PRO1 Sentry Switched DC PDU
104 of 211
Network > LLDP
The
LLDP
page provides configuration options for the Link Layer Discovery Protocol (LLDP). These options enable
LLDP to standardize relationships across devices in a multi-vendor network so that device information can be
advertised directly to connected peer-neighbor devices.
To configure LLDP:
1.
Select the checkbox to enable LLDP.
2.
Type the Transmit Interval. This time interval is how often the PDU advertises itself to any LLDP receivers
on the network. The PDU acts as an LLDP transmitter only.
3.
Click Apply.
The LLDP packet transmits the Chassis ID (the MAC address), the Port ID ("eth0"), the time to live (the transmit
interval times four [by definition]).
Also transmitted is the system name (the SNMP system name or the system name in "show SNMP"), and the
system description (the STI production description [for example, "Sentry Switched CDU"]).
The table below shows the possible values included in the LLDP packet:
Type Length Values (TLV)
TLV Type
TLV Name
Usage in LLDPDU
0
End of LLDPDU
Mandatory
1
Chassis ID
Mandatory
2
Port ID
Mandatory
3
Time To Live
Mandatory
4
Port Description
Optional
5
System Name
Optional
6
System Description
Optional
7
System Capabilities
Optional
8
Management Address
Optional
9
–126
Reserved
Optional
127
Custom TLVs
Optional
Содержание 48DCWC-04-2X100-D0NB
Страница 1: ......
Страница 2: ...Sentry Switched DC PDU 2 of 211...
Страница 10: ...Sentry Switched DC PDU 10 of 211 Mounting Bracket The 48DCWC 16 2X100 A0 mounting bracket...
Страница 12: ...Sentry Switched DC PDU 12 of 211 Mounting Bracket The 48DCWC 04 2X100 D0NB mounting bracket...
Страница 14: ...Sentry Switched DC PDU 14 of 211 Mounting Bracket The 48DCWC 12 2X100 A1NB mounting bracket...
Страница 16: ...Sentry Switched DC PDU 16 of 211 Mounting Bracket The 48DCWC 08 2X100 B0NB mounting bracket...
Страница 18: ...Sentry Switched DC PDU 18 of 211 Mounting Bracket The 48DCWC 04 4X070 D0NB mounting bracket...
Страница 20: ...Sentry Switched DC PDU 20 of 211 Mounting Bracket The 48DCWC 04 4X125 E0NB mounting bracket...
Страница 22: ...Sentry Switched DC PDU 22 of 211 Mounting Bracket The 48DCWC 10 2X300 E0NB mounting bracket...