join the local network again. Then try
selecting the option again.
Once connection is established, the
LMIO-201
screen is displayed.
The top line shows the serial number of the LMIO-201.
Sensor Testing – Individual Sensor
Use this option to put an individual sensor into test mode. After
selecting
Individual Sensor
, point the LMCT-100-2 at that
sensor and press Select
NOTE:
The screenshots in this section show a Dual Technology
Sensor. For Ultrasonic or PIR sensors, only the appropriate
parameters for that particular sensors are displayed.
When testing an individual sensor, the serial number of that
sensor is displayed on the second line of the screen.
Adjusting Sensitivity during Test
DT Sensor Test
(0171986806)
PIR Sens:
<90%>
US Sens:
<70%>
Detection :
<PIR Only>
SEND RECEIVE EXIT
You can adjust sensitivity values while inside Test Mode. (The
new values must be sent to the sensor before they take effect.)
PIR Sens
– Passive Infrared sensitivity
US Sens
– Ultrasonic sensitivity
Values are 0 to 100%, in 10% increments.
Detection Criteria (Dual Technology Sensors only)
You can select to test one or the other technology, or both
technologies together. Available values: “PIR”, “US”, “PIR or
US”, “PIR & US”.
Send
If you change sensitivity or detection values, you must select
Send before they take effect. After the configuration is sent
press Select to return to the test menu.
Receive
Retrieves settings from the sensor so you can view or modify
them for further testing.
Exit
Exits test mode
Sensor Testing – All Sensors on Bus
When you select “All Sensors on bus”, you can test the selected
sensor along with other sensors on the DLM Local Network
(bus) to understand the coverage in the entire room.