22
Press
Select
G r o u p S t a t u s
G r o u p :
< 1 >
N E X T D O N E
Select the
Group
number that you want to display, then select
NEXT
. Point the LMCT-100-2 at any IR enabled device and
press Select.
L o a d 5 P a r m s N o t S a m e
0 1 1 1 .0
1
. . . . . 1 0
1 1 1 1 . . . . . . . 1 2 0
2 1 . . 1 0 1 . . . . . 3 0
3 1 . . . . . . . . . . 4 0
4 1 . . . . . . . . . . 5 0
5 1 . . . . . . . . . . 6 0
G r o u p 1 S t a t u s M i x e d
This screen indicates which loads are assigned to the group,
along with the on/off status of each load. A value of “1” indicates
it is ON. A value of “0” indicates it is OFF. A value of “.” indicates
the load is not assigned to the group.
On the top line, the
Status
will display “Off” if all assigned loads
are off, “100%” if all loads are on and there is no dimming, and
“Mixed” if some loads are on and others are off. If all loads in
the group dim and are set to the same dimming amount, it will
display that amount.
Move the cursor to highlight a specific load. If you scroll down
below the line for 51–60, you will see loads 61–64.
The load number will display in the second line. The
Parms
parameter will say either “Same” if the load parameters match
the group parameters, or “Not Same” if there is a difference.
To view the difference, press Select to open the
Actual Load x
Parms
1
screen.
B l i n k :
5 m i n
T D e l a y N H :
N o n e
T D e l a y A H :
1 2 0 m i n
N H – > A H :
Tu r n O f f
A H – > N H :
Tu r n O n
A c t u a l L o a d 5 P a r m s 1
MORE
GROUP PARMS
DONE
S e n s o r B e h a v i o r
A H :
M a n O n / A u t o O f f
N H :
A u t o O n / O f f
A c t u a l L o a d 5 P a r m s 2
MORE
GROUP PARMS
DONE
Selecting
MORE
toggles between the two screens of parameters.
The screens display the values of the parameters assigned to
the individual load. These parameters are also found on the Load
Status screens. See the previous section for a description of each.
To compare the values on this screen with the values for the
group, select
GROUP PARMS
.
B l i n k :
1 0 m i n
T D e l a y N H :
N o n e
T D e l a y A H :
1 2 0 m i n
N H – > A H :
Tu r n O f f
A H – > N H :
Tu r n O n
G r o u p L o a d 5 P a r m s 1
MORE
LOAD PARMS
DONE
S e n s o r B e h a v i o r
A H :
M a n O n / A u t o O f f
N H :
A u t o O n / O f f
G r o u p L o a d 5 P a r m s 2
MORE
LOAD PARMS
DONE
These screens display the values of the parameters assigned to
the group.
In this example, if you compare the Blink parameter to the one
on the Actual Load screen, you will see the group value is 10
minutes, while the individual load is 5 minutes.
Select
LOAD PARMS
if you need to view the load parameters
again. Once you finish comparing the values, select
DONE
to
return to the
Status
screen.
Light Level
L i g h t L e v e l :
1 f c
3 0 1 1 o f 2 L e v e l
M A C : 0 3 7 3 3 0 3 2 2 9
NEXT
PRIOR DONE
This screen displays the current light level, in foot candles,
registered by an LMIO-301 with an attached photosensor.
The top line of the display shows the number of LMIO-301s
connected to the network. The display shows the light level of a
single device. The second line shows the serial number (
MAC
address) of the currently displayed device.
Select
NEXT
to view the light level of another photosensor. Or
select
DONE
to return to the
Status
screen.
Occupancy Sensor Status
S t a t u s :
O n l i n e
S t a t e :
O c c u p i e d
L o a d Tr a c k i n g :
Ye s
O c c S e n 1 o f 4 S t a t
M A C : 0 2 0 9 7 1 5 2 0 4
NEXT
PRIOR DONE
This screen display current values of occupancy sensors
attached to the network.
The top line of the display shows the number of occupancy
sensors connected to the network. The display shows the values
for a single occupancy sensor. The second line shows the serial
number (
MAC
address) of the currently displayed device.
Status
This indicates whether the sensor is currently found on the
network. (When a sensor is connected, it is stored in memory
until the panel is reset. So, if the sensor is disconnected and the
panel has not been reset, the status will display “Offline”.)
State
This indicates whether the sensor currently is set as occupied or
unoccupied.
Load Tracking
If set to “Yes”, loads bound to the sensor will respond, based on the
programming settings for the sensor and group. If set to “No”, then
the loads will not respond to the sensor. This is used in situations
where the panel is connected to a BAS or other BACnet device
and you want to use the sensor to monitor occupancy/vacancy for
purposes other than turning loads on or off.
Select
NEXT
to view the values of additional sensors. Or select
DONE
to return to the
Status
screen.
PANEL SETUP
This option provides access to a number of sub-menus used for
setup of the LMCP panel and the LMZC-301 Zone Controller.
A d j u s t L i g h t L e v e l
G l o b a l N e t w o r k
U t i l i t i e s
P a n e l S e t u p
G r o u p S e t u p
M o r e
=
B AT
Location Settings
L o c a t i o n S e t t i n g s
D a t e a n d T i m e
P a n e l P r o g r a m m i n g
P a n e l S t a t u s
P a n e l S e t u p
L o c a t i o n S e t u p
DONE
SEND
S t a t e :
R h o d e I s l a n d
C i t y :
N e w p o r t
L a t i t u d e :
4 1 N
L o n g i t u d e :
7 1 W
H o u r s B e h i n d G M T 5
Setting the panel location provides sunrise/sunset information
to the panel, for use when you set a schedule according to an
astronomical clock.
NOTE:
The LMCT-100-2 has a limited number of locations to
choose from. For a much more extensive list, use the
LMCS-100 software to access this feature.