7
•
HiLum
– Applies to LMRC-22x controllers only. This is used
for 2 wire dimming ballasts such as the Phillips Advance X.
These ballasts can’t use a straight line voltage reduction
because at some point there isn’t enough voltage to power
the electronics in the ballast itself. This value provides a
smaller range of voltage change, resulting in an output from
100% to minimum %.
•
MarkX
– Applies to LMRC-22x controllers only. This used
for 3 wire dimming ballasts that have both a dimming hot
wire and a switched hot wire, such as the HiLume fixtures.
Pulsed Load Menu
Pulsed Load Menu
Load:
1
Load Type:
Pulsed
Pulse Seconds:
<0>
DONE
This menu displays when “Pulsed’ is selected for the
Load Type
and
Select
is pressed. Change the
Pulse Seconds
parameter
to set the length of the pulse. Then select DONE to return to the
Load Config <PnL> screen.
Send
To update the load parameters in the room controller, select
SEND
, point the LMCT-100-2 at any IR enabled device, and
press Select again.
New settings are sent to the selected load. Wait 5–6 seconds
for the message to clear. You can then select another function
(BIND, NEXT, EXIT). To instantly end load configuration press
the HOME key.
Bind
This feature binds an occupancy sensor to the selected load.
After selecting
BIND
, point the LMCT-100-2 to a specific
occupancy sensor, and press Select.
You can repeat this process to bind more than one sensor to the
same load.
Next
Select another load. When NEXT is selected, Load 1 turns OFF
and Load 2 turns ON.
Exit
This ends the configuration function and exits PnL.
DAYLIGHTING CONFIGURATION
Daylighting Config allows you to setup daylighting and operation
parameters specific to the type of sensor that is communicating
with the LMCT-100. Different menu options are displayed
depending upon the device.
Once you select
Daylighting Config
, you select the model of
the sensor you want to configure.
D a y l i g h t i n g C o n fi g
L M L S - 4 0 0
L M L S - 5 0 0
L M L S - 6 0 0
S e n s o r C o n fi g u r a t i o n
L o a d C o n fi g ( P n L )
D a y l i g h t i n g C o n fi g
B u t t o n C o n fi g u r a t i o n
D i m m i n g C o n fi g u r a t i o n
M o r e
=
B AT
Note regarding IR communication with the LMLS-600
:
Because of the great mounting heights of skylight sensors in
high-bay applications, it is important to stand directly underneath
the sensor, with the LMCT-100-2 held in a vertical orientation
pointed at the bottom of the sensor.
In some cases, direct communications between the
LMCT-100-2 and the LMLS-600 may be difficult to achieve
due to interference from very high ambient light when looking
up, from direct sunlight, high intensity fluorescent fixtures
(e.g.,T5HO) mounted close to the sensor, as well as some other
intense light sources. In these cases, communications can
be established with the sensor by aiming the LMCT-100-2 at
another DLM product in the room with a visible IR window (e.g.,
a wall switch or occupancy sensor).
Refer to the specific LMLS installation instructions for details
about daylighting setup and operation of each of the models
listed below.
Once you select a particular model, you have two choices:
Specific Photosensor
or
Search Photosensor
.
Specific Photosensor
Use this function if you are pointing the LMCT-100-2 directly at a
specific photosensor.
Press
Select
D a y l i g h t i n g L M L S - 4 0 0
S p e c i fi c P h o t o s e n s o r
S e a r c h P h o t o s e n s o r s
P o i n t t o t h e d e s i r e d
P h o t o s e n s o r a n d
p r e s s ‘ S e l e c t ’
Point and
Press Select
Serial number will be different
for each LMLS-400
L M L S - 4 0 0 0 2 9 3 7 2 4 9 0 9
Z o n e S e t u p
C a l i b r a t i o n
Z o n e S e t t i n g s
A d v a n c e d S e t t i n g s
C o n t r o l M o d e
Search Photosensor
The Search Photosensor function allows you to identify which
LMLS device will be commissioned. After enabling and pointing
the LMCT-100-2 to any DLM device, a list of all photosensors
of the previously selected model
in the DLM Local Network
appears on the screen. Each DLM device has its own serial
number. One advantage to this method is that you can point the
LMCT-100-2 at a switch or other easily accessible DLM device.
D a y l i g h t i n g L M L S - 4 0 0
S p e c i fi c P h o t o s e n s o r
S e a r c h P h o t o s e n s o r s
P o i n t t o A n y I R
e n a b l e d d e v i c e o n
t h e n e t w o r k
P r e s s ‘ S e l e c t ’
Point and
Press Select
Press
Select
Choose
Search
Photsensors
D a y l i g h t i n g L M L S - 4 0 0
‘ S e l e c t ’ a d e v i c e I D
0 2 9 3 7 2 4 9 0 9
Press
Select
Choose
Desired
Photsensor
P o i n t t o A n y I R
e n a b l e d d e v i c e o n
t h e n e t w o r k
P r e s s ‘ S e l e c t ’
Point and
Press Select
LMLS-400 Daylighting Menu
Serial number will be different
for each LMLS-400
L M L S - 4 0 0 0 2 9 3 7 2 4 9 0 9
Z o n e S e t u p
C a l i b r a t i o n
Z o n e S e t t i n g s
A d v a n c e d S e t t i n g s
C o n t r o l M o d e