81 of 211
Configuring Outlet Current Thresholds
1.
Click the Outlet Current Thresholds link at the bottom of the Outlets page:
2.
The configuration page displays:
To set outlet current thresholds:
1.
Provide threshold hysteresis between event state and recovery (A). the range is 0.0-10.0A; the default is
1.0A.
2.
Set the low/high alarm and low/high warning threshold values (A) for outlet current load. The range is min
0.0A; max is max current shown in the
show outlets
command.
3.
Click
Apply
.