PRO1 Sentry Switched DC PDU
67 of 211
Outlet State/Control State Descriptions
The following table shows the differences between outlet state and control state
•
The
outlet state
is the current operating state of the outlet.
•
The
control state
is the last user-issued control action on the outlet.
Outlet State
Control State
Description
On
On
Outlet is on.
Off
Off
Outlet is off.
Off
Pend On
Outlet is off and about to turn on in response to a sequence
timer.
Off
Reboot
Outlet is off and a Reboot action has been initiated.
On
Idle On
A restart has occurred
–
last control state has been
maintained.
On
Idle Off
A restart has occurred
–
last control state has been
maintained.
On
Wake On
A power-loss has occurred
–
wakeup state has been applied.
Off
Wake Off
A power-loss has occurred
–
wakeup state has been applied.
On/Wait
Off
Outlet state in transition
–
re-query of outlet status required.
Off/Wait
On
Outlet state in transition
–
re-query of outlet status required.
On/Error
(varies)
Error state
–
outlet should be off but current is sensed at the
outlet.
Off/Error
(varies)
Error state
–
outlet should be on but no current is sensed at
the outlet.
Off/Fuse
On
Outlet should be on but a blown fuse has been detected.
On/Fuse
On
Outlet should be on but a blown fuse has been detected
downstream
No Comm
(varies)
Communication to the outlet has been lost
–
control state will
be applied when communication is re-established.
Содержание 48DCWC-04-2X100-D0NB
Страница 1: ......
Страница 2: ...Sentry Switched DC PDU 2 of 211...
Страница 10: ...Sentry Switched DC PDU 10 of 211 Mounting Bracket The 48DCWC 16 2X100 A0 mounting bracket...
Страница 12: ...Sentry Switched DC PDU 12 of 211 Mounting Bracket The 48DCWC 04 2X100 D0NB mounting bracket...
Страница 14: ...Sentry Switched DC PDU 14 of 211 Mounting Bracket The 48DCWC 12 2X100 A1NB mounting bracket...
Страница 16: ...Sentry Switched DC PDU 16 of 211 Mounting Bracket The 48DCWC 08 2X100 B0NB mounting bracket...
Страница 18: ...Sentry Switched DC PDU 18 of 211 Mounting Bracket The 48DCWC 04 4X070 D0NB mounting bracket...
Страница 20: ...Sentry Switched DC PDU 20 of 211 Mounting Bracket The 48DCWC 04 4X125 E0NB mounting bracket...
Страница 22: ...Sentry Switched DC PDU 22 of 211 Mounting Bracket The 48DCWC 10 2X300 E0NB mounting bracket...