Monitoring > Phases
The
Phases
page reports the current
nominal voltage, state, and status of the PDU’s phases.
What to look for:
The phase status, should be Normal.
The phase voltage graph displays a blinking warning (yellow) when the total input load on an infeed exceeds the
user-defined set threshold. If an overload occurs, a blinking error condition (red) is displayed.
The unit continues to display yellow and red states until the condition changes or the issue has been resolved. The
same color-coding applies to the phase power factor graph if the threshold is exceeded.
The default input feed high load threshold is 80% of the input feed maximum load capacity.
Phase voltage and power factor thresholds are user-defined at